PE HVACR: Supportive Knowledge

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/72

encourage image

There's no tags or description

Looks like no tags are added yet.

Last updated 3:43 PM on 6/23/26
Name
Mastery
Learn
Test
Matching
Spaced
Call with Kai

No analytics yet

Send a link to your students to track their progress

73 Terms

1
New cards

ASHRAE 15?

Title: “Safety Standard for Refrigeration Systems”

CFMexhaust=100(lbrefrigerant)0.5CFM_{exhaust}=100\cdot\left(\operatorname{lb}_{refrigerant}\right)^{0.5} , use the largest circuit

2
New cards

ASHRAE 34?

Title: “Designation and Safety Classifications of Refrigerants”

Safety classifications of refrigerants in Handbook.

A1 least toxic and least flammable.

B3 most toxic and most flammable.

Designation, read from right to left if less than 3 digits:

R-(C−1)(H+1)(F)

3
New cards

ASHRAE 55?

Title: “Thermal Environmental Conditions for Human Occupancy”

Summer: 75 °F DB / 50% RH

Winter: 68 °F DB / 45% RH

Comfort conditions based on air velocity, temperature, humidity, clothing, activity level.

4
New cards

ASHRAE 62.1?

Title : “Ventilation for Acceptable Indoor Air Quality”

CFM/person and CFM/ft² guidelines in Handbook

Class 1 air: low contaminants and odors. (ex: office, classroom, conference room)

Class 2 air: moderate contaminants and odors. (ex: bathroom, shower, weightroom, gym)

Class 3 air: high contaminants and odors. (ex: janitor closets)

Class 4 air: highly contaminated and dangerous (ex: chemical storage, lab fumes, paint booths)

Anything Class 2+ needs to be exhausted or can be retruned to a higher class space.

5
New cards

ASHRAE 90.1?

Title: “Energy Standards for Buildings Except Low Rise Residential Buildings”

Minimum energy efficiency requirements for HVAC systems.

6
New cards

NFPA 90A?

Title: “Standard for the Installation of Air-Conditioning and Ventilating Systems”

Fire Protection Standard

Class 1 Flexible Duct (typical):

  • Flame Spread Index < 25

  • Smoke Index < 50

Fire dampers & Smoke dampers

7
New cards

NFPA 90B?

Title: “Standard for the Installation of Warm Air Heating and Air-Conditioning Systems”

Fire Protection Standard

8
New cards

NFPA 96?

Title: “Standard for Ventilation Control and Fire Protection for Commercial Cooking Operations”

Fire Protection Standard

Grease Exhaust Ducts need 304 stainless, 16 gauge, continuously welded.

9
New cards

NFPA 70?

Title: “National Electric Code”

Standards for electrical installations.

10
New cards

NFPA 54?

Title: “National Fuel Gas Code”

Standards for gas installations.

11
New cards

Montreal Protocol?

Phase out ozone-depleting substances, like CFC and HCFC refrigerants.

12
New cards

Refrigeration System Components?

Evaporator: Provides cooling, refrigerant evaporates into a gas. Low pressure.

Filter: Removes contaminants from refrigerant before entering compressor.

Accumulator: Place for any remaining refrigerant liquid to go (incase of insufficient heat to fully evaporate refrigerant), ensures only refrigerant gas enters the compressor.

Compressor: Compresses refrigerant gas.

Oil Separator: Separates oil from discharge refrigerant gas, and sends it back to the compressor.

Condenser: Rejects heat, refrigerant condenses into mostly liquid. Still high pressure. Determines amount of subcooling.

Reciever: Collects refrigerant liquid after condenser.

Dryer: Removes water moisture from system, prevents freezing.

Solenoid Valve: Opens/closes for refrigerant flow.

Sight Glass: Visual place to ensure no water/moisture buildup in system.

Expansion Valve: Lowers pressure from refrigerant down to evaporator pressure. Monitors super heat and regulates refrigerant flow.

Hot Gas Bypass: Applies heat from hot gas discharge to the evaporator to put a false load on the evaporator. Helps ensure only refrigerant gas enters the compressor. Typically active during reduced heat load in the space.

