WATER SUPPLYSYSTEM
consists of the piping and fittings which supply cold water from the
building water supply to the fixtures.
CORPORATION COCK/STOP
is inserted into the water main. It serves as a control of the water
service. And also serve as a shut off, when the service is disconnected.
HOUSE SERVICE PIPE
refers to the pipe connection from public water main or any source of water
supply to the building served.
GOOSE NECK
the part of a pipe curve like the neck of a goose, usually flexible.
CURB STOP
is installed between the curb and the sidewalk line accessible to cast iron stop box equipped with removable cover. It serves as control stop of the service between the curb and the building.
METER STOP
A valve placed at the street side of the water meter and serves as a controlling device for the building installation.
WATER METER
is a device used to measure the amount of water that passes through the water
service.
HORIZONTAL SUPPLY MAIN
OR DISTRIBUTION MAIN
the pipe within the structure or premises
which conveys water from service pipe to point of utilization.
RISER
water supply pipe that extends one full story or more to convey water
FIXTURE BRANCH
the supply pipe between fixture supply pipe and distribution pipe.
FIXTURE SUPPLY
water supply pipe connecting fixture to fixture
branch.
DIRECT UP-FEED
TYPE OF COLD WATER DISTRIBUTION, Normal water pressure from the public water main
PNEUMATIC AIR-PRESSURE SYSTEM
TYPE OF COLD WATER DISTRIBUTION, when pressure supplied by water service provider is
not enough
DOWN-FEED SYSTEM
TYPE OF COLD WATER DISTRIBUTION, water is pumped into a large tank on top of building and distributed to fixtures by means of gravity.
180 oF (82 oC):
HOT WATER DISTRIBUTION SYSTEM, Minimum temperature needed for sanitizing rinse.
140 oF (60 oC)
HOT WATER DISTRIBUTION SYSTEM, For General-purpose cleaning and food preparation.
105 oF to 120 oF (41 oC to 49 oC)
HOT WATER DISTRIBUTION SYSTEM, For showers
Up-feed and gravity return
commonly used in small residential houses and other industrial
installations with the follow service features:
1. It provides constant circulation of hot water
2. Hot water is quickly drawn from the fixtures at any desired time.
3. Provide economical circulating return of unused hot water.
4. Eliminate waste of water.
Overhead feed and gravity return
is an efficient type of hot water distribution generally used in building of extreme heights.
Pump circuit system
is a mechanical device used to circulate hot water to the plumbing
fixtures. It is recommended for large building where difficulty of providing natural circulation of hot water is encountered.
PUMPS
is a device used to move fluids.
Centrifugal Pump
use an impeller, which has curved blades that accelerate fluids towards their edge when rotating. The energy changes occur by virtue of two main parts of the pump, the impeller and volute or casing. The function of the casing is to collect the liquid discharged by the impeller and convert some of the kinetic (velocity) energy into pressure energy.
Centrifugal Pump
are the most common type of pump use, since they are suitable for handling water and relatively easy to manufacture. These pumps also tend to be the most affordable.
Axial flow
Produces flow along the same direction as the impeller shaft, and is also known as propeller pump
Radial flow
Produces flow perpendicular to shaft
(90 deg. Angle.)
Mixed Flow
Combines radial and axial flow, producing a conical flow pattern
around the impeller shaft
Positive Displacement Pumps
capture confined amounts of liquid and transfers it from the suction to the discharge port. Base on how the fluid is displaced, positive displacement pumps can be reciprocating or rotary.
Reciprocating
Works by the repeated back-and- forth movement (strokes) of either a
piston, plunger or diaphragm. These cycles are called reciprocation.
Rotary
Uses a rotor that traps water in cavities, releasing it at the pump
outlet. These cavities can be the spaces between gear teeth or screw
threads, among other configurations.
CENTRIFUGAL PUMP
Effect of system pressure, Flow is reduced when system
pressure increase.
