Engineer practical ques.

1. The minimum blowdown for a spring loaded safety valve shall be of what percent of the set pressure?

ANS: 10%

2. How is the Main Steam pressure gages tested?

ANS: With an Inspectors Gage

3. Who is in charge of the code for any plumbing installations?

ANS: The NYC Plumbing Code

4. When will anchorage or guides be inspected?

ANS: Annually

5. How many brass washout plugs does a miniature boiler have?

ANS:  3 Brass Washout Plugs 1” in size

6. How often is Hp piping expansion joints inspected?

ANS: Weekly

7. How long should a Hydronic System be pressure tested for?

ANS: 2 hours at no less than 100 PSIG

8. How is a gage protected from excessive pressure?

ANS: Shut off Cock

9. Who is authorized to witnessing a test on a gas piping system?

ANS: Plumbing Inspector, Architect, Licensed PE, Master Plumber, or Agency by the D.O.B

10. How should a remote disconnect be labeled?

ANS: Remote control for burner

11. When is a fusible plug not needed to be installed on a boiler?

ANS: Over 200 Psig

12. When shall a power boiler with a MAWP over 400 be tested?

ANS: Pressure tested annually

13. What shall a Design plan of a boiler and application contains but not limited to?

ANS: Size, Location, Operating Pressure + Temperature of the Pressure vessel, and Type + Specification of the PRV

14. Who is responsible for maintaining the copies of the certified welder qualifications report?

ANS: The Welding Agency and shall be available to the D.O.B

15. Who needs to furnish a control diagram and boiler operation instructions?

ANS: The Installer

16. Who will certify and calibrate all gages utilized for testing?

ANS: A Testing Operator

17. What shall be placed in between different joints and piping material?

ANS: An approved Adapter Fitting

18. What items are exempt from the reporting requirements?

ANS: The Seal Welds of Tubes and the Installation of Back Rings to Man holes and Hand Holes to Boilers

19. Who will be under control for any welding done to a High pressure tank?

ANS: an Engineer Supervising a welding inspection agency acceptable to the D.O.B

20. At what pressure is it required to have extra heavy valves installed?

ANS: 100 PSIG

21. The ___________ files an application for a boiler alteration

ANS: Inspector

22. How many safety valves does a boiler have with over 500 square feet of heating surface?

ANS: 2

23. Gas fired Boilers not exceeding 100 square feet of heating surface shall be provided with a?

ANS: Single or Double Cone type of Hood Diverter in the stack

24. A heater for either liquid fuels or other liquids harmful to the boiler shall not be installed?

ANS: Directly in the steam or water space within a boiler

25. Who is responsible for any spatial relationship between tanks and gas services?

ANS: The Installer of the last installation to correct the violation

26. Who is responsible for the setting of operating and safety controls?

ANS: The Installing Company

27. With what safety fitting shall you protect High Pressure Steam and water boilers with?

ANS: Dual Low Water Cut Outs**

28. Spring loaded safety valves have a total combined relieve capacity of?

ANS: 100% of the Max Designed Capacity of the Boiler

29. What is the total combined relieving capacity of power actuated relieving valves?

ANS: No less than 10% of the MAWP or no higher than 20% above the MAWP

30. What is the minimum blowdown for a spring loaded safety valve?

ANS: 2%

31. When a boiler is derated what changes?

ANS: The MAWP Decreases and the BTU Output

32. In Hydronic piping systems where shall a shutoff valve be installed?

ANS: Before and After the Pressure Reducing Valve

33. Hydronic piping joints between steel tubing and fittings shall be?

ANS: Mechanical or Welded

34. What appears on the plate of a boiler?

ANS: Serial #, Name of Manufacturer, Serial # of manufacturer, MAWP, Heating Surface, Year Built, and Rated Steam Capacity

35. Waste Gas removal of a boiler shall conduct the products of combustion where?

ANS: to the atmosphere

36. When a quick closing valve creates what hammer what is installed on the line?

ANS: A Water Hammer Adapter is installed

37. Safety valve capacity may be checked in what 3 ways?

ANS: Accumulation Test, Amount of Fuel Burned, Evaporative Capacity of Feed water

38. Records of inspects are kept where?

ANS: On the Premises

39. No joint anchorages or guides shall be repaired replaced or relocated without a work permit issued by the dept. this shall not apply to the repacking of a __________ or __________ joint.

