Electrical Switchgear, Switchboards, and Distribution Systems

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/69

flashcard set

Earn XP

Description and Tags

Comprehensive vocabulary flashcards covering low- and medium-voltage electrical switchgear, switchboards, busbar trunking, protective devices (MCBs, MCCBs, ACBs, fuses, RCDs), and relevant standards.

70 Terms

1
New cards

Electrical Switchgear

An assembly of main and auxiliary switching apparatus designed for the operation, regulation, protection, and control of electrical installations.

2
New cards

Factory Built Assembly (FBA)

A switchgear assembly complying with IEC 439 (or equivalent national standard) that has been type-tested, certified, and approved by a competent National Authority such as the NSAI.

3
New cards

Custom-Built Assembly (CBA)

A switchgear assembly designed to the principles of IEC 439 that is not type-tested or approved to that standard, requiring the manufacturer to provide verifiable evidence of code compliance.

4
New cards

Cubicle-Type Assembly

A freestanding, enclosed switchgear assembly of metal-clad construction rated for currents up to 6000 A6000\,\text{A}, comprising compartmented modules that each house devices behind individual doors.

5
New cards

Box-Type Assembly

An enclosed switchgear assembly intended for mounting on a wall or frame, built in metal-clad or all-insulated construction, and typically rated for currents up to approximately 1000 A1000\,\text{A}.

6
New cards

All-Insulated Switchgear

Switchgear housed in high-grade non-metallic enclosures (such as polycarbonate) that eliminates inter-box earth continuity requirements, reduces shock risk, prevents corrosion, and provides non-tracking protection.

7
New cards

Disconnector (Isolator)

A mechanical switching device that provides an isolating distance in the open position, capable of opening and closing circuits under negligible current while safely carrying normal and short-circuit currents for a specified time.

8
New cards

Isolating Switch (Load-Break Switch)

A mechanical switching device capable of making, carrying, and breaking currents under normal circuit conditions (including specified overloads) and carrying fault currents for a specified duration.

9
New cards

Switch-Fuse

An isolating switch comprising solidly mounted cartridge or HRC fuses housed within the same enclosure, where the mechanical switch mechanism remains separate from the stationary fuses.

10
New cards

Fuse-Switch

A compact, heavy-duty isolating switch in which the cartridge fuses are mounted directly on the moving contact carrier or switch blades, physically swinging in and out during switching.

11
New cards

Switch, Switch-Fuse, and Fuse-Switch Symbols

Standard graphical representations distinguishing a plain isolating switch, a switch with separate stationary series fuses (switch-fuse), and a switch where the fuse cartridge forms the moving blade (fuse-switch).

<p>Standard graphical representations distinguishing a plain isolating switch, a switch with separate stationary series fuses (switch-fuse), and a switch where the fuse cartridge forms the moving blade (fuse-switch).</p>
12
New cards

Circuit Breaker

A mechanical switching device capable of making, carrying, and breaking currents under normal conditions, and automatically making, carrying for a specified time, and breaking currents under abnormal conditions like short circuits.

13
New cards

Miniature Circuit Breaker (MCB)

A compact automatic circuit breaker manufactured to IS/EN 60898, rated up to 125 A125\,\text{A} with breaking capacities typically between 3 kA3\,\text{kA} and 10 kA10\,\text{kA}, utilizing thermal and magnetic tripping elements.

14
New cards

Type B MCB

An MCB calibrated for domestic and resistive applications with minimal startup surges, set to trip magnetically between 3×In3 \times I_n and 5×In5 \times I_n, and thermally between 1.13×In1.13 \times I_n and 1.45×In1.45 \times I_n.

15
New cards

Type C MCB

An MCB designed for commercial and inductive loads (such as motors and discharge lighting), set to trip magnetically between 5×In5 \times I_n and 10×In10 \times I_n, and thermally between 1.13×In1.13 \times I_n and 1.45×In1.45 \times I_n.

16
New cards

Type D MCB

An MCB engineered for high inrush inductive loads (such as welders, large transformers, and direct-on-line motors), set to trip magnetically between 10×In10 \times I_n and 20×In20 \times I_n, and thermally between 1.13×In1.13 \times I_n and 1.45×In1.45 \times I_n.