<p>Evaporator: Provides cooling, refrigerant evaporates into a gas. Low pressure.</p><p>Filter: Removes contaminants from refrigerant before entering compressor.</p><p>Accumulator: Place for any remaining refrigerant liquid to go (incase of insufficient heat to fully evaporate refrigerant), ensures only refrigerant gas enters the compressor.</p><p></p><p>Compressor: Compresses refrigerant gas.</p><p>Oil Separator: Separates oil from discharge refrigerant gas, and sends it back to the compressor.</p><p></p><p>Condenser: Rejects heat, refrigerant condenses into mostly liquid. Still high pressure. Determines amount of subcooling.</p><p>Reciever: Collects refrigerant liquid after condenser.</p><p>Dryer: Removes water moisture from system, prevents freezing.</p><p>Solenoid Valve: Opens/closes for refrigerant flow.</p><p>Sight Glass: Visual place to ensure no water/moisture buildup in system.</p><p></p><p>Expansion Valve: Lowers pressure from refrigerant down to evaporator pressure. Monitors super heat and regulates refrigerant flow.</p><p></p><p>Hot Gas Bypass: Applies heat from hot gas discharge to the evaporator to put a false load on the evaporator. Helps ensure only refrigerant gas enters the compressor. Typically active during reduced heat load in the space.</p><p></p>
13
New cards

Transmissibility? (Vibrations)

For small ratios: TR=11r2TR=\left|\frac{1}{1-r^2}\right|

Low Transmissibility → Damping is effective

High Transmissibility → Damping is ineffective

14
New cards

Acoustics?

Frequency → Determines Pitch

Sound Pressure → Determines Loudness

A-weighting → Considers different frequency bands for human hearing and weighs some frequencies more.

NC Rating → Use worst of all ratings at different frequencies

If distance doubles, sound drops by 6 dB. Sound level decreases by the square of the distance (inverse square law).

If sound pressure halves, sound drops by 6 dB.

15
New cards

USA frequency?

60 Hz

16
New cards

Control point types?

Digital: On/Off

Analog: 0-100%

17
New cards

Controls Inputs?

Signal received in to the BAS.

Switches, sensors

18
New cards

Controls Outputs?

Signal sent out from the BAS.

Dampers, valves, on/off buttons, actuators

19
New cards

Bypass Chiller Piping?

Maintain minimum flow to the chiller to prevent freezing.

20
New cards

Heat Pipe?

Sensible heat transfer only.

21
New cards

Equivalent Diameter?

For rectangular and oval ducts, determines equivalent circular duct size and allows us to use standard circular duct charts and equations.

First step before further calculations.

22
New cards

Cooling Tower Relief?

Lowers/resets CWS temperature to the chiller by taking advantage of cooler outside conditions and increasing cooling tower fan speeds. Results in energy savings at the chiller compressor, because it does not have to produce as much lift to achieve the same heat transfer. Reduces lift by decreasing discharge pressure, thus decreasing condenser temperature.

Chillers use more energy than cooling towers, so saving energy at the chiller is a priority.

23
New cards

Chilled Water Supply Temperature Reset?

Resets CHWS temperature according to load.

Reduces lift by increasing suction pressure and thus increasing evaporator temperature. Energy savings at the chiller compressor.

24
New cards

Lithium Bromide Absorption Chiller?

Water acts as a refrigerant.

Li Br acts as an absorbent.

25
New cards

1 Cooling Tower Ton?

1 CT Ton = 15,000 Btu/h

26
New cards

Most environmentally harmful chemical in refrigerants?

Chlorine, being phased out.

27
New cards

Payback Period?

Payback Period = Initial Cost / Yearly Gain

Formula in handbook considers Salvage Value, but this refers to the Salvage Value of the previously installed equipment that is being replaced.

28
New cards

Real Power (Useful Power)

Power that actually does the work and what is billed for.

Powerreal=IVPFPower_{real}=I\cdot V\cdot PF

Power Factor is how efficiently incoming power is converted to useful work.

Apparent Power is the total power the electrical system must supply (Electrical Engineer’s Job). Apparent Power - Real Power = Reactive Power, used to generate magnetic fields, moves back and forth, and is not actually consumed.

29
New cards

NTU?

Use when LMTD cannot be calculated.

30
New cards

Best way for windows to face for cooling design?

North, if in the Northern Hemisphere.

