How long is the emergency replacement chimney form good for and whose responsibility is it to see that it is replaced?

90 days (and the licensees)

2
New cards

What needs to be performed before all new heat installations?

Heat loss and Load calculations

3
New cards

A fill pipe should be how many feet from any building opening?

2 feet

4
New cards

What must be done when performing an annual tune-up on a heating system?

Efficiency test copy posted on site

5
New cards

Whenever a furnace, direct fired hot water heater, or boiler is installed the total installation must be brought into compliance with what requirements BEFORE appliance can be fired?

NFPA 31

6
New cards

When outside tanks are used a thermally operated shut off valve must be installed where?

Where the supply line enters the inside of the building and where the oil line enters the room where the appliance is located

7
New cards

When inside tanks are used and the oil supply tank is installed in a separate room, a thermally shutoff valve must be installed where?

Where the line enters the room where the appliance is located

Whenever the oil supply is taken from the top of an oil tank a thermally operated wheel or lever

8
New cards

type shut-off valve must be installed where?

At the tank and at the burner

9
New cards

What can be installed in the supply line but not the return?

Check Valve/Back flow Preventer

10
New cards

All copper oil supply and return lines must be encased in a continuous piece of non-metallic liquid tight conduit such as

PVC, ENT, coated copper tubing.

11
New cards

The end of the conduit shall not exceed how far from any connection except the connection at fuel tank?

2 inches

12
New cards

TT terminals are normally used for?

Thermostat

13
New cards

The stack mount primary control must be ______ prior to use.

Put in step

14
New cards

The cad cell control will go to the lock out position when a reading of ______ ohms are found at the cad cell.

1600

15
New cards

When the FF terminals are jumped after starting up and the controls goes into lock out what is the correct action?

Replace Control

16
New cards

What is the normal temperature setting of a high limit control?

200 F

17
New cards

What is the purpose of the fan in the oil burner?

To mix air with the fuel

18
New cards

What is the normal secondary voltage of an ignition transformer?

10000

19
New cards

What type of ignition turns off after flame is established?

Interrupted duty

20
New cards

What type of ignition stays in while the burner is running?

Intermittent duty

21
New cards

What is the normal voltage output for an Ignitor?

14000

22
New cards

For natural draft appliances the horizontal length of chimney connector shall not exceed how many feet?

10ft

23
New cards

When shall chimney connectors be permitted to pass through a combustible wall or partition?

When Type L vent pipe is used

24
New cards

The chimney connector shall have a minimum pitch of what?

1/4" per foot

25
New cards

What type of fuel burning appliances shall be permitted to be connected to the same flue?

Gas is allowed; solid fuel is not

26
New cards

Minimum thickness for steel pipe connectors: Up to 9in, 9 to 10, 10 to 16, and >16

Sheet metal gauge 26, 24, 22, and 16 respectively

27
New cards

All portions of a mechanical draft system under positive pressure during operation shall be designed and installed as to prevent what?

Leakage of flue gas into the building

28
New cards

Where should combustion air inlet and flue gas outlet of a DIRECT VENT appliance terminate in relevance to each other?

The same plane/ambient zone

29
New cards

Any air inlet and any flue gas outlet of any appliance shall terminate how many feet from the vent outlet of a liquid fuel supply tank?

5 feet

30
New cards

Tanks and their supports shall rest on a foundation made of what?

Solid Concrete

31
New cards

What type of fitting shall not be used?

Cast iron

32
New cards

Where shall the connections in underground tanks be?

Top of the tank

33
New cards

What size should a fill pipe be?

1 1/4

34
New cards

Vent pipes shall terminate not more than how many feet from the fill pipe and a point visible from the fill point?

12 feet

35
New cards

The fuel piping between the tank and the appliance shall be what size?

3/8

36
New cards

When the primary control relay is chattering what is the main cause of this condition?

Low Voltage

37
New cards

The following list of terminals in the Honeywell 8124 are connected to what devices? (1, B1, ZC, ZR, TT)

1- line 1; B1- burner 1; ZC- zone control; ZR- zone request; TT- thermostat

38
New cards

What type of control monitors the liquid level in a boiler?

low water cut off

39
New cards

What is the purpose of the heat anticipator?

prevent short cycling

40
New cards

When a limit control closes its contacts on a rise in temperature it is said to be

Reverse acting

41
New cards

What is not an advantage to using a PSC burner motor?

Runs at full RPM

42
New cards

When a new burner is installed, what wiring must also be updated?

Breaker, properly rated wiring, properly installed and located emergency switch, properly installed and located thermal electric switch, properly installed and located service switch and properly installed and located low water cut off

43
New cards

Who shall be consulted before welding a heat exchanger?

the manufacturer

44
New cards

A master or journeyman plumber shall not:

Pipe an oil tank, install any electrical wiring unless licensed, install safety equipment, install any portion of the venting system, install thermostats and relays

45
New cards

A master or journeyman plumber shall:

Connect radiation, supply mains, valves etc, connect supplies and returns to boilers, connect make-up water to boiler, install back flow preventer, connect domestic water piping to tank-less indirect or direct fire water heater

46
New cards

A master or journeyman Oil Tech may do what electrical items?

