Vocabulary practice flashcards covering power distribution systems, diversity factors, microgeneration rules, solar PV equipment, and transformer construction, operation, testing, and cooling.

45 Terms

1
New cards

Diversity

The ratio of the maximum demand to the connected load in an electrical installation.

2
New cards

Industrial Diversity Factors (ETCI Rules)

Design diversity allowances defined for specific industrial loads: 0.250.25 for mechanical engineering industry, 0.900.90 for food industry (including process engineering), 0.700.70 for cranes, and 0.500.50 for lifts.

3
New cards

Anti-Tamper Device

A closed-circuit security component designed to initiate an alarm condition when the access door, lid, or enclosure of intruder alarm equipment is opened by its normal method of opening.

4
New cards

Instrument Transformer Advantages

Three principal operational benefits: enables the use of standardised measuring instruments; provides increased personnel safety by allowing the secondary side to be connected to earth; and permits measuring instruments to be changed without isolating the main electrical supply by using a suitable short-circuiting switch and voltage links.

5
New cards

Grid-Connected Solar PV Electrical Components

The essential interface components required to link a solar PV array to the grid: a DC Isolator Switch (isolates panel output), an Inverter (converts DC to AC and synchronises with grid supply), an AC Isolator Switch (provides electrical isolation of the two AC supplies), and a kWh meter (measures electrical energy exported to the grid).

6
New cards

Stand-Alone Solar PV System Components

The key equipment needed for an off-grid solar installation supplying low-power consumption AC loads: Solar PV Panels, Charge controller, DC Disconnector, Batteries, and an Inverter (with or without SPD).

7
New cards

Microgenerator Interface Protections

Five electrical protection functions required when interconnecting a microgenerator to the national grid: undervoltage protection, overvoltage protection, underfrequency protection, overfrequency protection, and a means to detect loss of mains supply.

8
New cards
<p>Dual Supply Warning Label Locations</p>

Dual Supply Warning Label Locations

Four mandatory positions where dual-supply warning signs must be posted in premises with microgeneration: at the ESB Networks metering position, at the consumer unit position, on all switchboards between the consumer unit and microgenerator, and at all points of isolation for the microgenerator.

9
New cards

Standard Test Conditions (STC)

The standardised laboratory reference conditions used to rate and compare solar PV modules: an irradiance of 1,000 W/m21{,}000\,\text{W/m}^2, a cell temperature of 25 ∘C25\,^{\circ}\text{C}, and an AM1.5AM1.5 reference solar spectrum.

10
New cards

Air Mass (AM)

The relative optical path length that sunlight travels through Earth's atmosphere compared with the shortest near-vertical path; AM1.5AM1.5 represents a path length approximately 1.51.5 times this reference length and relates to the solar spectrum.

11
New cards

ESB NC6 Form

A formal notification document submitted to ESB Networks advising that a customer intends to install a microgenerator; it provides owner/MPRN details, installer data, equipment specifications (including EN50438 compliance certificate), inverter maximum capacity in kVA, and generator type.

12
New cards

Mutual Inductance

The magnetic phenomenon where an alternating current changing in one coil induces an EMF in an adjacent coil; mutual inductance is one henry (1 H1\,\text{H}) when a current change of 1 A/s1\,\text{A/s} in the primary induces an EMF of 1 V1\,\text{V} in the secondary.

13
New cards

Self-Inductance

The production of an opposing counter-EMF in a coil resulting from changes in its own current; its value is one henry (1 H1\,\text{H}) when current changing at the rate of 1 A/s1\,\text{A/s} induces an EMF of 1 V1\,\text{V} within the same winding.

14
New cards

Inductive Time Constant (\tau)

The ratio controlling transient current growth and decay in an inductive RL network, calculated as τ=LR\tau = \frac{L}{R} (henrys divided by ohms); transient rise or decay is considered complete after approximately five time constants (5τ5\tau).

15
New cards

Core-Type vs Shell-Type Transformer

Two distinct magnetic core constructions: core-type transformers split windings across both outer limbs to minimise leakage flux, whereas shell-type transformers concentrate both windings on a central limb flanked by two outer limbs that provide parallel magnetic return paths.

16
New cards

Concentric vs Sandwich Windings

Two winding configurations: concentric (cylindrical) windings feature one winding placed completely over the other (predominantly in core-type transformers), while sandwich (disc-type) windings divide primary and secondary coils into interleaved alternating discs (predominantly in shell-type transformers).

17
New cards

On-Load Tap Changer (OLTC)

An automated transformer switching mechanism that modifies the winding tap positions and turns ratio under full operational load without interrupting power, ensuring stable terminal voltage across variable supply or load demands.

18
New cards

Iron Losses (Core Losses)

The combined heat losses within a transformer's magnetic circuit composed of eddy current losses (minimised by thin laminations) and hysteresis losses (minimised by silicon steel); iron losses depend on frequency and peak flux density and remain practically constant from no load to full load.

