When pressurizing a low-pressure system for leak-detection purposes, do not exceed
10 psig
Which organization establishes the refrigerant safety group standard?
ASHRAE
After all the liquid has been removed from an average 350-ton, low-pressure appliance, approximately how much vapor refrigerant remains in the system?
100 pounds
The rupture disk on a low-pressure chiller has a burst pressure of;
15 psig
In a low-pressure chiller, air and other non-condensables collect at the;
top section of the condenser.
The Standard for machine room safety is;
ASHRAE-15
When leak testing a low-pressure chiller, the maximum pressure to use is;
10 psig
Where is refrigerant added to a low-pressure system during the charging process?
The lowest access point on the system such as the evaporator charging valve.