ANS: Ball or Slip Joints

40. Internal high pressure inspection requires the boiler to be __________,__________, ___________ and _________.

ANS: Shutdown, Drained, Removal of Hand and Man Holes

41. The outlet of the blowoff tank is what size?

ANS: 2 times the diameter of the Blowdown piping, 6 inches internal entering the bottom of in the blow off tank

42. What info is not necessary to send to D.O.B?

ANS: Use, Type, Size, Location, Operating Temp of Pressure Tanks, and Location, Type, Specs of Pres Reliev. Valve

43. Miniature boiler specs are _____ I.D            ____ ft gross volume ____ ft water heating surface ___ MAWP

ANS: 16 Inner Diameter, 5 Ft Gross Volume, 20 ft of heating surface, less than 100 PSIG

44. Safety valve popping tolerance + capacity up to 70 psig? 71-300 Psig? 301-1000 psig? >1000psig?

ANS: 70 psig = 2PSIG​71-300PSIG = 3%​​301-1000PSIG = 10PSIG ​1000PSIG+ = 1%

45. What are other ways of testing safety or relief valve for rated capacity?

ANS: Accumulation test, Amount of Fuel Burned, Evaporatative Capacity of Feed water

46. What is someone is found not following the rules and regulation for gas piping inspections?

ANS: Revocation of License

47. What range of the gage shall not excess when using a magnitude of 5 psig?

ANS: 10 psig (2x the Operating Pressure)

48. What can be connected to the float chamber or water column?

ANS: A Damper Regulator, a Feed water Regulator, a Gage, a Drain

49. On a steam gage what keeps the tube filled with water?

ANS: A Siphon

50. The minimum working clearance around boilers is ________? Vertical______?

ANS: The NYC code says 18”, while the High Pressure code says 24” | both Vertical 7ft

51. Boilers shall have all controls set, adjusted, and tested by

ANS: By the installer

52. Mufflers prevent ______

ANS: Back Pressure

53. External piping of a desuperheater in relation to a boiler has a _____ valve

ANS: Stop Valve (EXTERNAL)

54. When shall a boiler with a MAWP up to 400 psi be tested?

ANS: Once a year

55. What is the minimum safety or relief valve capacity for electric boilers?

ANS: 3 ½ lb/hr/kW

56. After welded repairs or alterations of the equipment, what shall retain a copy of the report?

ANS: The Owner

57. Any boiler changing location within the state may be reinstalled; an application for permission to install a second boiler is filled with whom?

ANS: Commissioner

58. When it is necessary to go on top of boilers for maintenance how much clearance is needed?

ANS: 7 Feet

59. Wet bottoms boiler shall be set above the floor not less than?

ANS: 12”

