101 Terms

1
New cards
2
New cards
76 mm Ø
Minimum outlet size of a sand interceptor.
3
New cards
0.2 m²
Minimum net opening dimension of the inlet section of a sand interceptor.
4
New cards
610 mm
Minimum depth of sand interceptor under the invert of the outlet pipe.
5
New cards
0.09 m²
Increase in the area of inlet section for each 18.9 LPM or fraction thereof over 75.7 LPM.
6
New cards
50% of the inlet section
Minimum area of sand interceptor outlet section.
7
New cards
762 mm
Distance of trap to vent for 32 mm Ø.
8
New cards
1067 mm
Distance of trap to vent for 38 mm Ø.
9
New cards
1524 mm
Distance of trap to vent for 51 mm Ø.
10
New cards
1829 mm
Distance of trap to vent for 76 mm Ø.
11
New cards
3048 mm
Distance of trap to vent for 102 mm Ø and larger.
12
New cards
1829 mm
Maximum developed length between water closet and vent.
13
New cards
GA 26
Minimum thickness of galvanized sheet metal for rainwater downspout or conductor.
14
New cards
0.6 meter
Rainwater piping commencing ____ from the exterior of a building may be suitable approved materials.
15
New cards
102 mm
Extension of roof drain strainers above the surface of the roof.
16
New cards
1.5x the area of outlet
Minimum total net inlet area of roof drain with dome-type strainers.
17
New cards
2x the area of outlet
Minimum total net inlet area of drain with roof deck strainers.
18
New cards
102 mm/hour
Rainfall intensity normally used around Manila area.
19
New cards
50%
Additional for area of 1 wall.
20
New cards
35%
Additional for area of 2 adjacent walls.
21
New cards
0%
Additional for area of 2 opposite walls
22
New cards
50%
Additional for side of tall building exposed to rain
23
New cards
0.392x diameter
When gutter has semi-circular bottom, depth of equivalent area of rectangular gutter
24
New cards
0.8862x diameter
When gutter has semi-circular bottom, width of equivalent area of rectangular gutter
25
New cards
7/24 full
Basis of Table 11-4
26
New cards
3:1
Ratio of the side dimension of a rectangular vertical piping
27
New cards
More than 61 m
Public sewer is not available if
28
New cards
6"
Minimum diameter of building sewer, but not less than the size of the building drain
29
New cards
2%
Recommended slope for building sewer
30
New cards
1%
Allowable slope for drainage piping 102 mm or 152.4 mm in diameter given site constraints
31
New cards
0.5%
Allowable slope for drainage piping 203 mm or larger in diameter
32
New cards
0.60 m
Distance of building sewer from outer face of any building foundation or wall
33
New cards
0.30 m
Minimum depth of building sewer below finished ground surface
34
New cards
Exceeding 135°
Aggregate offset angle to be provided with an additional cleanout
35
New cards
Less than 3 m
Length of building sewer not requiring a cleanout
36
New cards
91 m
Maximum distance between manholes
37
New cards
0.30 m
Distance between bottom of water pipe and top of sewer or drain line
38
New cards
0.30 m
Horizontal distance between water line and sewer or drain line
39
New cards
0.30 m
Distance between sewer/drainage piping and water pipes crossing above
40
New cards
3 m
Minimum distance of water pipe joints away from a sewer line
41
New cards
1.5 m
Distance within property line where abandoned building sewer shall be plugged or capped
42
New cards
30 days
Maximum time from connection to public sewer to fill abandoned disposal facility
43
New cards
0.60 m
Minimum horizontal distance of a building/structure from the building sewer
44
New cards
0
Minimum horizontal distance of property line from building sewer
45
New cards
15.2 m
Minimum horizontal distance of water supply wells from building sewer
46
New cards
15.2 m
Minimum horizontal distance of streams from building sewer
47
New cards
0.30 m
Minimum horizontal distance of on-site domestic water service line from building sewer
48
New cards
0.30 m
Minimum horizontal distance of public water main from building sewer
49
New cards
7.6 m