19
New cards

Copper Losses

The heating losses generated in transformer windings due to conductor resistance (P=I2RP = I^2 R); copper losses are proportional to the square of the operating load current and are assumed to be zero when the secondary is open-circuited (no-load condition).

20
New cards

Transformer Voltage Regulation

The percentage variation in secondary terminal voltage between zero load and full rated load caused by internal winding impedance, expressed as Vno load−Vfull loadVno load×100%\frac{V_{\text{no load}} - V_{\text{full load}}}{V_{\text{no load}}} \times 100\%.

21
New cards

Open Circuit Test (No Load Test)

A diagnostic procedure where rated voltage is supplied to the primary with the secondary terminals open; because the no-load magnetising current is very small (3–5%3\text{--}5\% of full load), winding copper loss is negligible and the wattmeter reading indicates transformer iron losses.

22
New cards

Short Circuit Test

A transformer test where the LV winding is shorted by a thick conductor and a reduced voltage (5–10%5\text{--}10\% of rated) is applied to the HV side to circulate rated full-load current; because core flux density is minimal, core loss is negligible and the wattmeter reading indicates full-load copper losses (I2RI^2 R).

23
New cards

Conservator Tank

An elevated cylindrical tank mounted above the main oil-filled transformer body to accommodate the volumetric expansion and contraction of insulating oil during heating and cooling cycles, preventing excessive hydraulic pressure from rupturing the transformer tank.

24
New cards

Buchholz Relay

A protective gas-actuated safety relay fitted in the pipe linking the main transformer tank and conservator; minor faults liberate gas that displaces oil to lower an upper float and trigger an alarm, while severe faults cause violent oil surges that deflect a lower flap to trip the circuit breaker and isolate the transformer.

25
New cards

Silica Gel Breather

A moisture-extraction device connected to the conservator breathing pipe containing silica gel crystals that dehydrate air entering the transformer; dry crystals exhibit a blue tint, which turns pink as moisture saturates the gel, signalling the need for replacement or reactivation.

26
New cards

Transformer Bushings

Insulated feed-through assemblies that facilitate the connection of internal windings to external conductors through the grounded metal tank; LV bushings utilize porcelain or ebonite posts, while HV bushings operating above 33 kV33\,\text{kV} employ capacitor-graded bakelized paper and tin-foil layers encased in porcelain.

27
New cards

Arcing Horns

Paired spark-gap electrodes positioned across high-voltage insulator bushings (one connected to the line conductor and the other to tank ground) to safely divert overvoltage surges and lightning flashovers away from the fragile bushing porcelain and windings to earth.

28
New cards

ONAN and ONAF Transformer Cooling

Standard transformer cooling classifications: ONAN (Oil Natural Air Natural) cools through natural internal oil convection and natural external air currents over radiator banks; ONAF (Oil Natural Air Forced) maintains natural oil circulation but uses cooling fans to force air across the radiator exterior.

29
New cards

Conditions for Paralleling Transformers

The mandatory parameters required before paralleling two or more transformers: identical primary and secondary voltage/turns ratios, equal percentage impedance, identical tap changer positions, matching phase angle shift, identical rated frequency, correct relative polarity, and matching phase sequence.

30
New cards

Transformer Oil Crackle Test

A field test used to confirm that insulating oil is free from moisture, performed by gently heating a small oil sample in a test tube over a flame, where any audible crackling signifies the presence of water.

31
New cards

Transformer Oil Electric Strength Test

A dielectric breakdown test that evaluates the physical cleanliness and dielectric integrity of insulating oil by applying an increasing alternating voltage across submerged electrodes (typically 27–30 kV27\text{--}30\,\text{kV}) until a spark appears, averaging six consecutive readings.

32
New cards

Domestic Shower Circuit Sizing and Current (10 kW10\,\text{kW} at 230 V230\,\text{V})

Under ETCI rules:

  • Current without diversity: I=PV=10,000 W230 V=43.48 AI = \frac{P}{V} = \frac{10{,}000\,\text{W}}{230\,\text{V}} = 43.48\,\text{A}

  • Current with diversity applied: 40 A40\,\text{A}

  • Fixed wiring cable: 6 mm26\,\text{mm}^2 copper

  • Protective device: 40 A40\,\text{A} MCB or fuse

  • Isolating switch: 40 A40\,\text{A}


33
New cards

Current Transformer (CT) Multiplier and Secondary Reading (1,200 A1{,}200\,\text{A} Load, 1,500/51{,}500/5 Ratio)

  1. CT Multiplier: 1,5005=300\frac{1{,}500}{5} = 300

  2. Secondary ammeter reading: 1,200 A300=4 A\frac{1{,}200\,\text{A}}{300} = 4\,\text{A}


34
New cards

Industrial Distribution Board Load Calculation (40 kVA40\,\text{kVA} at 0.80.8 PF Lagging and 35 kW35\,\text{kW} at Unity PF)

  1. Active power (PP): (40 kVA×0.8)+35 kW=32 kW+35 kW=67 kW(40\,\text{kVA} \times 0.8) + 35\,\text{kW} = 32\,\text{kW} + 35\,\text{kW} = 67\,\text{kW}