60. How do you set the pressure of the safety and relief valves? Find the _____?

ANS: Find the Nameplate of the Safety Valve

61. If there is one safety valve on an electric boiler what is the max output?

ANS: less than 1100 kw

62. What pressure shall a system using utility street steam have?

ANS: 200 PSIG at 413*F which than is reduced by a PRV

63. What chemical should be used for oxygen scavenging?

ANS: Sodium Sulfite or Sodium Hydroxide

64. What is the minimum distance from the wall to the Boiler?

ANS: 18” in NYC Construction Code, 24” in High Pressure Code

65. What is the lowest part of a water gage?

ANS: 2” above the lowest permissible water level

66. What standard are used on gages?

ANS: ASME, ANSI

67. What is the only thing that could tap onto a low water cut-off?

ANS: A Drain

68. How many expansion tanks are needed for 6 boilers?

ANS: 1

69. Who shall design the boiler system?

ANS: The Professional Engineer or the Architect

70. Gage to be measured in the magnitude of 5 psig shall not be calibrated in no less than?

ANS: 1/5” increments

71. At what percent do you hydrostatically test a boiler?

ANS: 150%

72. Beside a log book being inspected by a state boiler inspector who else can look at the book?

ANS: The Insurance Company

73. What is the difference between low pressure and high pressure safety relief valves?

ANS: Low Pressure relieves to a drain, while High pressure relieves to a vent

74. What is the minimum dial arc on a 2 ¼ gage?

ANS: 270*

75. Where is the steam gage installed on a mini boiler?

ANS: On the steam space side

76. What is an effective stop for a gauge?

ANS: The indicating point at zero

77. How long is the prepurge on a low pressure boiler?

ANS: 90 seconds

78. What does the Stamp (S) mean and the Stamp (h) mean?

ANS: S Means Power Boiler       ​H Means Low Pressure Boiler

79. Each superheater shall be equipped with how many drains?

ANS: AT LEAST one

80. How often does an insurance inspector inspect the boilers?

ANS: Annually

81. What is the work that is done to a boiler that doesn’t have to be reported and is exempt?

ANS: Replacement of Backings to Man Holes and Hand Holes and Seal Welds to tubes

82. How do you prepare a brazed joint? A weld?

ANS: Braze: Clean, Flux, Heat, Filler Metal           Weld: Clean, Convex, Weld a Filler Metal, Wire Wheel

83. Mufflers are not to be installed on___?

ANS: High Pressure Boilers

84. What would happen if your strainers from your discharge and supply lines are clogged?

ANS: Deep Vacuum

85. How many safety valves are on a miniature boiler?

ANS: 1 since only 20 sq ft

86. When connecting two different types of metallic pipe what is used in between?

ANS: A dielectric Kit or fitting

87. Where do you install gas service or distribution line from a new high pressure tank?

ANS: In a Separate Room

88. How many square feet of heating surface does a fusible plug require?

ANS: 50 sq ft

89. Where does a low pressure safety and relief valve discharge to?

ANS: The Drain

90. Electric boilers have two or more safety valves @ a power output of ___KW

ANS: 1100 KW

91. If an electric boiler is operating at a max of 1100 kW how many safety valves are required?

ANS: 2

92. When is a bullseye water sigh glass acceptable on a miniature boiler?

ANS: When there is insufficient space for a Gage Glass on a Mini Boiler

93. After an inspector notice is given to the owner where is it posted?

ANS: On or Close to the boiler

94. What type of welding shall the pipes of 2” or more have?

ANS: Butt Welding

95. Gage measured in the magnitude of 3 psig calibrated in increments of?

ANS: 1/10

96. What are the minimum and the maximum temp when performing a hydrostatic test?

ANS: Above Ambient Temperature CODE: 70-120*F

97. Where does a low pressure safety and relief valve discharge to?

ANS: A drain

98. How do you prepare a soldered joint?

ANS: Clean, Flux, Heat, Solder

99. How often do you bottom blow off?

ANS: Daily

100. Who authorizes changes to High Pressure piping anchors, guides and expansion joints without effect to health and safety?

ANS: the professional Engineer

101. When installing an expansion tank what factor is taken into consideration?

ANS: the MAWP of the Boiler System

102. If you are reading 12% Co2 what does it pertain to?

ANS: Incomplete Combustion

103. When should you inspect expansion joints?

ANS: Weekly

104. How far does a pressure tank to be away from any gas services?

ANS: 5 feet horizontal

105. Where is a remote disconnect located? What is it labeled?

ANS: Remote control for burner, located at the egress

106. What range of gage magnitude of 3 psig shall not exceed?

ANS: 1/10 increments @ 4.5PSIG (1 ½ x times) (they might say 5) to 6PSIG (2x times)

107. What is the minimum face size of a non mercury gage?

ANS: 2 ¼”

108. How many complete turns do a slow opening valve take from full-close to fill-open?

ANS: 5 ​360* Turns

109. What is the size pipe of the surface blow off?

ANS: 2 ½” Max

110. What is the pipe size of a gage cock connection?

ANS: ½”

111. How many gauge cocks are needed if a boiler is not over 36 inches in diameter and does not exceed 100 sq feet of heating surface?

