Minimum length of a pull box (straight run)

For a straight run of five 4ext"4 ext{"} conduits containing 2extAWG2 ext{ AWG} copper conductors, the minimum length is 32ext"32 ext{"} per NEC 314.28(A)(1)314.28(A)(1).

2
New cards

Free conductor length for splicing

In a 12extinch12 ext{-inch} by 12extinch12 ext{-inch} junction box, there shall be at least 6ext"6 ext{"} of free conductor left for splicing per NEC 300.14300.14.

3
New cards

Flat conductor cable

A wiring method that is not recognized for use as feeder or branch-circuit conductors per NEC 324.10(A)324.10(A).

4
New cards

Maximum hole size in a wood stud

For a nominal 1.5extinch1.5 ext{-inch} by 3.5extinch3.5 ext{-inch} wood stud without additional protection, the largest size hole permitted is 1ext"1 ext{"} per NEC 300.4(A)(1)300.4(A)(1).

5
New cards

Type MI cable strapping interval

This cable type is required to be strapped at intervals not exceeding 66' per NEC 332.30332.30.

6
New cards

Cellular metal floor raceway conductor limit

Generally, no conductor larger than 1/0extAWG1/0 ext{ AWG} shall be installed in this type of raceway per NEC 374.20374.20.

7
New cards

Insulated conductor operating temperature

No conductor shall be used in a manner where its operating temperature exceeds that designated for the type of insulated conductor involve per NEC 310.14(A)(3)310.14(A)(3).

8
New cards

Article 358

The Chapter 3 article in the NEC that covers the requirements for electrical metallic tubing.

9
New cards

Minimum-size parallel aluminum feeders

The smallest size aluminum feeder conductors permitted to be installed in parallel is 1/0extAWG1/0 ext{ AWG} per NEC 310.10(G)(1)310.10(G)(1).

10
New cards

Damp locations

Locations protected from weather and not subject to saturation with water or other liquids, but subject to moderate degrees of moisture.

11
New cards

Smallest single current-carrying conductor in cable tray

In an industrial establishment, the smallest size permitted is 1/0extAWG1/0 ext{ AWG} per NEC 392.10(B)(1)(a)392.10(B)(1)(a).

12
New cards

Pull box length for conductors 4extAWG4 ext{ AWG} or larger

Where conductors are pulled straight through, the box length shall be at least 88 times the trade diameter of the largest raceway per NEC 314.28(A)(1)314.28(A)(1).

13
New cards

Flush device enclosure design

A box used to enclose flush devices must be designed so that devices are completely enclosed on the back and sides per NEC 314.19314.19.

14
New cards

6 AWG THW copper conductor ampacity

When installed in a raceway with not more than three current-carrying conductors, it can carry 65extA65 ext{ A} continuously per Table 310.16310.16.

15
New cards

Integrated gas-spacer cable

A wiring method that is not permitted for use as an interior wiring method per NEC 326.12326.12.

16
New cards

Minimum covering for 4,160-volt feeder

For nonmetallic conduit identified for direct burial without concrete encasement, the minimum covering is 18ext"18 ext{"} per Table 305.15(A)305.15(A).