Article 625 covers the electrical conductors and equipment connecting an electric vehicle to premises wiring for the purposes of _____.
(D) all of these
“Electric vehicle supply equipment” includes the conductors and electric vehicle connectors, _____ installed specifically for the purpose of transferring energy between the premises wiring and the electric vehicle.
(D) all of these
Electric vehicle power export equipment, and electric vehicle supply equipment are sometimes contained in one piece of equipment, sometimes referred to as a “_____ EVSE”.
(C) bi-directional
“Wireless power transfer equipment” (WPTE) is equipment consisting of a charger power converter and a primary pad that are _____.
(C) separate units or contained within one enclosure
All equipment covered by the scope of Article 625 shall be _____.
(A) listed
Each outlet installed for the purpose of charging electric vehicles shall be supplied by an individual _____ circuit that shall have no other outlets.
(C) branch
Conductors that supply electric vehicle supply equipment shall be sized for continuous duty and have a rating of not less than 125 percent of the maximum load of the electric vehicle supply equipment.
(A) True
For electric vehicle equipment rated more than _____ or more than 150 volts-to-ground, the disconnecting means shall be provided and installed in a readily accessible location.
(D) 60A
The electric vehicle supply equipment located outdoors shall be located to permit direct electrical coupling of the EV connector (conductive or inductive) to the electric vehicle.
(A) True
The _____ of electric vehicle supply equipment located indoors shall be located not less than 18 in. above the floor level.
(D) coupling means
Where electric vehicle storage batteries are used or electric vehicle supply equipment is _____ for charging electric vehicles indoors without ventilation, mechanical ventilation shall not be required.
(A) listed
Where the equipment is listed for charging electric vehicles that require ventilation for _____ charging, mechanical ventilation, such as a fan, shall be provided. The ventilation shall include both supply and exhaust equipment and shall be permanently installed and located to intake from, and vent directly to, the _____.
(B) indoor, outdoors
In addition to the requirements in 210.8, all receptacles installed for the connection of electric vehicle charging shall have arc-fault circuit-interrupter protection.
(B) False