Where Public Mode audible appliances are installed they shall be ____________ above average ambient sound level

15dba

2
New cards

Where audible appliances are installed in mechanical equipment rooms, the average ambient sound level is

85dba

3
New cards

An average ambient sound level greater than ______ shall require the use of a visible notification appliance

105dba

4
New cards

T/F: All fire detection devices shall be listed or approved for the purpose for which they are intended

True

5
New cards

A detector should not be recessed in any way unless they have been _______________ for such a mounting

listed and tested

6
New cards

How far from the doorway shall a Manual fire alarm station be mounted

5'

7
New cards

Vane type flow switch have no longer than _____ to initiate alarm

90 sec

8
New cards

smoke detectors must be tested every

1 year

9
New cards

Sensitivity in smoke detectors and single & multiple-station smoke alarms in other than 1&2 family dwellings shall be checked within _____ year or years after installation

1

10
New cards

A spot-type heat detector located on a wall shall not be more than _____ inches from the ceiling

12''

11
New cards

With a peak ceiling, heat and smoke detectors shall be located within _____ of the peak, measured horizontally

36'' (3 ft)

12
New cards

smoke detectors shall not be located near

Air supply diffusers

13
New cards

When beams project more than _____ inches below the ceiling and are more than 8' on center, each bay formed by the beams shall be treated as a separate area for heat detectors

18''

14
New cards

When manual fire alarm boxes are used, the distance between boxes will not be in excess of

200'

15
New cards

A water flow device should be field adjusted so that an alarm is initiated in no more than _____ seconds

90 seconds

16
New cards

smoke detectors shall not be located directly in the air stream of

supply registers

17
New cards

Detectors shall not be installed until after

Final clean up of all trades

18
New cards

a heat detector integrally mounted on a smoke detector shall be listed and approved for not less than

50'

19
New cards

Detectors for common return systems should be installed up to ______ in front or behind openings

12''

20
New cards

A line-type obsucration smoke detector, where the light beam is projected across the area to be protected

projected beam smoke detector

21
New cards

A device which detects the visible particles of combustion is a ____ detector

Smoke

22
New cards

Manual Fire alarm boxes shall not be less than _______ inches and not more than ______ inches above the floor level

42" (3.5 ft) /48" (4 ft)

23
New cards

single and multiple stations smoke alarms shall be tested after the initial installation test every ____

1 year

24
New cards

smoke detectors installed within _______ feet of cooktop or range must be of the _____ type

20 /photoelectric

25
New cards

Dwelling smoke alarms must produce an audible _____ signal for at least _____ minutes

evacuation/ 4 minutes

26
New cards

Rechargeable power supplies for smoke alarms must recharge in _____ hours or less when connected to a _____ portion of branch circuit

4/switched

27
New cards

smoke detectors must be installed within ______ feet of a door to a sleeping room

21 feet

28
New cards

Wall mounted heat detectors must be mounted between _____ and _____ inches from a ceiling

4''/12''

29
New cards

a fire alarm system must operate on standby for a period of not less than ______ days followed by at least ______ minutes of alarm

7/4

30
New cards

For spot type smoke detectors _____ feet shall be permitted to be used as a guide

30'

31
New cards

Actuation of alarm notification appliances or emergency voice communications. fire alarm safety functions, and annunciation at the protected premises shall occur within _____ seconds after the activation of the initiating device

10 seconds

32
New cards

the secondary power source for a fire alarm may be a battery with enough capacity to support the fire alarm panel with enough power to last for ______ hours after which it shall have enough capacity to sound the notification appliances for at least _______ minutes

24 hours/ 5 minutes

33
New cards

a fire alarm system is required to have _____ sources of power

2

34
New cards

If heat detectors are used to shut down elevator power prior to sprinkles operation, they shall be placed within _____ feet of each sprinkler head

2 feet

35
New cards

what type of fire alarm system transmits alarm to a public emergency fire service communications center