Install branch circuit, fittings, devices and raceways for powering oil, solid fuel and propane or natural gas systems as well as motors or controls.

47
New cards

A master or journeyman oil tech may not do what electrical item?

Install a kickspace heater

48
New cards

In order to avoid undetected oil leaks under floors, the conduit must be how much bigger than the supply and return lines?

One pipe size larger

49
New cards

An oil line that penetrates a foundation wall must be? -

Sealed

50
New cards

When an oil filter or other accessory equipment is connected to a copper piping smaller than 3/4" and is not directly connected to the oil tank or burner the filter or other device must be what

Rigidly supported by hangers or mounted brackets

51
New cards

What must supply and return lines be connected with?

Flare fittings

52
New cards

What fittings shall not be used unless for introduction of lines at top of the tank with a single or double tap bushing?

Compression

53
New cards

All connections of supply or return oil lines located outside must be made with what?

flare frost fittings

54
New cards

All fuel oil supply tanks must be a minimum of how many feet from any gas or solid fuel burning appliance?

5 feet

55
New cards

All outside tanks should NOT be installed on?

Wood or combustible material

56
New cards

All oil supply tanks must be liquid tight. Leaking tanks may be temporarily repaired with a tank patch, this patch is good for how long?

30 days

57
New cards

For steam safety or pressure relief valves which terminate inside the structure must terminate how far above the floor?

6 to 12 inches

58
New cards

Steam safety and pressure relief valves on boilers must be installed with the spindle in what position?

upright vertical position

59
New cards

How far should oil burners be installed from an electrical panel?

3feet

60
New cards

How far should oil burners be installed from an unenclosed fuel oil tank?

5 feet

61
New cards

Screens used in louvers and grilles shall not be smaller than?

¼ mesh

62
New cards

Two or more oil burning appliances shall be permitted to be connected to a single chimney when?

When there is adequate draft

63
New cards

What shall be provided for each oil burning appliance that is connected to a chimney or power vent, unless designed, conditions of install, or combination, or appliance is listed for use without one?

Draft Regulator

64
New cards

What size should a chimney connector be?

as short as possible

65
New cards

A duct furnace shall have what clearance to walls, ceilings, and floors of combustible materials?

6 inches

66
New cards

A duct furnace flue pipe shall be installed to provide a clearance to combustibles of how many inches?

18 inches

67
New cards

What percent of heating oil is carbon and what percent is hydrogen?

85% Carbon, 15% Hydrogen

68
New cards

What NFPA do chimneys fall under?

211

69
New cards

To prevent undetected oil leaks under floors the conduit must penetrate the cement or earth surface a minimum of what inches above grade?

2 inches

70
New cards

No oil supply line shall be connected in a wall, ceiling, or partitions unless what?

Access can be made without cutting through existing wall, ceilings or partitions

71
New cards

How many apprentices can a journeyman directly supervise?

2

72
New cards

When outside tanks are used a ______ must be installed where the supply line enters (inside) the building.

Thermally operated shut off valve

73
New cards

The minimum clearance under an outside oil tank to any surface is?

4 inches

74
New cards

What is the required thickness of the vertical oil tank pad?

3 inches of reinforced concrete

75
New cards

What is the maximum length for the legs on an inside oil tank installed on a finished cement floor?

12 inches

76
New cards

What is the maximum size of mini-split heat pump a Journeyman Technician may install in a one and two family dwelling?

Mini-splits with heating and cooling capacity of 36,000 BTUs maximum.

77
New cards

What size vent is required for a waste oil tank?

2 inches

78
New cards

If an oil line passes through a wall what must be installed?

Firomatic valve

79
New cards

Who is responsible for ensuring repairs or the chimney is lined within the 90 days?

installer/licensee

80
New cards

The low-water cut off must be located where?

6 inches above boiler crown sheet but in no case below

81
New cards

What must be installed within 18 inches of a water heater?

expansion tank

82
New cards

The following factors affect cad cell performance except:

thermostat setting

83
New cards

A switching relay can be used to:

Control a line voltage device with low voltage controller, control a low voltage device with a line voltage controller, OR control two devices from a single controller

84
New cards

Safety timing is the same as flame response. True or False?

False

85
New cards

How do you take a control out of latch up?

Press reset and hold for 60 seconds.

86
New cards

The red wire on Carlin microprocessor controls is for what purpose?

Post Purge

87
New cards

The normal ohms range for a cad cell during burning operation?

300-1000

88
New cards

Electrode insulators should be removed and cleaned to new condition and inspected for hair line cracks when investigating rough starts, delayed or no ignition. True or False?

True

89
New cards

What is the purpose of the motor overload switch?

Prevent fires, protect motor, and interrupt power if motor is hot

90
New cards

What determines the proper electrode setting for each oil burner?

The Burner Manufacturer

91
New cards

Interrupted ignition prolong the life of the ignition system components. True or False?

True

92
New cards

How do we supply power for the post purge circuit?

Line 1

93
New cards

Before using an ohmmeter to test a capacitor start motor you should

discharge the capacitor

94
New cards

What is the advantage to pre-purge operation of an oil burner?

Start air flow, cleaner ignition, and pump is at full pressure

95