Standard Slope of Horizontal Drainage Piping

Horizontal drainage pipes shall be run at a uniform slope of not less than 20mm/m20\,mm/m or 2%2\% toward the point of disposal.

2
New cards

Sloping Exception for Large Diameter Pipes

Any pipe or piping 102mm102\,mm or larger in diameter may have a slope of 10mm/m10\,mm/m or 1%1\% where a 2%2\% slope is impracticable.

3
New cards

Double Sanitary Tee Vertical Installation Rule

May be used when the barrel of the fitting is at least two (22) pipe sizes larger than the largest side inlet.

4
New cards

Sewer Requirement

Where plumbing fixtures are installed, they shall connect to a Public or Private Sewer System or a Private Sewage Disposal System.

5
New cards

Unlawful Deposits

It is unlawful to deposit ashes, rags, cinders, poisonous or explosive liquids, solids, grease, oil, or flammable gases into the plumbing system.

6
New cards

Industrial Waste Treatment

Waste must be first rendered innocuous through subjection to some acceptable form of treatment before being discharged.

7
New cards

Location of Facilities

Facilities shall be located in the lot which is the site of the building, structure, or premises served by such facilities.

8
New cards

Prohibited Workmanship Practices

It is unlawful to conceal cracks, holes, or other imperfections in materials by welding, brazing, soldering, or using paint, wax, tar, or other sealing agents.

9
New cards

Pipe Reaming

Burred ends of all pipes and tubings shall be reamed to the full bore of the pipe or tubing and all chips removed.

10
New cards

Prohibited Fittings for Drainage System

Includes Double hub fittings, Single Tee Branch, Double Tee Branch, Side Inlet Quarter Bend, Running Thread, and Band or Saddle.

11
New cards

Double Hub Sanitary Tapped Tee Exception

This fitting may be used on vertical lines as a fixture connection.

12
New cards

Tapping and Threading Restrictions

No drainage or vent piping shall be drilled and tapped for connections, and no cast iron soil pipe shall be threaded.

13
New cards

Water Closet Waste Connection Restriction

No waste connection shall be made to a closet bend or stub of a water closet or similar fixtures.

14
New cards

Vent and Waste Pipe Use Restriction

No vent pipe shall be used as a soil or waste pipe, and no soil or waste pipe shall be used as a vent.

15
New cards

Closet Bend Enlargement

The enlargement of a 76-mm76\text{-mm} closet bend or stub to 102mm102\,mm diameter shall not be considered as an obstruction.

16
New cards

Dissimilar Metals Connection

Where mixing occurs, the points of connection shall be confined to exposed or accessible locations.

17
New cards

Independent System

The drainage system of each new building shall be separate and independent from that of any other building.

18
New cards

Protection from Breakage

All pipings passing under or through walls shall be protected from breakage with pipe sleeves.

19
New cards

Pipe Sleeve Sealing

The void between pipes and sleeves through concrete floors in the ground shall be appropriately sealed with bitumen.

20
New cards

Pipe Trenching Near Footing

The bottom of all pipe trenches deeper than and parallel to an adjacent building footing must be at least forty-five (4545) degrees therefrom.

21
New cards

Building Sewer Horizontal Clearance

No building sewer shall be installed under or within 0.6meter0.6\,meter of any building or structure.

22
New cards

Building Sewer Burial Depth

No building sewer shall be installed less than 0.3meter0.3\,meter below the finish ground surface.