Municipal fire alarm system

36
New cards

The minimum decibel level for a fire alarm signal for a sleeping area is

75dBA

37
New cards

when the distance the ceiling and the top of the door is greater than ____ inches NFPA 72 states that you should have two smoke detectors on each side of the door

24 inches

38
New cards

Wall mounted audible notification appliances shall have their tops above finished floor at heights of not less than _____ inches and below the finished ceilings at distances not to exceed _____ inches

90'' (7' 6") / 6''

39
New cards

the mounting heights of a manual pull station shall be between ___ and ___ feet above finished floor

3 1-2/ 4 feet

40
New cards

Visible notification appliances shall be installed within ____ feet of the end of the corridor with a separation of no greater than _____ feet

15'/100'

41
New cards

a signaling method characterized by simultaneous or sequential transmission on both, and reception of multiple signals on a signaling line circuit, a transmission channel, or a communications channel, including means for positively identifying each signal.

Multiplexing

42
New cards

the number of water flow initiating devices permitted to be connected to a single initiating device circuit shall not exceed ________

5

43
New cards

you must be certified by the of Ohio if you are ___

installing fire pumps, fire alarm systems, testing and inspecting fire alarm systems

44
New cards

T/F: If your building is fully sprinklered, a pull station is not required

True

45
New cards

Circuit disconnecting means shall have a red marking, shall be accessible only to authorized personnel, and shall be identified as ________________________

"fire alarm circuit"

46
New cards

In corridors where _________________ visible notification appliances are in any field of view, they shall flash in sync.

more than 2

47
New cards

Installation of wiring, conduit, and equipment must be in accordance with NFPA 70 article _______________

760

48
New cards

Smoke detectors shall not be installed in ______________________ hoistways unless they are installed to activate the elevator hoistway smoke relief equipment

unsprinklered

49
New cards

T/F: Fire alarm signals and trouble alarms may have the same tone and characteristics as long as the lenses are painted different colors

False

50
New cards

T/F: The word "should" indicates a mandatory requirement

False

51
New cards

T/F: Central stations are offices which provide alarm and supervisory service and are located on the protected premises

False

52
New cards

A coded alarm signal shall consist of not less than _____ rounds of the number transmitted

3

53
New cards

Water flow in a sprinkler system shall be indicated by an alarm within

90 seconds

54
New cards

Are smoke detectors permitted to be in air stream

No

55
New cards

T/F: Fire alarm signals shall take precedence over any other signal even if a non-fire signal is activated first

True

56
New cards

T/F: Smoke detectors installed beneath raised floors or above suspended ceilings or both including raised floors and suspended ceilings used for environmental air may be used in lieu of providing detection within the room

False

57
New cards

T/F: Area smoke detectors within smoke compartments shall be used to control the spread of smoke by initiating operating controls and other equipment

True

58
New cards

Manual fire alarm boxes shall be ___ in color

Red

59
New cards

Initiating devices shall be supported independently from ___________________________

the circuit carrying conductors

60
New cards

When partitions extend to within ________ of the ceiling height, rooms separated by the partitions are not considered as separate rooms

15%

61
New cards

The name of photoelectric light obscuration where the beam spans the protected area is ___

Projected beam smoke detector

62
New cards

The _____________ of all detectors in air duct systems shall be permanently and clearly identiied and recorded

location

63
New cards

Audible alarm notification devices shall provide a sound level of _____ dBa above the average ambient sound level or ___ dBa above the maximum sound level having a duration of at least 60 seconds, whichever is greater, in every occupied space

15 dBa /5 dBa

64
New cards

Where a fire alarm serves more than one building each building shall be ___________________________

annunciated separately

65
New cards

___________________ refers to equipment or operation not required by NFPA standards or required by the AHJ

Supplementary

66
New cards

Smoke detector sensitivity shall be tested____

within one year of installation and every other year after

67
New cards

T/F: If your certification is suspended you can still work on a fire alarm systems, if the company for which you are employed is certfied