Sun angles from the South.

East and West receive direct sunlight at some point every day.

31
New cards

Time Delay?

Effects heat conduction from outside to space.

Metal → Low time delay & high thermal conductivity.

Concrete → High time delay & low thermal conductivity.

32
New cards

MERV?

MERV 1-6: <90% arrestance

MERV 7-14: <98% arrestance

MERV 18: >99% arrestance

33
New cards

Valve CvC_{v} ?

Valve Flow Coefficient, the GPM with 1 psi pressure drop across the valve fully open.

Higher CvC_{v} means the valve is larger and has less flow resistance

Lower CvC_{v} means the valve is smaller and has more flow resistance

Select a valve with a slightly higher CvC_{v} if the calculated value is between 2 table values.

34
New cards

ASHRAE Zones?

0 is really hot

8 is really cold

A is humid

B is dry

C is mild/mixed

35
New cards

Interpolating from a table?

yy1y2y1=xx1x2x1\frac{y-y_1}{y_2-y_1}=\frac{x_{}-x_1}{x_2-x_1}

36
New cards

Purpose of Pipe Supports?

Prevents the pipe from exceeding it’s allowable stress, determined by pipe material, pipe weight, fluid weight, thermal expansion, etc.

37
New cards

Expansion Tank types

Bladder: Uses replaceable “balloon”. Higher upfront cost, for higher pressures/larger systems. Can replace the balloon by itself if it fails.

Diaphragm: Uses permanently bonded flexible membrane. Lower initial cost, for smaller systems. Whole unit needs to be replaced if it fails.

38
New cards

Purpose of making duct long enough for 100% recovery?

Allows airflow from a fan to reach a uniform velocity profile, which will help minimize system effects.

9.3.6.7 in Handbook (Fan Outlet Conditions): Minimum duct length for 100% recovery equation.

39
New cards

On a cooling tower, what’s the most economical way to run the fans?

All fans at the same speed. By affinity laws, when a fan reduces in speed, there is a cubed reduction in power.

40
New cards

Pressure Dependent vs Pressure Independent VAV Terminal Unit?

Pressure Dependent: Thermostat controls damper % open to meet temperature setpoint. If main duct pressure changes (i.e. from other VAVs opening/closing), airflow volume changes even if the thermostat hasn’t moved. Thus, airflow depends on pressure. Less control, older systems.

Pressure Independent: Thermostat controls CFM to space, not directly the damper position, to meet temperature setpoint. An airflow sensor measures actual airflow, and the controller modulates the damper to maintain the target airflow even if main duct pressure changes. Thus, airflow is independent of pressure. More accurate control, standard in modern VAV systems.

41
New cards

Primary/Secondary (Decoupled) System?

Primary: Production, pumps constant speed

Secondary: Distribution, pumps variable speed

Bypass: Maintains constant flow through the chillers (or boilers). No valve.

<p>Primary: Production, pumps constant speed</p><p>Secondary: Distribution, pumps variable speed</p><p>Bypass: Maintains constant flow through the chillers (or boilers). No valve.</p>
42
New cards

Variable Primary System?

Variable speed pumps at the inlets of the chillers (or boilers)

Bypass: Valve opens to maintain minimum flow if needed. Typically closed. Flow meter signals to actuator to open/close the bypass valve.

<p>Variable speed pumps at the inlets of the chillers (or boilers) </p><p>Bypass: Valve opens to maintain minimum flow if needed. Typically closed. Flow meter signals to actuator to open/close the bypass valve.</p>
43
New cards

VAV Static Reset Strategies?

Damper Position Reset: Resets based on the most-open VAV damper position %

Flow Error Reset: Resets based on desired vs actual CFM at VAV boxes

Saturation Signal Reset: Resets based on overall VAV control effort (“saturation”) to meet zone demand

44
New cards

Fire Barrier Door ΔP\Delta P Purpose?

Maximum pressure differential to ensure the door can be opened by people during emergency.

Minimum pressure differential to keep smoke out.

Fire barriers, especially stairwells in high rises, use smoke control and pressurization systems to keep toxic gases from entering evacuation routes.

45
New cards

Fire Dampers? Dynamic vs Static?

Fire dampers close when high heat/fire melts a fusible link.

