1/26
Vocabulary practice flashcards covering domestic gas appliance ventilation rules, standards, compartment sizing calculations, adventitious air allowances, and ventilator installation requirements.
BS 5440: Part 2
The British Standard covering the installation of flues and ventilation for gas appliances not exceeding 70kW net.
Gas Safety (Installation and Use) Regulations - Regulation 26 (1)
The statutory requirement stating that a gas appliance cannot be installed unless it can be used without constituting a danger to any person, which includes the adequate provision of air for combustion and ventilation.
Gas Safety (Installation and Use) Regulations - Regulation 26 (9) (b)
The regulation mandating that after carrying out any work during a customer visit, the supply of combustion air shall be examined and any defects notified to the responsible person.
Gas Safety (Installation and Use) Regulations - Regulation 34
The statutory regulation specifying that existing appliances shall not be used, or allowed to be used, if it is known or suspected that the appliance is not adequately ventilated.
Adventitious Ventilation
Naturally occurring air infiltration entering a dwelling through cracks and gaps around doors, windows, floors, and skirtings.
Adventitious Ventilation Allowance
A fixed deduction of 35cm2 (equivalent to 7kW net heat input) applied when calculating permanent combustion ventilation for open flued appliances.
Post-2010 Building Adventitious Air Rule
Due to Building Regulations reducing air infiltration to prevent thermal losses, buildings constructed post-2010 do not permit an adventitious air allowance; all ventilation must be calculated from the total heat input.
Room Sealed Appliance
An appliance where combustion air is drawn directly from outside and combustion products are discharged directly outside via an attached flue duct, requiring no permanent openings for combustion air when installed in a room.
Open Flued Appliance
An appliance that takes its air supply for combustion from the room or internal space in which it is installed and discharges its products of combustion to the outside atmosphere via a chimney or flue.
Flueless Appliance
An appliance that takes air for combustion from the room in which it is installed and discharges the products of combustion directly back into the room.
Compartment (Gas Installation)
An enclosure or purpose-designed structure of less than 5m3 that is not normally inhabited, designed to house a gas-burning appliance.
Free Area
The total unobstructed open cross-sectional area through which air can pass in an air vent, typically expressed in cm2 (metric) or in2 (imperial).
Net Heat Input Conversion
The calculation used to convert gross heat input to net heat input by dividing the gross figure in kW by 1.11.
Ventilator Aperture Dimension Requirements
Physical aperture criteria stating that ventilator openings must prevent the entry of a 10mm diameter ball while permitting the entry of a 5mm diameter ball.
Low Level Vent Smoke Prevention Rule (450mm)
The requirement that an air vent in an internal wall communicating with an adjacent internal space (such as a hall) must be located no more than 450mm above floor level to reduce smoke spread during a fire.
Ventilated Roof Space Joist Clearance (300mm)
The requirement that air vents supplying ventilation from an unoccupied roof space must be sited not less than 300mm above the joists to prevent blockages from roof insulation materials.
Series Internal Ventilation Rule
The requirement that when ventilation passes in series through two or more internal walls, internal vents must each be sized to 150% of the combustion free area required (a single 50% increase).
Terracotta Airbrick Free Area Measurement
Because terracotta airbricks have tapered openings that are wider at the external face and narrower at the internal face, the measurement of the smaller inner opening must be used to calculate true free area (typically around 26cm2).

Louvre Vent Measurement Method
The measurement procedure where the measuring probe must be inserted into the grille at the exact angle of the louvre blades rather than horizontally to determine the opening height (X).

Decorative Fuel Effect (DFE) Fire
A gas appliance designed to simulate an open solid fuel fire primarily for aesthetic purposes with an efficiency typically under 50%, normally requiring a permanent air vent of 100cm2 free area.
Throatless Chimney DFE Ventilation Rule
When a DFE fire is installed without a throat (chair brick) or under a canopy, the ventilation requirement must be calculated as half (50%) of the chimney opening's cross-sectional area.
Chimney Reversal
A dangerous situation where exhaust flue gases are pulled backwards down the chimney into the living space, commonly caused by inadequate combustion ventilation or competition from mechanical extraction fans.
Room Sealed Compartment Ventilation (Direct to Outside)
Compartment cooling ventilation requiring high- and low-level vents communicating directly to outside, each providing a free area of 5cm2 per net kW of appliance heat input.
Room Sealed Compartment Ventilation (Adjoining Room)
Compartment cooling ventilation communicating with an internal room, requiring high- and low-level vents each providing a free area of 10cm2 per net kW of appliance heat input.
Open Flued Compartment Ventilation (Direct to Outside)
Ventilation for open flued appliances in compartments taken direct from outside, requiring high-level vents at 5cm2/kW net and low-level vents at 10cm2/kW net (combustion air included).
Open Flued Compartment Ventilation (Internal Space)
Compartment ventilation communicating with an adjoining room requiring a high-level vent at 10cm2/kW net, a low-level vent at 20cm2/kW net, plus an external combustion vent sized at (Net kW−7kW)×5cm2.
Purpose Provided Ventilator Installation Rules
Mandatory standards requiring air vents to be non-closable, non-adjustable, unobstructed, constructed of corrosion-resistant material, and never fitted with a fly screen or fine mesh gauze.