Domestic Gas Appliances - Ventilation and Combustion Air

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/26

flashcard set

Earn XP

Description and Tags

Vocabulary practice flashcards covering domestic gas appliance ventilation rules, standards, compartment sizing calculations, adventitious air allowances, and ventilator installation requirements.

27 Terms

1
New cards

BS 5440: Part 2

The British Standard covering the installation of flues and ventilation for gas appliances not exceeding 70 kW70\,\text{kW} net.

2
New cards

Gas Safety (Installation and Use) Regulations - Regulation 26 (1)

The statutory requirement stating that a gas appliance cannot be installed unless it can be used without constituting a danger to any person, which includes the adequate provision of air for combustion and ventilation.

3
New cards

Gas Safety (Installation and Use) Regulations - Regulation 26 (9) (b)

The regulation mandating that after carrying out any work during a customer visit, the supply of combustion air shall be examined and any defects notified to the responsible person.

4
New cards

Gas Safety (Installation and Use) Regulations - Regulation 34

The statutory regulation specifying that existing appliances shall not be used, or allowed to be used, if it is known or suspected that the appliance is not adequately ventilated.

5
New cards

Adventitious Ventilation

Naturally occurring air infiltration entering a dwelling through cracks and gaps around doors, windows, floors, and skirtings.

6
New cards

Adventitious Ventilation Allowance

A fixed deduction of 35 cm235\,\text{cm}^2 (equivalent to 7 kW7\,\text{kW} net heat input) applied when calculating permanent combustion ventilation for open flued appliances.

7
New cards

Post-2010 Building Adventitious Air Rule

Due to Building Regulations reducing air infiltration to prevent thermal losses, buildings constructed post-2010 do not permit an adventitious air allowance; all ventilation must be calculated from the total heat input.

8
New cards

Room Sealed Appliance

An appliance where combustion air is drawn directly from outside and combustion products are discharged directly outside via an attached flue duct, requiring no permanent openings for combustion air when installed in a room.

9
New cards

Open Flued Appliance

An appliance that takes its air supply for combustion from the room or internal space in which it is installed and discharges its products of combustion to the outside atmosphere via a chimney or flue.

10
New cards

Flueless Appliance

An appliance that takes air for combustion from the room in which it is installed and discharges the products of combustion directly back into the room.

11
New cards

Compartment (Gas Installation)

An enclosure or purpose-designed structure of less than 5 m35\,\text{m}^3 that is not normally inhabited, designed to house a gas-burning appliance.

12
New cards

Free Area

The total unobstructed open cross-sectional area through which air can pass in an air vent, typically expressed in cm2\text{cm}^2 (metric) or in2\text{in}^2 (imperial).

13
New cards

Net Heat Input Conversion

The calculation used to convert gross heat input to net heat input by dividing the gross figure in kW\text{kW} by 1.111.11.

14
New cards

Ventilator Aperture Dimension Requirements

Physical aperture criteria stating that ventilator openings must prevent the entry of a 10 mm10\,\text{mm} diameter ball while permitting the entry of a 5 mm5\,\text{mm} diameter ball.

15
New cards

Low Level Vent Smoke Prevention Rule (450 mm450\,\text{mm})

The requirement that an air vent in an internal wall communicating with an adjacent internal space (such as a hall) must be located no more than 450 mm450\,\text{mm} above floor level to reduce smoke spread during a fire.

16
New cards

Ventilated Roof Space Joist Clearance (300 mm300\,\text{mm})

The requirement that air vents supplying ventilation from an unoccupied roof space must be sited not less than 300 mm300\,\text{mm} above the joists to prevent blockages from roof insulation materials.

17
New cards

Series Internal Ventilation Rule

The requirement that when ventilation passes in series through two or more internal walls, internal vents must each be sized to 150%150\% of the combustion free area required (a single 50%50\% increase).

18
New cards

Terracotta Airbrick Free Area Measurement

Because terracotta airbricks have tapered openings that are wider at the external face and narrower at the internal face, the measurement of the smaller inner opening must be used to calculate true free area (typically around 26 cm226\,\text{cm}^2).

<p>Because terracotta airbricks have tapered openings that are wider at the external face and narrower at the internal face, the measurement of the smaller inner opening must be used to calculate true free area (typically around $$26\,\text{cm}^2$$).</p>
19
New cards

Louvre Vent Measurement Method

The measurement procedure where the measuring probe must be inserted into the grille at the exact angle of the louvre blades rather than horizontally to determine the opening height (XX).

<p>The measurement procedure where the measuring probe must be inserted into the grille at the exact angle of the louvre blades rather than horizontally to determine the opening height ($$X$$).</p>
20
New cards

Decorative Fuel Effect (DFE) Fire

A gas appliance designed to simulate an open solid fuel fire primarily for aesthetic purposes with an efficiency typically under 50%50\%, normally requiring a permanent air vent of 100 cm2100\,\text{cm}^2 free area.

21
New cards

Throatless Chimney DFE Ventilation Rule

When a DFE fire is installed without a throat (chair brick) or under a canopy, the ventilation requirement must be calculated as half (50%50\%) of the chimney opening's cross-sectional area.

22
New cards

Chimney Reversal

A dangerous situation where exhaust flue gases are pulled backwards down the chimney into the living space, commonly caused by inadequate combustion ventilation or competition from mechanical extraction fans.

23
New cards

Room Sealed Compartment Ventilation (Direct to Outside)

Compartment cooling ventilation requiring high- and low-level vents communicating directly to outside, each providing a free area of 5 cm25\,\text{cm}^2 per net kW\text{kW} of appliance heat input.

24
New cards

Room Sealed Compartment Ventilation (Adjoining Room)

Compartment cooling ventilation communicating with an internal room, requiring high- and low-level vents each providing a free area of 10 cm210\,\text{cm}^2 per net kW\text{kW} of appliance heat input.

25
New cards

Open Flued Compartment Ventilation (Direct to Outside)

Ventilation for open flued appliances in compartments taken direct from outside, requiring high-level vents at 5 cm2/kW5\,\text{cm}^2/\text{kW} net and low-level vents at 10 cm2/kW10\,\text{cm}^2/\text{kW} net (combustion air included).

26
New cards

Open Flued Compartment Ventilation (Internal Space)

Compartment ventilation communicating with an adjoining room requiring a high-level vent at 10 cm2/kW10\,\text{cm}^2/\text{kW} net, a low-level vent at 20 cm2/kW20\,\text{cm}^2/\text{kW} net, plus an external combustion vent sized at (Net kW−7 kW)×5 cm2(\text{Net kW} - 7\,\text{kW}) \times 5\,\text{cm}^2.

27
New cards

Purpose Provided Ventilator Installation Rules

Mandatory standards requiring air vents to be non-closable, non-adjustable, unobstructed, constructed of corrosion-resistant material, and never fitted with a fly screen or fine mesh gauze.