ANS: 2

112. How do you protect a bottom blow off pipe when exposed to direct furnace heat?

ANS: Fire Brick

113. Who has prior approval by the D.O.B when an eminent health or safety hazard happens?

ANS: the professional Engineer

114. If a muffler is installed on a safety valve or safety relief valve the function is to?

ANS: Prevent Back pressure on a boiler

115. What do you do when adding a new tube to a boiler? Water tube boiler? Fire tube boiler?

ANS: Roll and Expand​Water Tube Roll and Flare​Fire tubeRoll and Bead

116. Prior to the Clean Air act what were boiler operations concerned with?

ANS: Sulfur Dioxide

117. What standard is plastic pipe/pvc in Hydronic systems held to?

ANS: ASTM

118. What boiler should be used for hot water?

ANS: A Low Pressure Hot Water Boiler operating at a max of 120 *F

119. What is potable water?

ANS: Drinking Water

120. What is the flame index of Insulation?

ANS: 25 Flame Index

121. What is the flame spread index of smoke density?

ANS: 450 Smoke Index

122. What are the allowed tapings of a water column?

ANS: Feed Water Regulator, Damper Regulator, Drain, Steam Gage

123. What is the seat of a safety valve composed of?

ANS: High Pressure is stainless, low pressure is bronze/ stainless

124. What is the minimum reading of a digital gage?

ANS: 1/100 of a PSIG

125. Where do you find the maximum setting for the safety and relief valves?

ANS: the nameplate of the Safety and Pressure Relief Valve

126. How many water gage glasses are needed over 400 psig boilers?

ANS: 2

127. There must be _______ gage cocks within the visible length of the water glass?

ANS: 3 Visible

128. When will the LWCO trip?

ANS: A ¼” below the lowest permissible water level given by the company who installed the LWCO

129. What pressure do you hydrostatically test a 400 psi boiler?

ANS: 600 psi

130. A boiler operates at 300 psi, it is tested once ______________?

ANS: Once a month and pressure tested every year

131. When a safety valve is replaced what is different?

ANS: Shall be equal to the last valve installed

132. What pressure will a safety valve lift completely?

ANS: 3%

133. Safety Valves shall be set at?

ANS: The MAWP

134. What kind of valve is located between the boiler and a safety valve?

ANS: None

135. Where no mechanical feed is attached to a boiler what is the safety valve set pressure?

ANS: 6%

136. PEX conforms to

ANS: ASME

137. Where shall a pressure relief valve be installed on a Hydronic piping system that has been reduced in pressure?

ANS: on the low pressure Side of the System

138. What size is the overflow on an open type of expansion tank?

ANS: 1”

139. What size is the inspectors test gage connection

ANS: ¼”

140. Where is the test gage connected to?

ANS: Shall be connected to the Boiler

141. Brazed joints use a filler metal that conforms to AWS A_._?

ANS: AWS A 5.8

142. Pipe Insulation shall have a maximum flame spread of _____?

ANS: 25 Flame Spread Index

143. Where does the gaseous waste of boiler combustion go?

ANS: Should be equipped with means for conducting products of combustion outside to the atmosphere

144. You blow down the boiler every?

ANS: Daily

145. The boiler shall be equipped with automatic devices responsive to variations in _______

ANS: Steam Pressure

146. What are all the specs of a Non mercury gage of magnitude of 3 psig

ANS: Has a Min of a 2 ¼” Gage, Dial 270* arc, Minimum increments of 1/10 PSIG, shutoff cock, indicating point at zero and has a calibration screw

147. What are all the specs of a non mercury gage of magnitude of 5 psig

ANS: Has Min of 2 ¼” Gage Dial, 270* arc, Minimum increments of 1/5 of a psig, Shut off cock, indicating point at zero, and has a calibration screw

