How many fire exits are required

Minimum 2 fire exits with 2 staircases and a fire/emergency elevator near the vertical circulation/core regardless of occupancy,function,sprinkler system etc.

The exit doors should not be too close to each other on the same wall

2
New cards

How are fire doors standardised?

Fire door dimensions should be standardised and indicated on the plan (210 × 100)

3
New cards

What are the requirements for fire doors in plans?

They should open outwards to the egress route especially in fire vestibules/halls without blocking the egress route

4
New cards

What are the requirements for the egress route?

Should be as direct to the exit as possible and free of obstacles

5
New cards

What are the dimension requirements for an egress corridor?

Fire escape corridor must be min 120 cm

6
New cards

What is necessary for every fire stair

Every fire stair must have a fire vestibule/hall (buffer zone) and fire-rated doors + a pressurisation shaft

<p>Every fire stair must have a fire vestibule/hall (buffer zone) and fire-rated doors + a pressurisation shaft </p>
7
New cards

What are requirements for the fire vestibule/hall?

  • Minimise L and Z shaped corridors upon entering the vestibule

  • Vestibule must be 3-6m²

  • Vestibule exitway should be min 180cm (1.8m)


8
New cards

What are dimension requirements for fire stairs

  • stair step width minimum : 120 cm

  • landing must have min same width as one stair/step

  • max 17 steps from landing to landing

  • max riser height : 17.5 cm

  • min tread width : 25 cm


9
New cards

What is the required fire rating for fire staircases

fire doors - min 90-min fire rating (EI 90)

fire walls - min 120 min fire rating (REI 120)

10
New cards

What are the requirements for emergency elevators

Emergency elevators must include

  • min dimension of 2m

  • pressurisation shaft

  • fire vestibule 6-10m²


11
New cards

What is the fire rating for egress routes?

fire egress corridor walls - 60 minutes

12
New cards

What is the use of fire compartments and how many are required ?

At least 2 fire compartments required to create separate zones where smoke and heat cannot penetrate from one to the other

<p>At least 2 fire compartments required to create separate zones where smoke and heat cannot penetrate from one to the other</p>
13
New cards

How can fire compartments/compartmentation be done?

Divide space using a wall on corridor and a fire door at proper location - can also apply in the section (must be fire rated walls and floors)

14
New cards
15
New cards

What are other requirements on the fire safety plan?

  • fire alarm warning devices

  • fire cabinets

  • sprinkler system

  • smoke detectors

  • heat detector (has to have a unique purpose - e.g meeting hall, larger capacity, etc)

  • smoke vent

  • emergency lighting along egress route

  • exit signs

  • areas of refuge


16
New cards

How should smoke detectors be placed?

preferably in centre of corridor and room ceilings, one every 4.5m

17
New cards

How should sprinklers be placed?

Sprinklers cover max 21m² , every 4.5m

18
New cards
<p>What is necessary for sprinkler systems?</p>

What is necessary for sprinkler systems?

connect sprinkler heads to ducts → risers within a major mechanical shaft (fire shaft) + show another shaft for ducting on the plan (min 70×100cm for water intake)

<p>connect sprinkler heads to ducts → risers within a major mechanical shaft (fire shaft) + show another shaft for ducting on the plan (min 70×100cm for water intake) </p>
19
New cards

How can fire shaft be shown on the plan?

piping can be shown as lines connecting sprinklers to the shaft

20
New cards

What is a fire riser?

knowt flashcard image
21
New cards
<p>What is a standpipe system?</p>

What is a standpipe system?

standpipe system provides water into the system and is connected to the fire cabinets - it should be supplied in the same shaft and should be shown on plan

<p>standpipe system provides water into the system and is connected to the fire cabinets - it should be supplied in the same shaft and should be shown on plan</p>
22
New cards

What are requirements for placement of fire cabinets?

  • On egress route every 30m, one for each separate route/path

  • should be closer to exits and fire stairs


23
New cards

What is the requirement for portable fire extinguishers?

max 25m in reach or one per compartment

24
New cards

What are the requirements for fire buttons?

  • 110-130cm height

  • max 60m from furthest location in plan

  • should be on egress route

  • should be closer to exits, fire stairs


25
New cards

What signage is required and where?

  • exit ways, emergency lighting, egress route arrows starting from within room to closest exit


26
New cards

What are the different types of occupancies?

A - Assembly

B - business

E - educational

M - mercantile

27
New cards

In BYKHY, what is the dead end limit without sprinklers?

15 m

28
New cards

In BYKHY, what is the dead end limit with sprinklers?

20 m

29
New cards

In BYKHY, what is the dead end limit for high hazard?

10 m / 20 m

30
New cards

What is MRP?

Most Remote Point - primary and secondary escape routes must be shown from this point to appropriate exits

31
New cards

What is the Maximum Exit Access Travel Distance without sprinklers (same for all occupancies)?

61 m

32
New cards

What is the Maximum Exit Access Travel Distance with sprinklers for A?

76 m

33
New cards

What is the Maximum Exit Access Travel Distance with sprinklers for B?

91 m

34
New cards

What is the Maximum Exit Access Travel Distance with sprinklers for E?

76 m

35
New cards

What is the Maximum Exit Access Travel Distance with sprinklers for M?

76 m

36
New cards

What are travel distances by direction?

knowt flashcard image
37
New cards

What is the diagonal method?

(look at ppt)