17
New cards

Arc Chute (Splitter Plates)

An arc control structure inside circuit breakers comprising insulated metal splitter plates that cool the arc, lengthen its path along arc runners, and split it into multiple segments to raise the arc voltage and extinguish it.

18
New cards
<p>Moulded Case Circuit Breaker (MCCB)</p>

Moulded Case Circuit Breaker (MCCB)

A heavy-duty circuit breaker housed in a moulded casing, rated from 15 A15\,\text{A} up to 3200 A3200\,\text{A} with breaking capacities between 25 kA25\,\text{kA} and 150 kA150\,\text{kA}, featuring adjustable thermal and magnetic trip thresholds.

19
New cards
<p>MCCB Operating Positions</p>

MCCB Operating Positions

The three handle states of a moulded case circuit breaker: ON (closed circuit), OFF (isolated/open circuit), and a distinct centre TRIPPED position that provides positive visual indication of an automatic trip.

20
New cards
<p>Air Circuit Breaker (ACB)</p>

Air Circuit Breaker (ACB)

A large metal-enclosed circuit breaker using atmospheric air for arc quenching, rated from 800 A800\,\text{A} to 6300 A6300\,\text{A} with breaking capacities up to 150 kA150\,\text{kA}, commonly utilized for primary low-voltage distribution.

21
New cards

Air Blast Circuit Breaker

A high-voltage circuit breaker that quenches the switching arc by blasting compressed air from a storage reservoir across the contacts into the atmosphere, rapidly deionizing the gap.

22
New cards

Oil Circuit Breaker (OCB)

A circuit breaker whose switching contacts are immersed in low-viscosity hydrocarbon oil, which insulates live parts and generates hydrogen gas during arcing to rapidly cool and extinguish the arc.

23
New cards

Vacuum Circuit Breaker (VCB)

A circuit breaker whose contacts operate inside a sealed ceramic vacuum bottle evacuated to approximately 0.0023 in Hg0.0023\,\text{in Hg}, quenching arcs almost instantaneously due to the absence of ionizable gas.

24
New cards

Sulphur Hexafluoride (SF6\text{SF}_6) Circuit Breaker

A circuit breaker utilizing pressurized SF6\text{SF}_6 gas as an arc-quenching and insulating medium, providing a dielectric strength 2 to 3 times2\text{ to }3\text{ times} higher than air, low arcing times, and silent enclosed operation.

25
New cards

Residual Current Device (RCD)

A protection device operating on the core-balance principle that continuously monitors circuit currents and automatically isolates all live poles when leakage to earth exceeds a predetermined value (e.g., 30 mA30\,\text{mA}).

26
New cards

Core-Balance Principle

The operating concept where supply conductors pass through a toroidal current transformer core; equal opposing currents cancel magnetic flux, while an earth leakage creates an imbalance flux that induces an e.m.f. to trigger the trip coil.

27
New cards

Type AC RCD

A residual current device designed to detect and respond solely to sinusoidal alternating residual currents, suitable only where negligible direct current components exist.

28
New cards

Type A RCD

A residual current device that provides all Type AC protections while also detecting and disconnecting circuits with pulsating direct current fault components.

29
New cards

Type F RCD

An advanced RCD that detects all Type A faults in addition to composite high-frequency residual currents, specifically intended for circuits feeding single-phase frequency-controlled speed drives.

30
New cards

Type B RCD

A high-performance RCD capable of detecting Type F fault currents plus smooth direct current residual currents, specified for electric vehicle charging stations and photovoltaic supplies.

31
New cards

Residual Current Breaker with Overcurrent Protection (RCBO)

A single combined protective unit that integrates residual current earth-fault protection alongside standard overcurrent and short-circuit MCB protection for an individual circuit.

32
New cards

Arc Fault Detection Device (AFDD)

A microprocessor-equipped protective device complying with Clause 421.7 that analyses current waveforms for high-frequency signatures characteristic of series or parallel electric arcs, disconnecting the circuit to prevent fires.

33
New cards

Busbar

A low-impedance copper or aluminium conductor of rectangular, circular, or tubular cross-section acting as a common electrical connection point for incoming sources and outgoing feeder circuits.