Dynamic Fire Dampers: Spring-loaded to close against moving airflow. Used where HVAC airflow continues during a fire.

Static Fire Dampers: Gravity-operated (or curtain-style) and rely on airflow stopping before fully closing. Used where HVAC shuts down during a fire.

46
New cards

Fan/Pump HP Rating Meaning

The fan/pump horsepower rating is the required brake horsepower (BHP) at design conditions, used to select the motor. Actual required horsepower varies with flow, pressure/head, and efficiency and is usually lower than or near the design value.

47
New cards

Motor HP Rating Meaning

The motor horsepower rating is the maximum continuous shaft power the motor can safely deliver under rated conditions. The motor supplies only the horsepower required by the load, up to its rated limit.

48
New cards

Space Fraction?

In lighting, its the amount of heat produced by the light fixture that is gained by the space. The rest of the fraction is heat gained by the plenum.

49
New cards

Absorprtion Chillers

LiBr & Water: Water is the Refrigerant, LiBr is the Absorbent. For AC/Chilled water.

Ammonia & Water: Ammonia (NH3) is the Refrigerant, Water is the Absorbent. For Industrial Refrigerantion/Low Temp.

No compressor, replaced with a generator and absorber.

50
New cards

Purpose of minimum velocity in kitchen exhaust grease ducts?

Ensure great particles, VOCs, and smoke are exhausted to outdoors. Grease deposits can become a fire hazard if not removed.

51
New cards

Static pressure sensor location for VAV systems?

Rule of thumb: 2/3 of the way down the main supply duct from the AHU, or just before the furthest major branch.

ASHRAE: 75% of the way down.

52
New cards

Sound modeling for Equipment?

Approximately modeled as radiating outward in a sphere from a point source.

53
New cards

Cooling Tower Icing Prevention?

Fan Capacity Control: Prevents overcooling of condenser water.

Reversing Fans: Warm saturated discharge air flows downward through the tower.

Basin Heater: Prevents basin water from freezing when load is low/off.

Insulating exposed pipes: Reduces heat loss and pipe freezing risk, often combined with heat tracing in colder climates.

54
New cards

Vertical vs Horiztontal Centrifugal Pumps?

Vertical: Smaller footprint (motor stacked on top, tall/compact). Harder to install and maintain.

Horizontal: Larger footprint (long/wide). Easier to install and maintain.

55
New cards

Steam Piping Facts

Horizontal piping should be sloped in the direction of steam flow to allow condensate to drip in the opposite direction of the steam flow.

Branch lines should be off the top of mainlines at a 45° or 90° angle.

Horizontal piping should use eccentric reducers, positioned with the flat side on top. Curved side on the bottom for draining condensate.

56
New cards

Steam Trap Facts

Steam traps remove condensate from the bottom of the steam branch and main legs, and returns to the boiler.

Required after steam coils.

Steam condensate needs to be removed because it can cause water hammer, corrosion, and retain air (reducing heat transfer).

57
New cards

Altitude increase effect on boilers?

As altitude increases, atmospheric pressure decreases. Air density decreases, thus reducing the amount of oxygen in the air. Fuel gas density also decreases, thus reducing the heating value.

The amount of air supplied must be increased to match the fuel to air ratio required.

Heater capacity is directly related to atmospheric pressure, so we can use altitude correction density factors from the handbook to find a new rating at a different eleveation. This follows the local gas heat content equation in the handbook 10.6.

58
New cards

Respiration rate?

In refrigeration (especially cold storage for fruits, vegetables, and other produce), the respiration rate describes the heat generated by the produce itself as it “breathes” biologically after harvest.

Produce continues converting sugars and oxygen into carbon dioxide, water, and heat.

59
New cards

Terminal Units

Located at the end of the ductwork that conditions and controls air delivered from the AHU. Terminal units can include components such as dampers, reheat coils (hot water or electric), sound attenuators, and sometimes a fan, depending on the type.

Constant volume (CAV) terminal unit: Delivers constant airflow to the zone and controls temperature using supply air temperature reset or terminal reheat.

VAV terminal unit: Modulates a damper to vary airflow to the zone while maintaining a relatively constant supply air temperature, typically from a central AHU.