148. A boiler operates at 100 psig, how many fusible plugs are there?

ANS: 1 Fusible Plug (over 50 sq ft)

149. A boiler operating at 100 psi mawp, how are pipes joined together?

ANS: Flanged or Welded

150. If you were getting 16-90psig from an outside source, what shall the system be designed for?

ANS: 125 PSIG

151. Where is shutoff valves located on a PRV?

ANS: Before and After the Pressure Reducing Valve

152. Natural Gas has how many Btu’s?

ANS: 960 Btu’s

153. What kind of scrubber does an incinerator have?

ANS: Wet Scrubber (slurry)

154. __________ is the term used with a wet absorber nozzle in relation to anincinerator.

ANS: Slurry

155. What is the first step of a hydrostatic test?

ANS: Fill the boiler with water till you see it up out the boiler vent

156. The size of each connection to a water column? Boiler-> W.C | G.G| Cocks| Test Gage| Drain

ANS: Boiler=> 1” W.C => ½” GG => ½” Cocks => ¼ Test Gage => ¾” Drain

157. How often do you test for water treatment of boiler feed water?

ANS: Daily

158. How do you decrease back pressure on a condensing engine?

ANS: Have the exhaust (steam) flow right into the (surface) condenser

159. Where is the absorber pump located in between?

ANS: Outlet Damper and the Stack

160. What is the minimum size for a safety valve?

ANS: ¾”

161. What is the capacity of a relief valve for a low pressure boiler under 30psig? Over 30psig?

ANS: under 30 PSIG has a relieve capacity of 20% above and over 30% is 10% above

162. In a low pressure boiler the safety valve shall not rise _ psi above the MAWP?

ANS: 5 PSI above the MAWP

163. A combustion regulator prevents water from rising above ___ *F or a steam pressure of __ in relation to LPB.

ANS: 250*F or a steam pressure of 15PSIG

164. The minimum size of a bottom blow off valve is?

ANS: ¾”

165. Relief valves on LPB are rated up to ___*F

ANS: 275*F

166. What are the 3 different types of stress?

ANS: Compression, Shear, Tensile

167. A low Pressure Boiler needs inspection if it occupies more than __ Families?

ANS: 6

168. One sq ft of fresh air for every ______ btu’s of fuel burned, in relation to LPB Gas Fire Burners

ANS: 2,000,000 Btu’s

169. Hydrostatic Inspection must has __ days notice

ANS: 15 Days

170. The certificate of inspection is placed?

ANS: As close to the boiler as possible

171. A L.P How Water Boiler is considered low pressure below?

ANS: 160PSIG @ 250*F

172. What size are brass wash out plugs on a mini boiler?

ANS: 1”

173. When your roll and expand tubes how far should they extend?

ANS: Evenly ¼”, ½”, ¾”

174. What item is not exempt from reporting requirements of welds?

ANS: Cracks on the Boiler Shell

175. What is the valve order on a desuperheater? Boiler  Proper->____->____->_____

ANS: Stop Valve => Pressure Regulating Valve => Block Valve

176. Who cannot oversee a gas piping inspection?

ANS: Insurance Company

177. Hydronic system runs at 150 psi, hydrostatic test at 225 psi, rated to run at 115 psi what pressure should it not exceed?

ANS: 150PSIG

178. How would you prevent damage to piping due to temp changes?

ANS: Expansion Bends

179. How do you protect potable feed water for a boiler?

ANS: Pressure Vacuum Breaker

180. Brass pipes cannot be joined by

ANS: Solder

181. In relation to Testing of High Pressure steam Piping Systems, where the changes in an existing system involves less that 30% of the piping in the system, the testing may be done in accordance with?

ANS: ASME – On Hydrostatic Tests

182. Where is a siphon located?

ANS: before the gauge

183. On boilers with water jacked boiler furnace mouth, protector valves are locked and sealed open shall be of what type?

