sensible heat
Heat that causes change in temperature of a substance
latent heat
Heat that is added with out a rise in temperature
super heat
Heat added to refrigerant in vapor state after evaporation process is
involute spirals
Scroll compressor moves refrigerant by means of
convection
movement of heat by way of fluid or air
conduction
movement of heat by way of solid
BTU
Standard unit for measuring heat
Condensor
refrigerant gives up heat in the
liquid slugging
refrigerant in suction line must be slightly warmer than the saturation temperature to prevent
low
state of refrigerant in the suction line is ____ pressure _____ temp vapor
High
state of refrigerant entering the condensor would be ______ pressure ______ superheated vapor
evaporator
transfers heat from refrigerated space to the refrigerant
flammability
which is not a thermo-dynamic property of refrigerants
Compression, condensation, expansion and vaporization
the sequential order of steps in vapor-compression process
201 psig
30 lbs cylinder of R410A sits overnight at 70 degrees would have a pressure of
inches of water column (WC)
fan airflow pressures are usually measured in
0 psia
pressure that cannot be further reduced
0 psig
the same as atmospheric pressure
dew point temp
the temp at which moisture will start to condense from the air is the
pressure and vacuum
compound pressure gauge measures
open drive compressor
a mechanical shaft seal is necessary on an
liquid slugging
liquid refrigerant in the compressor clearance space
clearance space
has an effect on compressor capacity in a reciprocating compressor
scroll
which type of air conditioning compressor is the most effecient
De-superheat, condense and subcool
what is the right order of function in a condensor
air cooled, water cooled and evaporative
3 basic types of condensors
sensible and latent
heat removed from refrigerant by condensor is both _____ and ______
energy recovery ventilator
what uses an air to air heat exchanger to recover heat
30 degrees hotter than the air entering
when testing the efficiency of an air cooled condenser the refrigerant condensing temp should be approximately
10 degrees hotter than the air entering
When testing efficiency of a water cooled condenser the refrigerant condensing temp should be approximately
de-superheat
First function of a condensor is to ____________________ before condensing can occur
TXV
A _______ is designed to maintain constant superheat
Auto Expansion Valve
______ ______________ _________ maintains constant evaporative pressure
evaporative, spring, sensor bulb
Thermo Expansion valve (TXV) has 3 pressures _____________________, _________________, and ___________________
lower than valve body
When mounting TXV sensor bulb, you do not install it _________________________________________________ .
warmer
In an air conditioning system that uses TXV, the temp of the evaporator outlet will usually be ______________ than evaporator inlet
fairly constant
Auto expansion valve (AXV) is best suited when the system load remains ___________ ______________.
evaporator temp
Capillary tubes do not maintain constant _________________________________ .
close
A decrease in superheat causes the TXV to begin to ___________.
close
A rise in evaporator pressure causes AXV to ___________.
NTC Thermistor
A thermal electric (solid state) expansion valve is controlled by _______ _______________.
mixture of liquid and flash gas
In a direct expansion evaporative system, the refrigerant enters the evaporator as a ________________________________________________________ .
coil to the condensing unit and latent/sensible load
Most important consideration in evaporator coil selection is to match the _______________________________________________
evaporator
In the ______________________ latent heat is transferred from refrigerated space to the refrigerant.
condensor and metering device
The liquid line filter dryer should be placed between the____________________________________________ .
sub-cooling
The only way to minimize flash gas is by ____________________ the liquid refrigerant.
Liquid receiver
______________ _______________ is used to store the liquid refrigerant.
Accumulator
The ________________________ keeps liquid from getting to the compressor
Site glass
_______ __________ is located in the liquid line before the metering device
bubbles in sight glass
_____________________________________ indicate refrigerant blend with a high temp glide
discharge line
Oil separator is installed in the ______________ ______.
metering device
A solenoid valve pump in a down system is located before the ____________ _____________.
Keep pressure from falling below limit
The purpose of the evaporator pressure regulating valve is to ___________________________________________________.
liquid sub-cooling
A liquid-to-suction heat exchanger is often used to increase ___________ _________________.