Series fan-powered VAV terminal unit: Uses a continuously operating local fan in series with the primary air stream to maintain nearly constant total airflow and improve comfort, especially in perimeter zones.

Parallel fan-powered VAV terminal unit: Uses a local fan that operates only when needed (typically at low load or heating conditions) to supplement or replace primary air with plenum air, reducing energy use compared to series fan-powered units.

Induction VAV terminal unit: Uses high-velocity primary air to induce and mix plenum or room air without a local fan, improving air distribution and reducing required primary air at low loads. Older.

60
New cards

GWP

Global Warming Potential

Reference point is Carbon Dioxide, where GWP = 1

61
New cards

Evaporative Cooling Effectiveness?

Lower ambient wet-bulb → higher evaporative cooling effectiveness, since drier air allows more evaporation and greater latent heat removal (cooling towers, evaporative coolers).

62
New cards

Capillary tube

Fixed small diameter expansion device in very small systems like window AC units; refrigerant flow varies with pressure differential across the tube.

63
New cards

Compressor housing types

Hermetic: Compressor and motor in same housing, permanently sealed. Motor heat added to refrigerant.

Semi-hermetic: Compressor and motor in same housing, not permanently sealed. Serviceable. Motor heat added to refrigerant.

Open drive: Compressor and motor are separate. Motor heat not added to refrigerant.

64
New cards

Sound types

Airborne Sound: Sound transmitted through air, via direct line of sight or reflected off environment.

Aerodynamic Sound: Sound from airflow turbulence, dependent on air velocity. Problem at duct fittings, dampers, and terminal units.

Ductborne Sound: Sound through ducts from fans or other spaces. Can travel upstream and downstream.

65
New cards

Frequency types and avoiding resonance?

Natural Frequency: Frequency at which a system freely vibrates due to its mass and stiffness.

Operating (Disturbing) Frequency: Frequency of the forcing function during normal operation (often RPM/60).

Resonance: Condition occurring when operating frequency equals or closely matches natural frequency, causing large vibration amplitudes.

Avoid resonance by decreasing the natural frequency by using softer spring vibration isolators.

Avoid resonance by decreasing the disturbing frequency by decreasing fan speed.

66
New cards

Infiltration driving force?

Positive pressure outside and negative pressure inside.

Stack effect (warm air inside has lower density, rises, and creates negative pressure)

Wind

67
New cards

Good piping materials for heat and pressure?

Steel and Copper

Cast iron should not be used under pressure due to its inherent brittleness, corrosion vulnerability, and joint weaknesses make it prone to catastrophic bursts!

68
New cards

Cooling tower types?

Forced Draft Colling Tower → Pushes air in with bottom mounted fans. Positive pressure inside the tower.

Induced Draft Cooling Tower → Pulls air out with with top mounted fans. Negative pressure inside the tower. Most common HVAC type.

Natural Draft Cooling Tower → No fans. Stack effect creates airflow. Common at power plants.

69
New cards

Chilled water chemical feed use?

Controls pH, minerals, and biological growth in the water. Helps prevent corrosion and biological scale.

70
New cards

Purge use in a chiller?

Removes air and water vapor from refrigeration cycle. Non-condensable gases reduce condenser performance so purge is placed before condenser.

71
New cards

Useful Refrigerant Info in Handbook?

8.6 Comparative Refrigerant Performance per Ton Refrigeration (at various evaporator temps, provided COPs, pressures, etc)

8.9 Refrigerant Safety (Safety classifications and chemical formulas)

72
New cards

Useful Boiler Combustion Info in Handbook?

10.1 Heating Values (LHV and HHVs for common fuels)

10.3 Stoichiometric Combustion of Fuels (air requirements, theoretical CO2 values, thermal efficiency, and combustion reactions)

73
New cards

Traits of higher efficiency boilers, considering the same fuel.

Lower leaving flue gas temperature → More heat was transferred to the water/steam and less heat was lost up the stack.

Lower excess air → Less energy is wasted heating unnecessary air that leaves through the stack.

  • Higher CO₂ in flue gas → Indicates less excess air dilution and more effective use of combustion air.

  • Lower O₂ in flue gas → Indicates less excess air is leaving the boiler unused.

Low CO in flue gas → Indicates more complete combustion and less fuel energy lost to incomplete combustion.