ANS: Of the Straight – Way Type

184. Ground source heat pump loop systems should be pressure tested for minutes at _ psi

ANS: 30 Minutes at no less than 100 psig

185. Street steam PSI and TEMP is then reduced by a PRV to 90- 16 pounds which is Designed as a ___psig system

ANS: 125 PSIG Systems

186. Forced steam flow generator safety valve relieve ___ of the MAWP, they pop at no less than % of the mawp and no higher then % of the MAWP and shall have ___ “fail safe” to stop the flow of ____ and ___ to the boiler, these valves then reseat at no less than __%

ANS: 100% of the MAWP pop no less than 10% and no higher than20%, with 2 fail safes stopping the flow of fuel and feed water to the boiler, reseat no less than 10%

187. On a boiler proper, if a safety valve pops it must relieve all the pressure without allowing that pressure to rise more than __% above the highest pressurerated

ANS: 6%

188. Safety valves are a ______-____ type?

ANS: Pop-Spring Type

189. The Minimum lift ” and a safety valve blowdown is % of the set pressure and no greater than % and must reseat at _% of the pressure?

ANS: Min Lift is 1/16 of a inch, Min safety valve blow down is 2%, fully lifted at 3% and reseats at 96% of the pressure.

190. The popping point tolerance shall not exceed 70=? 71-300=? 301-1000=? 1000+

ANS: 70 = 2PSIG+/-  71-300= 3%+/-  301-1000= 10PSIG+/-  1000+PSIG= 1%+/-

191. All piping over 2” shall be ____ welded?

ANS: Butt Welded

192. All piping under 2” shall be ____ welded or_____?

ANS: Socket Welded or Flanged

193. How long do you hydrostatically test a hydronic system? At a pressure not less than?

ANS: 2 hours @ <100PSI

194. 1cfm for every _____ Btu’s in accordance with forced combustion air

ANS: 2400 Btu’s

195. Who witnesses gas piping inspections?

ANS: an authorized Plumbing Inspector, or Licensed P.E or Master Plumber, or Architect

196. Repairs to Safety Valves Must be performed by an organization in possession of a

ANS: National Board V.R (Valve Repair) Certificate

197. When you roll and expand tubes how far should they extend?

ANS: Evenly ¼”, ½”, ¾”

198. A fuel regulating governor is controlled by?

ANS: Steam Pressure

199. The lowest permissible water level in a miniature boiler is?

ANS: 1/3”

200. The minimum size of a feed water connection to a miniature boiler is?

ANS: ½”

201. All miniature boiler openings in the boiler shall be (construction) _____________ or ______ reinforcement? How many threads?

ANS: Mechanical Construction with a minimum 4 threads, or Welded

202. How many brass washout plugs are on a Miniature boiler with less than 12 “ ID of shell and Less than 10 sq ft of heating surface?

ANS: only 2, where one may be used as a blow down line

203. Where the brass washout plugs of miniature boilers shall be screwed into?

ANS: On the bottom part of the Miniature boiler

204. A miniature boiler has less than ___ MAWP

ANS: less than 100 MAWP (PSI)

205. A miniature boiler has up to __ sq ft of heating surface?

ANS: 20 Sq Ft of heating surface

206. A miniature boiler has up to___ cubic ft of gross volume?

ANS: 5 cubic ft of gross volume

207. A miniature boiler has up to__” of ID of shell?

ANS: 16” Inner Diameter

208. Any MOUTH PROTECTOR on a boiler shall be locked or sealed ____. What type?

ANS: Locked or Sealed Open, of the Straight Way Type

209. When are fusible plugs replaced?

ANS: Annually

210. When a discharge pipe is used on a safety valve it shall be ____ (size) of the safety valve, and fitted with a ___ drain?

