How long is the emergency replacement chimney form good for and whose responsibility is it to see that it is replaced?
90 days (and the licensees)
What needs to be performed before all new heat installations?
Heat loss and Load calculations
A fill pipe should be how many feet from any building opening?
2 feet
What must be done when performing an annual tune-up on a heating system?
Efficiency test copy posted on site
Whenever a furnace, direct fired hot water heater, or boiler is installed the total installation must be brought into compliance with what requirements BEFORE appliance can be fired?
NFPA 31
When outside tanks are used a thermally operated shut off valve must be installed where?
Where the supply line enters the inside of the building and where the oil line enters the room where the appliance is located
When inside tanks are used and the oil supply tank is installed in a separate room, a thermally shutoff valve must be installed where?
Where the line enters the room where the appliance is located
Whenever the oil supply is taken from the top of an oil tank a thermally operated wheel or lever
type shut-off valve must be installed where?
At the tank and at the burner
What can be installed in the supply line but not the return?
Check Valve/Back flow Preventer
All copper oil supply and return lines must be encased in a continuous piece of non-metallic liquid tight conduit such as
PVC, ENT, coated copper tubing.
The end of the conduit shall not exceed how far from any connection except the connection at fuel tank?
2 inches
TT terminals are normally used for?
Thermostat
The stack mount primary control must be ______ prior to use.
Put in step
The cad cell control will go to the lock out position when a reading of ______ ohms are found at the cad cell.
1600
When the FF terminals are jumped after starting up and the controls goes into lock out what is the correct action?
Replace Control
What is the normal temperature setting of a high limit control?
200 F
What is the purpose of the fan in the oil burner?
To mix air with the fuel
What is the normal secondary voltage of an ignition transformer?
10000
What type of ignition turns off after flame is established?
Interrupted duty
What type of ignition stays in while the burner is running?
Intermittent duty
What is the normal voltage output for an Ignitor?
14000
For natural draft appliances the horizontal length of chimney connector shall not exceed how many feet?
10ft
When shall chimney connectors be permitted to pass through a combustible wall or partition?
When Type L vent pipe is used
The chimney connector shall have a minimum pitch of what?
1/4" per foot
What type of fuel burning appliances shall be permitted to be connected to the same flue?
Gas is allowed; solid fuel is not
Minimum thickness for steel pipe connectors: Up to 9in, 9 to 10, 10 to 16, and >16
Sheet metal gauge 26, 24, 22, and 16 respectively
All portions of a mechanical draft system under positive pressure during operation shall be designed and installed as to prevent what?
Leakage of flue gas into the building
Where should combustion air inlet and flue gas outlet of a DIRECT VENT appliance terminate in relevance to each other?
The same plane/ambient zone
Any air inlet and any flue gas outlet of any appliance shall terminate how many feet from the vent outlet of a liquid fuel supply tank?
5 feet
Tanks and their supports shall rest on a foundation made of what?
Solid Concrete
What type of fitting shall not be used?
Cast iron
Where shall the connections in underground tanks be?
Top of the tank
What size should a fill pipe be?
1 1/4
Vent pipes shall terminate not more than how many feet from the fill pipe and a point visible from the fill point?
12 feet
The fuel piping between the tank and the appliance shall be what size?
3/8
When the primary control relay is chattering what is the main cause of this condition?
Low Voltage
The following list of terminals in the Honeywell 8124 are connected to what devices? (1, B1, ZC, ZR, TT)
1- line 1; B1- burner 1; ZC- zone control; ZR- zone request; TT- thermostat
What type of control monitors the liquid level in a boiler?
low water cut off
What is the purpose of the heat anticipator?
prevent short cycling
When a limit control closes its contacts on a rise in temperature it is said to be
Reverse acting
What is not an advantage to using a PSC burner motor?
Runs at full RPM
When a new burner is installed, what wiring must also be updated?
Breaker, properly rated wiring, properly installed and located emergency switch, properly installed and located thermal electric switch, properly installed and located service switch and properly installed and located low water cut off
Who shall be consulted before welding a heat exchanger?
the manufacturer
A master or journeyman plumber shall not:
Pipe an oil tank, install any electrical wiring unless licensed, install safety equipment, install any portion of the venting system, install thermostats and relays
A master or journeyman plumber shall:
Connect radiation, supply mains, valves etc, connect supplies and returns to boilers, connect make-up water to boiler, install back flow preventer, connect domestic water piping to tank-less indirect or direct fire water heater
A master or journeyman Oil Tech may do what electrical items?
