1/27
Looks like no tags are added yet.
Name | Mastery | Learn | Test | Matching | Spaced | Call with Kai |
|---|
No analytics yet
Send a link to your students to track their progress
13.1 What electrical systems serve residences vs small commercial (~100 kVA)?
Residences: 120/240 V single-phase, 3-wire; Small commercial: 120/208 V three-phase, 4-wire (handles larger and mixed loads).;
13.2 What systems serve mixed single-phase and three-phase loads?
120/208 V, 3-phase, 4-wire system (provides both 120 V and 208 V).;
13.3 What is voltage spread? Voltage drop?
Voltage spread = difference between highest and lowest system voltages; Voltage drop = reduction in voltage along conductors due to resistance.;
13.4 Max motor size on 100-kVA single-phase system? Why lower?
Typically limited to ~20–30 kVA; large motors cause voltage drop, imbalance, and starting issues → must be much smaller than system rating.;
13.5 Voltage to ground (120/208 V, 3φ, 4-wire)?
120 V (line-to-neutral voltage).;
13.6 Voltage to ground (480 V, 3φ, 3-wire)?
Typically ~277 V if grounded system (480/277 system); if ungrounded, no defined voltage to ground.;
13.7 Why should systems be grounded?
Safety, fault protection, and stable voltage reference.;
13.8 Must all electrical systems be grounded?
No, but most building systems are grounded for safety and code compliance.;
13.9 Should switchboard IC be higher or lower than short-circuit current?
Higher; must safely interrupt maximum possible fault current.;
13.10 Examples of NEC wire types and temp ratings?
THHN (90°C), THWN (75–90°C), XHHW (90°C); insulation type determines rating.;
13.11 Best on-floor power system for high-rise office?
Raised floor or modular underfloor distribution → flexible for computers and layout changes.;
13.12 Switches for control from two locations?
Two 3-way switches (no 4-way needed unless more than two locations).;
13.13 Advantages of fuses vs circuit breakers?
Fuses: fast, reliable, cheap; Breakers: reusable, convenient, adjustable.;
13.14 Currents in 120/240 V system (1500 W & 1000 W loads)?
I1 = 1500/120 = 12.5 A; I2 = 1000/120 ≈ 8.3 A; Neutral = difference ≈ 4.2 A (loads on opposite legs).;
13.15 Short-circuit current (5% impedance, 500 A full load)?
Isc ≈ 500/0.05 = 10,000 A (fault current increases as impedance decreases).;
13.16 NEC ampacity for #3/0 conductor?
≈ 200 A (single); reduced with multiple conductors (derating); conduit size depends on fill (use NEC tables).;
13.17 Best distribution system for 20,000 ft² school?
Use 480/277 V 3-phase for mechanical loads and lighting; step down to 120/208 V for receptacles.;
13.18 Standard Europe frequency and voltage?
50 Hz; ~230 V single-phase (utilization).;
13.19 Line-to-line voltage from line-to-neutral?
V_LL = √3 × V_LN → 220→~381 V; 2400→~4157 V.;
13.20 Max short-circuit current (300 kVA, 480 V, 3φ, 3% impedance)?
Isc ≈ (300,000)/(1.732×480×0.03) ≈ 12,000 A.;
13.21 If voltage is 240 V instead of 480 V?
Isc doubles → ≈ 24,000 A (lower voltage → higher current for same power).;
13.22 Required interrupting capacity?
Must exceed calculated Isc → ≥12 kA and ≥24 kA respectively (choose higher safety margin).;
13.23 Three alternative power sources?
Utility power, on-site generators, renewable sources (e.g., solar).;
13.24 Difference between K-4 and K-13 transformers?
K-13 handles higher harmonic loads (e.g., electronics) than K-4.;
13.25 Why are large cables stranded?
More flexible, easier installation, reduces mechanical stress.;
13.26 Standby vs uninterruptible power?
Standby: backup with delay; UPS: instant power with no interruption.;
13.27 Functions of K-type transformers, UPS, SPD?
K-type: handle harmonics; UPS: provide continuous power; SPD: protect against voltage surges.;
13.28 Generator indoors vs outdoors (pros/cons)?
Indoors: protected, quieter; needs ventilation; Outdoors: easier exhaust, less noise inside, but exposed to weather.