POSITIVE DISPLACEMENT PUMP
Effect of system pressure, Constant flow, If system pressure increases, the pump produces more pressure as well.
CENTRIFUGAL PUMP
Effect of viscosity, Higher fluid viscosity reduces flow rate. Pumping efficiency drops as viscosity increases.
POSITIVE DISPLACEMENT PUMP
Effect of viscosity, Higher fluid viscosity increases flow rate.
Submersible Pump
are close-coupled pumps driven by a submersible motor and designed for
submerged installation in a wet well.
Turbine Pumps
are centrifugal pumps specially designed to move water from an underground
well or reservo
Pneumatic Pumps
compressed air is used to move the liquid.
Cistern
usually built of reinforced concrete underground and connected with a pump.
Overhead tank / Gravity Supply Tank
are placed over the head that is built on a certain height,
relies on gravity to supply water to fixtures below. Use in overhead feed system.
Pneumatic Water Tank
is designed to store water and air under pressure. It is use in the air
pressure system and often used with a pump.
Hot Water Tank
is to serve the domestic hot water system. The tank should be strong enough to resist the high pressure of hot water stored in it.
Range Boiler
small hot water tank (30cm to 60cm diameter and legth not more than 180cm)
Storage Boiler
large hot water tank (60cm to 130cm and not more than 5m long)
GATE VALVE (Full-way Valve)
used to completely close, or open the line but not necessarily
to control the flow of water.
The Wedged Shape or Tapered Disc
is used where the stem must be installed pointing
downward.
The Double Disc Valve
closes in the same manner as wedged type, except that its
parallel faces drop in a vertical position.
GLOBE VALVE
actuated by a stem screw, and hand wheel, suited on installation that calls for
throttling. Globe valve affords greater resistance to flow than gate valve because of the change in flow directions.
Plug Type Disc Valve
Has a wide bearing surface producing good resistance to the
cutting effect of scale, dirt and other kind of foreign matter found inside the pipe.
Conventional Disc Valve
has a pressure tight bearing between the disc and the seat
recommended for cold water and any temperature service.
Composition Disc Valve
is used for various types of services on oil, gasoline, steam, and
hot or cold water.
ANGLE VALVE
operates same manner as glove valve. It is available in similar range of disc and seat. It used in making 90 degrees turn in a line to reduce number of joints.
FOOT VALVE
is located at the lower end of the pump used to prevent loss of priming. It is
sometimes referred to as Retention Valve.
CHECK VALVE
main function is to prevent the reversal flow of fluids in the line.
SAFETY VALVE
is used on cold water systems, heating systems, compressed air lines & other
pipelines with excessive pressure.
AIR GAP
the minimum air gap to provide backflow protection.
25
Lavatories & other fixture with effective openings not greater than 13mmm in diameter. (Not affected side wall (min))
38
Lavatories & other fixture with effective openings not greater than 13mmm in diameter. ( affected side wall (min))
38
Sinks, laundry trays, goosenecks bath faucets & other fixtures with
effective openings not greater than 19mm in diameter. (Not affected side wall (min))
57
Sinks, laundry trays, goosenecks bath faucets & other fixtures with
effective openings not greater than 19mm in diameter. (Affected side wall (min))
51
Over rim bath filters & other fixtures with effective openings not greater
than 25mm in diameter. (Not affected side wall (min))
76
Over rim bath filters & other fixtures with effective openings not greater
than 25mm in diameter. (Affected side wall (min))
EFFECTIVE OPENING
the minimum cross sectional area at the seat of the control valve or the supply pipe or tubing which feeds the device outlet. If two or more lines supply one outlet, the effective opening shall be the sum of the cross-sectional areas of the individual supply lines or the area or the single outlet, whichever is smaller.
ATMOSPHERIC VACUUM BREAKER (AVB)
consist of a body, a checking member & an atmospheric opening.
DOUBLE CHECK VALVE BACKFLOW PREVENTION ASSEMBLY (DC)
consists of two independently acting internally or externally loaded check valves, four properly located test cocks with connectors & two isolation gate valves.