ANS: no less than the same size, fitted with a open drain

211. Three different ways to check the safety valve capacity?

ANS: Accumulation Test, Maximum amount of fuel burned, Maximum evaporative capacity of feed water

212. If a boiler has a Lap Seal Crack it shall be?

ANS: Discontinued

213. What is stamped on a Boiler?

ANS: Serial #, Name of Manufacturer, Serial # of manufacturer, MAWP, Heating Surface, Year Built, and Rated Steam Capacity

214. What is stamped on a boiler identification plate?

ANS: NAME, ID#, CLASS, Tensile Strength (according to the High Pressure code)

215. Safety valves are ____ or held by a ___ during a hydrostatic test?

ANS: Removed or Approved Clamp

216. If a boiler is gravity fed, there shall be what valves on the line?

ANS: A stop valve as close as the boiler as possible followed by a Check valve

217. What must you not adjust on the safety valve during a hydrostatic test?

ANS: The compression screw

218. What is the max psig of a water column constructed of Cast iron? Malleable iron?

ANS: Cast Iron = 250 PSIG Malleable Iron = 350

219. What is the minimum size of the blow off piping?

ANS: 3/4

220. When shall a water column have a shield of a sleeve?

ANS: Over 400 PSIG

221. What is the minimum size of a feed water piping connection to a boiler with less than 100 sq ft of heating surface? More than 100 sq ft of heating surface?

ANS: The minimum Less than 100 sq ft is ½” and more than 100 sq ft is ¾”

222. When shall a boiler have at least two means of feed water?

ANS: When the boiler is over 500 SQ FT of Heating Surface

223. How many drains are on a super heater, and is the minimum size in inches?

ANS: 1 drain measuring a minimum of 1”

224. Boilers have 2 bottom blow downs when the MAWP exceeds___ psi?

ANS: 100 PSIG

225. What schedule pipe can you use on boiler blow down lines?

ANS: Schedule 80

226. What is the Maximum size of a blow down valve? Minimum size and less than how many sq feet?

ANS: 2 ½ ”, ¾” less than 100 sq ft

227. All boiler fittings are what standard?

ANS: ASME

228. How many gage cocks are on a boiler with less than 36 “and 100 sq ft of surface?

ANS: 2

229. How many gage cocks are on a boiler with over 36” and more than 100 sq ft of surface?

ANS:  3

230. What size are the gage cocks on a boiler?

ANS:  ½”

231. How many gage cocks does a boiler have with two water glasses on the same horizontal line?

ANS:  2 Cocks @ ½”

232. Any valve used as a shutoff to a water column shall be sealed ___ and ____.

ANS: Sealed Open and LOCKED

233. HRT Fire tube boiler what is the minimum water level in a gage glass?

ANS: 3”

234. What can be attached to the same outlet from a super heater that is used also for the safety valve connection?

ANS: Soot Blower

235. A safety valve over 3” and over 15 psig shall have what type of inlet connection?

ANS: Flanged or Welded

236. The discharge of safety valves or safety relief valves shall be located so as to prevent ______

ANS: Scalding

237. Safety valve plate has what?

ANS: Name, Manufacturer #, Size, Seat, Pressure (PSIG), Year built, Capacity, Capacity lift, ASME

238. Where an isolation transformer is provided, one conductor of the secondary winding shall be?

ANS: Grounded

239. When would a heat exchanger not need shutoff valves?

ANS:  When it is integral with the boiler

240. The flash point in a Hydronic system is __*F above the maximum operating temperature.

ANS:  50 *F

241. The slope of piping for condensate is __%

ANS:  1/%

242. Piping Supports (Mechanical code 2008)

a. Steel Pipe Supports are spaced every Ft horizontal and Ft vertical

ANS:  12 Ft Horizontal and 15 Ft Vertical

b. Steel tube Supports are spaced every Ft horizontal and Ft vertical

ANS:  8 Ft Horizontal and 10 Ft Vertical

243. What is the Inspection Frequency of a Boiler?

a. Low Pressure Steam Internal and External?

ANS: Internal every 3 years and External every 2 years

b. Low Pressure Hot Water Internal and External?

ANS: Internal every 5 years and External every 2 years

c. High Pressure Steam Internal and External?

ANS: Internal every 1 year and External every 1 year

d. High Pressure Hot Water Boilers?

ANS: Internal every 3 years and External every 1 year