overload
is a moderate increase in current beyond the normal rated current value, overloaded equipment ect
overcurrent
an overcurrent may range from six times to many hundred times of normal rated currents, short circuit , ground fault ect
short circuits
is a larger than normal current which flows outside the normal current path. it is a parallel path of low resistance
short circuit damage to circuits
thermal and magnetic stress damage
fault current is
not normally present in a cct, but is the maximum current that can flow should a fault occur
fault current can be calculated by
Isec / z (percent impedance) in the secondary of a transformer
if overloading is permitted it can cause
annealing, rapid oxidation, burning insulation, cracking insulation
typical causes of an overload are
too much equipment connected, improper size equipment, worn out or seized motor bearing / excessive mechanical load
the role of protective devices is to
open the cct before any damage can be done to the conductor and equipment
Table ___ in the cec to find maximum ampacity of fuses and breakers
13
voltage rating in protective devices relates to
quickly extinguish the arc after the fuse elements melt or the cct breaker opens
prevent the open circuit voltage in the system from restriking across the open fuse element or cct breaker contacts
voltage rating of a fuse or circuit breaker must be
equal to or greater than than the voltage of the circuit or system
the ampere rating in a protective device relates to
the rating the current device can carry continuously without opening
when selecting a fuse or breaker your ampere rating should
not exceed the current carrying capacity of the current
interrupting rating
is the maximum short circuit current an over current protective device can safely interrupt without damaging itself
time current characteristics
for any fuse the more severe the fault(the higher fault current), the faster the fuse responds. time current characteristics compare fault magnitude and speed of response
time delay fuses must be marked the letter
“D”
non-time delay fuses must be marked with the letter
“P” for low melting point
besides where current exceeds the fuses current rating, a fuse may occasionally open by
high ambient temperature
when the connection is loose or dirty
excessive vibration
when replacing a fuse consider these
voltage rating
current rating
interrupting-capacity rating
time-current characteristic
two general types of fuses
plug fuses
cartridge fuses
max rating voltage rating and amp rating of a plug fuse
150v to ground, 30a
the fuse is designed to be
the weakest link in the circuit. its job is to break the circuit before damage is done to the conductors
arc quenching powder in a fuse is
a fire-extinguishing powder that prevents an arc from continuing or bursting through the tubing of the fuse
all renewable fuses are
non time delay
overload situation in a fuse
when a overload exceeds a fuses current rating for a sufficient length of time, the fuse melts
short circuit situation in a fuse
the links melt instantly, the large current causes portions of the links to vaporize
a fuse with time delay
delays opening in a overload situation, the time required for the fuse to open depends on its time-current characteristic curve
time delay fuses are sometimes referred to as
dual element fuse
standard fuse interrupting capacity is
10,000 a
hrc fuses are
high rupturing capacity fuses that interrupt large short circuit currents without disintegrating, at the same time, they protect cables and equipment
hrc fuses are
non interchangeable, that is they are designed in such a way that other fuses will not fit into their holders
hrcI fuses
provides protection from both overloads and short circuits, has a high interrupting capacity of 200,000a
hrcII
fuses only give short circuit protection only
a fuse with current limiting ability
opens the circuit before the fault current reaches its max value
most standard fuses have a rating of
600a, 600v
circuit breakers
an electro-mechanical device designed to open a current carrying capacity under both overload and short circuit conditions without injury to the device
trip free in a circuit breaker
this means that the internal tripping mechanism must trip an overload or short circuit even if the operating lever is held in the on position
greatest advantage of circuit breakers
that is they are resettable
circuit breakers have 5 major components
frame or case
operating mechanism
trip elements
contacts
terminal connection
circuit breaker operation
the handle turns the circuit breaker on and off. it is quick make, quick break type
thermal element in circuit breakers
is a heat sensitive element bimetallic strip , excessive current or overload causes one of the metals to bend and force the other over it and opens the circuit
magnetic element in a circuit breaker
short circuit or ground fault protection element uses an electromagnetic device, when a short circuit occurs, the fault current passes through the electromagnet to attract an armature mounted on the trip bar, and opens the contacts
magnetic only breaker
is an instantaneous trip circuit interrupter , this only provides short circuit protection but no overload protection. used for motors ect
hic breaker
high interrupting capacity breaker, used when the available short circuit current often exceeds the interrupting capacity of standard breakers.
75.000 a and higher
gfi breaker
the ground fault circuit breaker is a thermal-magnetic breaker that incorporates a solid state, ground fault sensing circuit to detect ground currents of 6ma and higher