Oil pressure safety switch
______ ____________ __________ __________ is opporated by the difference between crank case pressure and oil pressure.
Low
_______ pressure cut off switch is used to establish a minimum opporating pressure
undercharge
Partially iced over evaporator coil can be caused by an ___________________________.
soap bubbles
_________ ____________ can be used for leak detection with all high pressure systems
40-70%
The flow rate of a R410A system is ___________ higher than that of R22
1 in
An electronic leak detector should be used at ___________ every 2 seconds
100 degrees
10 lbs. of refrigerant passing through a water cooled condenser will lose 20 Btu's of heat per lb. if 10 lbs of water passes through the condenser with an entering temp of 80 degrees. The temp. of the water leaving the condenser is
stopped up filter drier
a temperature differential across a filter drier indicates a
compressor failure
Moisture in a refrigeration system will cause _____________ _____________
Electronic vacuum gauge
_____________ _____________ __________ will measure microns
100
Water will vaporize at ___________ degrees F in a 28 in vacuum
Replace filter dryer, leak check, evacuate, charge
After a system has been opened and the compressor changed _____________________________, _____________, _______________________, and _______________.
500 microns
To remove as much moisture as possible from a system, triple evacuate the system to _______ ____________
124 psig
R134A vapor enters the condenser at 124 psig, 100 degrees Fahrenheit it leaves the condenser at 80 degrees fahrenheit its pressure will be approximately
compressor
it is desirable for refrigerant in the suction line to be slightly superheated in order to insure liquid refrigerant does not enter
high discharge line pressure and low liquid line pressure
What would be indicative of an oil logged condenser
12
A 410A system has compound gauge reading of 54 degrees F at 124 psig, the super heat would be _______ degrees F.
liquid into low side
When topping off an operating system using a blended refrigerant, introduce ________________________________________ while throttling the valve.
starved evaporator
Partially clogged capillary tube can cause_____________ _____________.
15
R134A high pressure gauge reads 146 psig and the liquid line temp at condensing unit is 95 degrees, the sub-cooling is _______ degrees F.
Increased head pressure
Overcharged refrigerant will cause an ____________ ______ ______________
dirty evaporator
Complaints that the air system runs constantly but there is no cooling would be ___________ __________________
negative
Drain trap should be installed on split system when air handler drain is on _______________ side of evaporator.
debris in filter dryer
If liquid line is sweating there is _____________________________________ .
350-450
Generally accepted range for evaporator airflow CFM per ton is __________________________ CFM
CFM
BTU/1.08x DeltaT
CFM
Cubic feet per minute______________
CFM
Temp rise method for determining air flow is _________
50
Recommended residential indoor relative humidity for summer is _____ %
lower higher
An inefficient compressor is indicated by __________ than normal head pressure _________ than normal suction pressure
high head pressure
A hermetic system that is low on refrigerant will not have
32
Frost on suction line indicates it's below dewpoint temp and below ______ degrees F
More
Increase in head pressure causes _______ refrigerant to flow through capillary tube.
Valve
With auto expansion valve an increase in evaporator load will cause the _________ to close
Low head pressure
When a TEV or capillary tube is used as a metering device low refrigerant charge will cause _________ ____________ __________________.
15
Max oporating pressure setting for an acetylene torch is _____ psig
45
When connecting copper to steel braise with ______ % silver alloy
flushing filter dryers
Solid contaminants from a hermetic compressor burnout are best removed by _____________ the system and installing _______ /_______ in both the liquid and suction lines
reduce
If the cut off plate is removed from blower assembly, it will ___________ air flow
Inert gas
Can use a trace amount of refrigerant and __________ ______ to leak test the system
low
After properly recharging a system, if the compressor is noisy, it is _____ on oil
inefficient
Over sized air conditioning system can cause _________________ de-humidification of the space
low
Low operating pressure and low system amperage draw causes _______ air flow across the evaporator
high
Air or other non-condensables will cause ______ suction line and ________ discharge line pressure
high
Refrigerant overcharge will cause _______ suction and _______discharge pressure
high low
Compressor with broken reed valve causes _______ suction and ________ discharge pressure