False

68
New cards

Spacing of detectors on a smooth ceiling shall be ___

30'

69
New cards

within how many seconds shall a trouble signal be returned to normal

200 seconds

70
New cards

T/F: All pneumatic line type heat detectors shall be tested for leak and proper operations at six month intervals

False

71
New cards

All household fire alarm equipment should have enough back up power to sound an alarm for _____ minutes

4 minutes

72
New cards

A __________________ installer is qualified and experienced under the requirements NFPA 72

State Licensed

73
New cards

T/F: Visible notification appliances designed to be wall mounted can be ceiling mounted, if the color is differentiated by a color other than red

False

74
New cards

Drawings that are used to install a job rae called

Shop drawings

75
New cards

Fire alarm specifications are usually developed by a(n) _________________, who is also responsible for designing the system

Engineer

76
New cards

Which signal indicates an off normal condition

Supervisory

77
New cards

Horns, bells, and chimes are ___ appliances

Notification

78
New cards

Transmission trouble signals by a supervising stations system must occur between ____ and ____ minutes

1/3

79
New cards

Secondary power supplies for fire alarm systems must operate that system in standby for a period of at least

24 hours

80
New cards

where required, survivability means that fire alarm circuits must operate for not less than ___

two hours

81
New cards

The most commonly used scale in drawings is

1/8" = 1 ft

82
New cards

A _____ is an unwanted activation of signaling or an alarm initiating device in response to a stimulus or condition that is not the result of potentially hazardous condition

Nuisance Alarm

83
New cards

A ______ is an unwanted activation of an alarm initiating or system output function where the cause is not been identified

Unknown alarm

84
New cards

A ____ is an unwanted alarm that occurred when there is no hazard condition present

Unwanted alarm

85
New cards

Smoke detectors found to have a sensitivity outside of the listed and marked sensitivity range shall be ____

cleaned and recalibrated or replaced

86
New cards

These detectors are tested after 15 years and every 5 years after by being removed and sent to a testing lab

non restorable spot type detectors

87
New cards

Photoelectric smoke detectors shall be no more than ____ feet away from an oven measured horizontally

6'

88
New cards

T/F: Water level supervisory signal initiating devices send out two signals, one when the water level has been raised or lowed, and one when it returns back to normal

True

89
New cards

For water level supervisory signal initiating devices in pressurized tanks, the signal will be initiated when the water falls or rises ______ inches

3 inches

90
New cards

For water level supervisory signal initiating devices in non-pressurized tanks, the signal will be initiated when the water falls ______ inches, but will not initiate if the water rises

12 inches

91
New cards

A secondary power supply shall have sufficient capacity to operate the system under a non alarm condition for a minimum of ___ hours and ____ minutes under a full load

24/5

92
New cards

Individuals who conduct a visual examination of the system to verify it is in operating condition, proper location, and free of physical damage

Inspection personnel

93
New cards

Individuals who perform those procedures, adjustments, replacements of components, system programming, and maintenance, as described, in the manufacturer service instructions that can affect any aspect of the performance of the system

service personnel

94
New cards

Carbon monoxide signals shall be permitted to take precedence over ___

supervisory and trouble signals

95
New cards

Ionization smoke alarms with an alarm silencing switch are not to be installed less than ____ horizontally from a permanently installed cooking appliance

10'

96
New cards

Smoke alarms shall be installed not less than ____ from the door or opening of a bathroom that contains a bathtub or shower unless this would prevent placement of a smoke alarm

3'

97
New cards

each floor shall be zoned___ and shall not exceed 22,500 sq ft

separately

98
New cards

where fire alarm systems are not monitored by supervising station and approve permanent sign shall be installed adjacent to each manual fire alarm box that reads

when alarm sounds contact fire department

99
New cards

In a corridor, visible appliances shall be rated not less than _____

15 candela

100
New cards

for smooth ceilings all points on the ceiling shall have a detector within a distance equal to ____ times the selected spacing

0.7