1/246
Looks like no tags are added yet.
What is the minimum blowdown for a spring loaded safety valve as a percent of the set pressure?
10% of the set pressure
How are Main Steam pressure gages tested?
With an Inspector's gage
Which code governs plumbing installations?
The NYC Plumbing Code
When are anchorages or guides inspected?
Annually
How many brass washout plugs does a miniature boiler have?
3 brass washout plugs, 1 inch in size
How often are HP piping expansion joints inspected?
Weekly
How long should a hydronic system be pressure tested?
2 hours at no less than 100 PSIG
How is a gage protected from excessive pressure?
A shut-off cock
Who is authorized to witness a test on a gas piping system?
A Plumbing Inspector, Architect, Licensed PE, Master Plumber, or an agency approved by the D.O.B
How should a remote disconnect be labeled?
Remote control for burner
When is a fusible plug not required on a boiler?
Boilers over 200 PSIG
When must a power boiler with a MAWP over 400 PSI be tested?
Pressure tested annually
What does a design plan for a boiler and application contain?
Size, location, operating pressure and temperature of the pressure vessel, and the type and specification of the PRV
Who maintains copies of certified welder qualification reports?
The welding agency, which must make them available to the D.O.B
Who must furnish a control diagram and boiler operation instructions?
The installer
Who certifies and calibrates all gages used for testing?
A testing operator
What is placed between different types of joints and piping materials?
An approved adapter fitting
What items are exempt from reporting requirements?
Seal welds of tubes and installation of back rings to manholes and handholes of boilers
Who controls welding performed on a high pressure tank?
An engineer supervising a welding inspection agency acceptable to the D.O.B
At what pressure are extra heavy valves required?
100 PSIG
Who files an application for a boiler alteration?
Inspector
How many safety valves does a boiler with over 500 square feet of heating surface have?
2
What must gas-fired boilers not exceeding 100 square feet of heating surface have?
A single or double cone type hood diverter in the stack
Where shall a heater for liquid fuels or other boiler-harmful liquids not be installed?
Directly in the steam or water space within a boiler
Who is responsible for spatial relationships between tanks and gas services?
The installer of the last installation, who must correct the violation
Who is responsible for setting operating and safety controls?
The installing company
What safety fitting protects high pressure steam and water boilers?
Dual low water cutouts
What total combined relieving capacity must spring loaded safety valves have?
100% of the maximum designed capacity of the boiler
What is the total combined relieving capacity of power actuated relieving valves?
No less than 10% of the MAWP and no more than 20% above the MAWP
What is the minimum blowdown for a spring loaded safety valve?
2%
When a boiler is derated, what changes?
The MAWP decreases and the BTU output decreases
Where shall shutoff valves be installed in hydronic piping systems?
Before and after the pressure reducing valve
How must hydronic piping joints between steel tubing and fittings be made?
Mechanical or welded
What appears on a boiler's nameplate?
Serial number, name of manufacturer, manufacturer's serial number, MAWP, heating surface, year built, and rated steam capacity
Where must boiler waste gas be conducted?
To the atmosphere
What is installed on a line when a quick-closing valve creates water hammer?
A water hammer adapter
What are the three ways safety valve capacity may be checked?
Accumulation test, amount of fuel burned, and evaporative capacity of feedwater
Where are inspection records kept?
On the premises
Repacking of which joint types does not require a work permit for anchorages or guides?
Ball or slip joints
What must be done before an internal high pressure inspection?
Shutdown, drained, and removal of hand and manholes
What is the blowoff tank outlet size requirement?
Outlet is 2 times the diameter of the blowdown piping, with a 6 inch internal pipe entering the bottom of the blowoff tank
What info is not necessary to send to D.O.B?
Use, type, size, location, and operating temperature of pressure tanks, and location, type, and specs of the pressure relief valve
What are the specs of a miniature boiler?
16 inch inner diameter, 5 ft gross volume, 20 sq ft heating surface, less than 100 PSIG MAWP
What are the safety valve popping point tolerances by pressure range?
Up to 70 psig: plus or minus 2 psig; 71-300 psig: plus or minus 3%; 301-1000 psig: plus or minus 10 psig; over 1000 psig: plus or minus 1%
What are other ways to test a safety or relief valve for rated capacity?