34
New cards

Busbar Current Density Limits

Standard operating current densities for uninsulated open busbars, typically up to 156 A/cm2156\,\text{A/cm}^2 for copper and approximately 117 A/cm2117\,\text{A/cm}^2 for aluminium at normal operating temperatures of 85∘C85^\circ\text{C}.

35
New cards

Skin Effect in Busbars

The physical phenomenon in AC circuits carrying large currents (exceeding 1000 A1000\,\text{A}) where alternating current concentrates near the conductor surface, necessitating tubular, laminated, or multi-bar arrangements.

36
New cards
<p>Single Busbar System</p>

Single Busbar System

A basic busbar layout where one continuous set of busbars runs through the switchboard to connect all generators, feeders, and transformers without any sectional isolation.

37
New cards
<p>Sectionalised Single Busbar System</p>

Sectionalised Single Busbar System

A single busbar arrangement divided into distinct sections by a bus section circuit breaker fitted with double isolation, permitting maintenance or fault containment on one section while others remain live.

38
New cards
<p>Ring Busbar System</p>

Ring Busbar System

A busbar scheme formed by connecting the ends of a sectionalised busbar to form a closed ring, ensuring any section can be supplied from generating plant on an adjacent section.

39
New cards
<p>Duplicate Busbar System</p>

Duplicate Busbar System

A switchgear arrangement featuring two parallel busbars designated 'Main' and 'Reserve' (or hospital), allowing on-load circuit transfer, plant commissioning, and maintenance without service interruption.

40
New cards
<p>Sectionalised Duplicate Busbar System</p>

Sectionalised Duplicate Busbar System

An advanced busbar configuration where the main and/or reserve busbars are divided into discrete sections by bus section switches, providing maximum operational flexibility, isolation, and system reliability.

41
New cards
<p>Busbar Trunking (Busduct)</p>

Busbar Trunking (Busduct)

A prefabricated overhead power distribution duct containing insulated or bare busbars in a sheet steel enclosure, supplied in standard 3 m3\,\text{m} lengths equipped with plug-in tap-off facilities.

42
New cards

Rising Main Busbar Trunking

A vertical busbar trunking system installed in multi-storey buildings, rated from 100 A100\,\text{A} to 500 A500\,\text{A} in 4 m4\,\text{m} sections, providing tap-off boxes at each floor level.

43
New cards

Thrust Unit

A heavy-duty mechanical support installed at the base of a vertical rising main and directly above expansion couplings to bear the accumulated physical weight of the busbars.

44
New cards

Chimney Effect

The natural upward air draught generated inside long vertical rising trunking runs that can accelerate the spread of fire between floors unless internal fire barriers and external building seals are fitted.

45
New cards

Prospective Short-Circuit Current (PSCC)

The maximum theoretical current that will flow in a circuit during a fault of negligible impedance occurring between live conductors or between a live conductor and earth.

46
New cards

Discrimination (Selectivity)

The coordination between series protective devices whereby only the device nearest downstream to a fault operates, isolating the affected circuit while upstream supplies remain energized.

47
New cards

Energy Let-Through (I2tI^2t)

A measure of the thermal energy dissipated during fault clearance, expressed in A2s\text{A}^2\text{s}, representing the integral of the squared fault current over the device clearing duration.

48
New cards

Pre-Arcing Time

The time period between the initiation of an overcurrent fault and the precise moment when the fuse element begins to melt and an electric arc is initiated.

49
New cards

Arcing Time

The duration between the strike of an electric arc across separating contacts or a melting fuse element and its total extinguishment and complete circuit interruption.

50
New cards
<p>High Breaking Capacity (HBC / HRC) Fuse</p>

High Breaking Capacity (HBC / HRC) Fuse

A ceramic cartridge fuse (BS 88) containing a precision-machined silver element surrounded by granular silica sand, engineered to clear severe short-circuit currents within 0.01 s0.01\,\text{s}.

51
New cards
<p>NH Type Fuse</p>

NH Type Fuse

A high-rupturing-capacity industrial blade-contact cartridge fuse with a silver element in quartz sand, designed to withstand internal explosion pressures during high fault interruption.

52
New cards

Fusing Factor

The numerical ratio of the minimum current required to blow a fuse to its continuous rated current, mathematically defined as Fusing Factor=Fusing CurrentRated Current\text{Fusing Factor} = \frac{\text{Fusing Current}}{\text{Rated Current}}.