PRESSURE VACUUM BREAKER BACFLOW PREVENTION ASSEMBLY (PVB)
consists of a loaded air inlet valve, an internally loaded check valve, two properly located test cocks & two isolation gate valves.
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION ASSEMBLY (RP)
consists of two independently acting internally loaded check valves, a differential pressure relief valve, four properly located test cocks & two isolation gate valves.
305mm, 1.52m
Access & clearance for testing, maintenance & repair shall require _____mm min. space between the lowest portion of the assembly & grade, floor or platform, Elevated installation more than _____m above the floor or grade shall be provided with platform sufficient to support maintenance person.
25mm
Where potable water is discharge to the drainage system, it shall be by means of an approved air gap two (2) pipe dia. of supply inlet and min. of ___mm from the supply outlet & the top surface of the drainage inlet.
152mm
Water Closet & Urinal Flushometer Valves shall be equipped with a listed atmospheric vacuum breaker & shall be installed at the discharge level of the flushometer valve with a critical level at least ____mm distance according to its listing above the overflow rim of a water closet bowl or highest part of a urinal.
25mm
Water Closet & Urinal Tanks shall be equipped with a listed ballcock & shall be installed with the critical level at least ___mm above the full opening of the overflow pipe.
For cold-water distribution systems
Water pressure pipes shall be of __________ Brass, Copper, Centrifugal Cast Iron Pipe (CCI), Ductile Cast Iron Pipe (DCI), Galvanized Wrought Iron, Galvanized Steel, or other approved PE & PVC water pressure pipe.
For hot & cold-water distribution systems
Water pressure pipes shall be of __________ CPVC water pipe & tubing
51mm
Cast iron fittings up to & including _____mm in size, when used in connection with potable water piping shall be galvanized.
8%
Water pipes & fittings with a lead content that exceed ___% shall be prohibited & shall not be used in potable piping systems.
51mm
Valves up to & including ___mm size shall be brass or other approved materials. Sizes over ___mm may have cast iron or brass bodies.
fullway gate valve
A valve used to control two (2) or more openings shall be a ______
Inadequate water pressure
residual water pressure less than 103 Kpa (15 psi), hydro-pneumatic pressure tank or an elevated water tank and booster pump.
Excessive water pressure
water pressure greater than 552 Kpa (80 psi) , approved type pressure regulator shall be installed
combination pressure and temperature relief valve (CT & PRV)
Any water system containing storage water heating equipment shall be provided with an approved, listed, adequately sized
3โ (80mm)
Except for listed non storage instantaneous heater having an inside diameter of
not more than
1033 Kpa. (150 psi)
Each pressure relief valve shall be an approved automatic type with drain, & each such relief valve shall be set at a pressure not more than
0.3m
All water service yard piping shall be at least ___m below the finish ground level.
0.3 m
Unions shall be installed in the water supply piping within ___ m away from regulating equipment, water heater, conditioning tanks & similar equipment which require removal for servicing or replacement.
Water Test
Upon completion of a section or the entire hot and cold water supply system, it shall be tested and proved tight under a water pressure not less than the working pressure in which it is to be used.
50 psi (344.5 KPA)
Air Test โ A ____ psi (____ Kpa) air pressure may be substituted for the water test. In either method of test, the piping shall withstand the test without leaking for a period of not less than 15 minutes.
20mm (3/4โ)
No building water service pipe shall be less than ___mm (___โ) in diameter.
50 ppm
The system shall be filled with water-chlorine solution containing not less than ___ppm of chlorine, and shall be valved-off and allowed to stand for 24 hours; or
200 ppm
The system shall be filled with water-chlorine solution containing not less than ___ ppm of chlorine, and shall be valved-off and allowed to stand for 3 hours
water hammer arrester(s)
Where quick-acting valves are installed shall be provided with _______ to absorb high pressure resulting from the quick closing of these valves.