  2. Reactive power (QQ): 40 kVA×0.6=24 kVAr40\,\text{kVA} \times 0.6 = 24\,\text{kVAr}

  3. Apparent power (SS): 672+242=71.17 kVA\sqrt{67^2 + 24^2} = 71.17\,\text{kVA}


35
New cards

Solar PV Sizing Calculation for a 12 kW12\,\text{kW} Installation (400 W400\,\text{W}, 1 m×1 m1\,\text{m} \times 1\,\text{m} Modules)

  1. Module power density: 400 W/m2400\,\text{W/m}^2

  2. Total surface area needed: 12,000 W400 W/m2=30 m2\frac{12{,}000\,\text{W}}{400\,\text{W/m}^2} = 30\,\text{m}^2

  3. Number of solar PV modules: 30 m21 m2=30 modules\frac{30\,\text{m}^2}{1\,\text{m}^2} = 30\,\text{modules}


36
New cards

Measures to Manage Surplus Solar PV Generation During Low Domestic Demand

Three practical solutions to utilize daytime excess power:

  • Install a battery storage bank to retain electrical energy for evening consumption
  • Install an immersion diverter switch to heat water in a storage cylinder
  • Connect an electric vehicle (EV) home charging station
37
New cards

Single-Phase Microgeneration Maximum Export Capacity (MEC) under ESB NC6

5.75 kVA5.75\,\text{kVA} (nominally 6 kVA6\,\text{kVA}), based on an inverter rated current output limit of 25 A25\,\text{A} at a standard voltage of 230 V230\,\text{V} (25 A×230 V=5,750 VA25\,\text{A} \times 230\,\text{V} = 5{,}750\,\text{VA}).

38
New cards

Commissioning Verification Tests for Grid-Connected Microgenerators (EN 50438 / EN 50549)

Key verification tests required at commissioning:

  • Verification of under-voltage and over-voltage protection trip operation
  • Verification of under-frequency and over-frequency protection trip operation
  • Loss of mains detection to confirm shutdown until grid power restoration
  • Measurement of DC solar array input voltage to ensure operation within inverter limits
39
New cards

Transformer Full-Load Copper Loss Calculation from Half-Load Loss (120 kW120\,\text{kW} at Half Load)

480 kW480\,\text{kW}; copper losses vary in proportion to current squared (P∝I2P \propto I^2), so doubling current from half load to full load increases copper dissipation by 22=42^2 = 4 times (120 kW×4=480 kW120\,\text{kW} \times 4 = 480\,\text{kW}).

40
New cards

Transformer Percentage Voltage Regulation Calculation (400 V400\,\text{V} No-Load to 390 V390\,\text{V} Full-Load)

2.5%2.5\%, calculated using:

Vno load−Vfull loadVno load×100%=400 V−390 V400 V×100%=2.5%\frac{V_{\text{no load}} - V_{\text{full load}}}{V_{\text{no load}}} \times 100\% = \frac{400\,\text{V} - 390\,\text{V}}{400\,\text{V}} \times 100\% = 2.5\%

41
New cards

Transformer No-Load Voltage Calculation (220.8 V220.8\,\text{V} Full Load, 4%4\% Regulation)

230 V230\,\text{V}, calculated using:

Vno load=Vfull load1−% regulation100=220.8 V1−0.04=220.8 V0.96=230 VV_{\text{no load}} = \frac{V_{\text{full load}}}{1 - \frac{\%\,\text{regulation}}{100}} = \frac{220.8\,\text{V}}{1 - 0.04} = \frac{220.8\,\text{V}}{0.96} = 230\,\text{V}

42
New cards

Fault Diagnosis for Parallel Transformer Voltmeters (V1=235 VV_1 = 235\,\text{V}, V2=470 VV_2 = 470\,\text{V}, V3=235 VV_3 = 235\,\text{V})

It is unsafe to close switch S. A reading of 470 V470\,\text{V} across switch S indicates that the two secondary windings are connected in additive series opposition (opposite polarity). Closing switch S would cause a dangerous short circuit across a 470 V470\,\text{V} potential.

43
New cards

Dual Safety Float and Flap Operation in a Buchholz Relay

  • Top tilt switch (hollow float): triggers an audible warning when gas generated by minor internal faults displaces oil and lowers the float
  • Bottom tilt switch (hinged flap): triggers a trip circuit to isolate the transformer when severe internal faults cause a violent oil surge towards the conservator
44
New cards

Winding Insulation Resistance (IR) Test Connections for Power Transformers

With all line and neutral bushings fully isolated from the external supply:

  1. Between HV studs and LV studs (checks insulation between windings)
  2. Between HV studs and the tank earth point (checks HV insulation to ground)
  3. Between LV studs and the tank earth point (checks LV insulation to ground)
45
New cards

Tertiary Winding Function in Star-Star (Y-Y) Transformers

An auxiliary delta-connected winding included in star-star systems to provide a path for circulating third-harmonic currents, stabilize the neutral point, and prevent severe voltage unbalance during single-phase loading.