53
New cards
<p>Neozed Fuse</p>

Neozed Fuse

A compact cartridge fuse manufactured to German VDE standards, available in sizes D01, D02, and D03 (2 A2\,\text{A} to 100 A100\,\text{A}) with breaking capacities up to 50 kA50\,\text{kA}, commonly used as a main switch-fuse in domestic boards.

54
New cards

Gauge Ring

A calibrated, colour-coded ceramic ring seated in a fuse base that mechanically matches the diameter of a specific fuse tip to prevent insertion of an over-rated replacement fuse.

55
New cards

Main Overcurrent Protective Device (MOD)

A customer-installed primary circuit breaker (typically a Type C MCB rated at least 9 kA9\,\text{kA} breaking capacity) housed in an IP55 enclosure in the bottom-right corner of the outdoor meter cabinet.

56
New cards

Diversity Factor

The ratio of the calculated maximum electrical power demand to the sum of all connected loads, accounting for the operating reality that all installed equipment will not run simultaneously.

57
New cards
<p>Switchgear Rating Plate</p>

Switchgear Rating Plate

A mandatory manufacturer-supplied identification plate specifying the trade name, origin, model designation, rated voltage, frequency, circuit current, and symmetrical short-circuit breaking capacity in kA RMS\text{kA RMS}.

58
New cards

Rated Operational Voltage (UeU_e)

The maximum continuous phase-to-phase operating voltage assigned to a piece of switchgear equipment to which its relevant performance tests are referenced.

59
New cards

Rated Insulation Voltage (UiU_i)

The reference voltage parameter for dielectric strength tests and clearance/creepage distances in an assembly, which must always equal or exceed the rated operational voltage (UeU_e).

60
New cards

Rated Impulse Withstand Voltage (UimpU_{imp})

The peak impulse voltage wave that the insulation and clearances of an assembly can withstand without flashover or dielectric puncture.

61
New cards

Rated Short-Time Withstand Current (IcwI_{cw})

The root-mean-square (RMS) short-circuit current that equipment can safely carry without thermal or mechanical degradation for a specified duration (typically 1 s1\,\text{s}).

62
New cards

Rated Ultimate Short-Circuit Breaking Capacity (IcuI_{cu})

The maximum short-circuit current that a circuit breaker can interrupt at its rated voltage following an O-t-CO sequence, verifying safety while allowing performance degradation.

63
New cards

Rated Service Short-Circuit Breaking Capacity (IcsI_{cs})

The short-circuit breaking current expressed as a percentage (25%25\%, 50%50\%, 75%75\%, or 100%100\%) of IcuI_{cu} that a breaker can clear repeatedly (O-t-CO-t-CO) and remain fully functional.

64
New cards

Form 4b Internal Separation

A high-integrity switchboard construction where busbars are physically separated from functional units, all functional units are separated from each other, and external cable termination points are separated from functional units and other circuits.

65
New cards

Type A Distribution Board

A distribution board featuring a horizontal busbar assembly designed exclusively to accept single-pole and/or double-pole overcurrent protective devices.

66
New cards

Type B Distribution Board

A distribution board featuring a vertical central busbar assembly arranged to accept single-pole and multi-pole overcurrent protective devices connected along its sides.

67
New cards
<p>Medium Voltage Switchgear (MVSG) Cell</p>

Medium Voltage Switchgear (MVSG) Cell

A standardized metal-enclosed bay containing medium-voltage circuit breakers (vacuum or SF6\text{SF}_6), current and voltage transformers, earthing switches, and an internal arc classification (IAC) exhaust tunnel.

68
New cards

Motor Protection Circuit Breaker (MPCB)

A specialized circuit breaker designed for motor branch circuits that provides coordinated thermal overload, electromagnetic short-circuit, and phase-loss protection.

69
New cards
<p>Smart Circuit Breaker (WiFi CB)</p>

Smart Circuit Breaker (WiFi CB)

An IoT-enabled circuit breaker that combines overcurrent protection with wireless connectivity to facilitate remote monitoring, power logging, and automated switching via smartphones or building networks.

70
New cards

Cut-Off Current

The maximum instantaneous peak value of current let through by a fast-acting protective device before the fault current can reach its unrestricted prospective peak.