Install branch circuit, fittings, devices and raceways for powering oil, solid fuel and propane or natural gas systems as well as motors or controls.
A master or journeyman oil tech may not do what electrical item?
Install a kickspace heater
In order to avoid undetected oil leaks under floors, the conduit must be how much bigger than the supply and return lines?
One pipe size larger
An oil line that penetrates a foundation wall must be? -
Sealed
When an oil filter or other accessory equipment is connected to a copper piping smaller than 3/4" and is not directly connected to the oil tank or burner the filter or other device must be what
Rigidly supported by hangers or mounted brackets
What must supply and return lines be connected with?
Flare fittings
What fittings shall not be used unless for introduction of lines at top of the tank with a single or double tap bushing?
Compression
All connections of supply or return oil lines located outside must be made with what?
flare frost fittings
All fuel oil supply tanks must be a minimum of how many feet from any gas or solid fuel burning appliance?
5 feet
All outside tanks should NOT be installed on?
Wood or combustible material
All oil supply tanks must be liquid tight. Leaking tanks may be temporarily repaired with a tank patch, this patch is good for how long?
30 days
For steam safety or pressure relief valves which terminate inside the structure must terminate how far above the floor?
6 to 12 inches
Steam safety and pressure relief valves on boilers must be installed with the spindle in what position?
upright vertical position
How far should oil burners be installed from an electrical panel?
3feet
How far should oil burners be installed from an unenclosed fuel oil tank?
5 feet
Screens used in louvers and grilles shall not be smaller than?
¼ mesh
Two or more oil burning appliances shall be permitted to be connected to a single chimney when?
When there is adequate draft
What shall be provided for each oil burning appliance that is connected to a chimney or power vent, unless designed, conditions of install, or combination, or appliance is listed for use without one?
Draft Regulator
What size should a chimney connector be?
as short as possible
A duct furnace shall have what clearance to walls, ceilings, and floors of combustible materials?
6 inches
A duct furnace flue pipe shall be installed to provide a clearance to combustibles of how many inches?
18 inches
What percent of heating oil is carbon and what percent is hydrogen?
85% Carbon, 15% Hydrogen
What NFPA do chimneys fall under?
211
To prevent undetected oil leaks under floors the conduit must penetrate the cement or earth surface a minimum of what inches above grade?
2 inches
No oil supply line shall be connected in a wall, ceiling, or partitions unless what?
Access can be made without cutting through existing wall, ceilings or partitions
How many apprentices can a journeyman directly supervise?
2
When outside tanks are used a ______ must be installed where the supply line enters (inside) the building.
Thermally operated shut off valve
The minimum clearance under an outside oil tank to any surface is?
4 inches
What is the required thickness of the vertical oil tank pad?
3 inches of reinforced concrete
What is the maximum length for the legs on an inside oil tank installed on a finished cement floor?
12 inches
What is the maximum size of mini-split heat pump a Journeyman Technician may install in a one and two family dwelling?
Mini-splits with heating and cooling capacity of 36,000 BTUs maximum.
What size vent is required for a waste oil tank?
2 inches
If an oil line passes through a wall what must be installed?
Firomatic valve
Who is responsible for ensuring repairs or the chimney is lined within the 90 days?
installer/licensee
The low-water cut off must be located where?
6 inches above boiler crown sheet but in no case below
What must be installed within 18 inches of a water heater?
expansion tank
The following factors affect cad cell performance except:
thermostat setting
A switching relay can be used to:
Control a line voltage device with low voltage controller, control a low voltage device with a line voltage controller, OR control two devices from a single controller
Safety timing is the same as flame response. True or False?
False
How do you take a control out of latch up?
Press reset and hold for 60 seconds.
The red wire on Carlin microprocessor controls is for what purpose?
Post Purge
The normal ohms range for a cad cell during burning operation?
300-1000
Electrode insulators should be removed and cleaned to new condition and inspected for hair line cracks when investigating rough starts, delayed or no ignition. True or False?
True
What is the purpose of the motor overload switch?
Prevent fires, protect motor, and interrupt power if motor is hot
What determines the proper electrode setting for each oil burner?
The Burner Manufacturer
Interrupted ignition prolong the life of the ignition system components. True or False?
True
How do we supply power for the post purge circuit?
Line 1
Before using an ohmmeter to test a capacitor start motor you should
discharge the capacitor
What is the advantage to pre-purge operation of an oil burner?
Start air flow, cleaner ignition, and pump is at full pressure