Allowable reduced distance from water supply wells if approved materials are used
50
New cards
No minimum
Maximum/Minimum FU on 152 mm building sewer @ 2%
51
New cards
3
900/275, Maximum/Minimum FU on 203 mm building sewer @ 2%
52
New cards
6
800/300, Maximum/Minimum FU on 254 mm building sewer @ 2%
53
New cards
11
200/235, Maximum/Minimum FU on 305 mm building sewer @ 2%
54
New cards
25.4 mm
Minimum depth to be filled with molten pig lead
55
New cards
3.2 mm
Extension of the finished joint below the rim of the hub
56
New cards
Schedule 80
Minimum wall thickness of threaded plastic pipe
57
New cards
19 mm
Minimum thickness of exposed wiped surface on each side of a wiped joint and at least as thick as the material being joined
58
New cards
0.002 (0.2%)
Maximum lead content allowable for solders and fluxes in potable water piping
59
New cards
Schedule 80
Job-fabricated female screws
60
New cards
76 mm to 102 mm
Enlargement of closet bend from ___ shall be considered an obstruction
61
New cards
6.4 mm
Minimum width of continuous and indelibly colored stripe marking for hard drawn copper tubing
62
New cards
Type K
Green copper tubing
63
New cards
Type L
Blue copper tubing
64
New cards
Type M
Red copper tubing
65
New cards
Type DWV
Yellow copper tubing
66
New cards
19.56 kg/sq. m ; 1.6 mm thick
Minimum weight and thickness of sheet lead for lead safe pans
67
New cards
14.63 kg/sq. m ; 1.2 mm thick
Minimum weight and thickness of sheet lead for flashing or vent terminals
68
New cards
3.2 mm
Minimum wall thickness of lead bends and lead traps
69
New cards
178 mm Ø
Approximate diameter of closet rings or flanges
70
New cards
38 mm
Width of closet ring or flange
71
New cards
6.4 mm
Minimum thickness of caulked-on closet rings or flanges
72
New cards
51 mm
Minimum overall depth of caulked-on closet rings or flanges
73
New cards
4
Number of bolts per water closet
74
New cards
2%
Slope of threaded-type drainage fittings
75
New cards
102 mm or larger
Sizes of valves that shall have cast iron bodies
76
New cards
Less than 102 mm
Sizes of valves that shall have cast brass or bronze bodies
77
New cards
Up to 51 mm
Sizes of valves that shall be brass and bronze metal
78
New cards
1 psi
2.31 feet of head
79
New cards
1 psi
6.895 kPa
80
New cards
103.42 kPa or 15 psi
Minimum pressure for a group containing flushometer valves
81
New cards
55.16 kPa or 8 psi
Minimum pressure for a group containing flush tanks
82
New cards
9.79
Multiplier to the elevation above the water main to determine loss in static pressure
83
New cards
75%
Multiplier to the total demand for fixtures with combined hot and cold water to arrive in maximum separate demands
84
New cards
3 m/sec
Maximum velocity of water for sizing supply piping
85
New cards
14 m²
Minimum area of trench bottom for disposal field
86
New cards
1 ft to 3 ft
Sidewall area below the leach line may be added to the trench bottom absorption area
87
New cards
50%
Where leaching beds are permitted in lieu of trenches the area of each bed shall be at least ___ greater than the tubular requirements for trenches
88
New cards
1.5 m
Separation distance of leach bed excavation from the water table
89
New cards
3 m
Separation distance of seepage pit excavation from the water table
90
New cards
2
Minimum number of compartments of a septic tank (as per plumbing code)
91
New cards
3
Minimum number of compartments of a septic tank (as per new ordinance)
92
New cards
2/3 of tank capacity
Minimum capacity of inlet compartment
93
New cards
2 m³
Minimum liquid capacity of inlet compartment
94
New cards
1.5 m
Minimum length of inlet compartment
95
New cards
0.9 m
Minimum width of septic tank
96
New cards
1/3 of tank capacity
Maximum capacity of secondary compartment
97
New cards
1 m³
Minimum capacity of secondary compartment
98
New cards
1.5 m
Minimum length of secondary compartment if tank has over 6 m³ capacity
99
New cards
2
Minimum number of manholes for septic tank
100
New cards
508 mm
Minimum dimension of a manhole