Accumulation test, amount of fuel burned, and evaporative capacity of feedwater
What happens if someone fails to follow gas piping inspection rules and regulations?
Revocation of license
For a 5 psig gage, what range must not be exceeded?
10 psig (2x the operating pressure)
What can be connected to the float chamber or water column?
A damper regulator, feedwater regulator, gage, and drain
On a steam gage, what keeps the tube filled with water?
A siphon
What is the minimum working clearance around boilers and vertical clearance?
NYC code requires 18 inches, High Pressure code requires 24 inches; vertical clearance is 7 feet
Who sets, adjusts, and tests boiler controls?
By the installer
What do mufflers prevent?
Back pressure
What valve is on the external piping of a desuperheater?
Stop valve (external)
How often must a boiler with MAWP up to 400 psi be tested?
Once a year
What is the minimum safety or relief valve capacity for electric boilers?
3.5 lb/hr/kW
Who retains a copy of the report after welded repairs or alterations?
The owner
Who receives the application for permission to install a second boiler?
Commissioner
How much clearance is needed to go on top of boilers for maintenance?
7 feet
How far above the floor must wet-bottom boilers be set?
12 inches
Where do you find the information needed to set safety and relief valve pressure?
The nameplate of the safety valve
If one safety valve is on an electric boiler, what is the maximum output?
Less than 1100 kW
What pressure must a system using utility street steam have?
200 PSIG at 413°F, then reduced by a PRV
What chemical should be used for oxygen scavenging?
Sodium sulfite or sodium hydroxide
What is the minimum distance from the wall to the boiler?
18 inches in NYC Construction Code, 24 inches in High Pressure Code
What is the lowest part of a water gage?
2 inches above the lowest permissible water level
What standards are used for gages?
ASME and ANSI
What is the only thing that can tap onto a low water cutoff?
A drain
How many expansion tanks are needed for 6 boilers?
1
Who designs the boiler system?
The professional engineer or the architect
For a 5 psig gage, what is the minimum calibration increment?
1/5 inch increments
At what percent of MAWP is a boiler hydrostatically tested?
150%
Besides the state boiler inspector, who else can look at the log book?
The insurance company
What is the difference between low and high pressure safety relief valves?
Low pressure relieves to a drain, while high pressure relieves to a vent
What is the minimum dial arc on a 2 1/4 inch gage?
270 degrees
Where is the steam gage installed on a miniature boiler?
On the steam space side
What is an effective stop for a gauge?
The indicating point at zero
How long is the prepurge on a low pressure boiler?
90 seconds
What do the stamps S and H mean?
S means power boiler; H means low pressure boiler
How many drains must each superheater have?
At least one
How often does an insurance inspector inspect boilers?
Annually
What boiler work is exempt from reporting?
Replacement of backings to manholes and handholes, and seal welds to tubes
How do you prepare a brazed joint and a weld?
Braze: clean, flux, heat, filler metal. Weld: clean, bevel/convex, weld with filler metal, wire wheel
On what boilers are mufflers not to be installed?
High pressure boilers
What happens if discharge and supply strainers are clogged?
Deep vacuum
How many safety valves are on a miniature boiler?
1 safety valve, since it has only 20 sq ft
What is used between two different types of metallic pipe?
A dielectric kit or fitting
Where is gas service or distribution line from a new high pressure tank installed?
In a separate room
How many square feet of heating surface does a fusible plug require?
50 sq ft
Where does a low pressure safety relief valve discharge?
The drain
At what power output do electric boilers need two or more safety valves?
1100 kW
How many safety valves are required for an electric boiler operating at a maximum of 1100 kW?
2
When is a bullseye water sight glass acceptable on a miniature boiler?
When there is insufficient space for a gage glass on a miniature boiler
Where is the inspector notice posted after being given to the owner?
On or close to the boiler
What type of welding must pipes 2 inches or larger have?
Butt welding
For a 3 psig gage, what is the calibration increment?
1/10
What are the minimum and maximum temperatures for a hydrostatic test?
Above ambient temperature; code range 70-120°F
Where does a low pressure safety relief valve discharge?
A drain
How do you prepare a soldered joint?
Clean, flux, heat, solder
How often do you bottom blow off a boiler?
Daily
Who authorizes changes to high pressure piping anchors, guides, and expansion joints without affecting health and safety?
The professional engineer