A04 CONSTRUCTION POLLUTION MANAGEMENT(PRECONDITION)

  • Protect indoor air quaility during building construction and renovation through a combination of strategies: envelope protection, moisture and dust management, filter replacement, air flush and proper equipment selection


2
New cards

Part 1: Mitigate construction pollution

  1. Ducts are maintained per: ducts are sealed and protected from contamination. And ducts are cleaned prior to installing registers,grills, and diffuser

  2. If permanently installed ventilation system is operating during construction, filter must meet: 

Media filters with a PM10 removal rating of at least 70% (e.g., MERV 8) are used to filter return air.6

All filters are replaced prior to occupancy.5

  1. Moisture and dust managment prodedures: 1. Carpet, acoustical ceiling panels, fabric wall covering, installation, upholstery and furnishing are stored separately in protected from moisture damaged. 2. Work areas isolated by sealed doorways or windows. 3. Walk-off mats are used at entryways. 4. Saws and tools use dust guards to capture dust.


3
New cards

05 ENHANCED AIR QUAILTY( OPTIMIZATION)(4 pts)

Improve human health and performance

4
New cards

Part 1: meet enhanced threshold from particulate matter: (2 point)



1 Point: PM2.5: 12 µg/m³ or lower.8

PM10: 30 µg/m³ or lower.9

2 Point PM2.5: 10 µg/m³ or lower.9

PM10: 20 µg/m³ or lower.9



5
New cards

Part 2: meet enhanced thresholds for organic gases (1 point)

  • Acetaldehyde: 140 µg/m³ or lower.10

  • Acrylonitrile: 5 µg/m³ or lower.10

  • Benzene: 3 µg/m³ or lower.10

  • Caprolactam: 2.2 µg/m³ or lower.10

  • Formaldehyde: 9 µg/m³ or lower.10

  • Naphthalene: 9 µg/m³ or lower.10

  • Toluene: 300 µg/m³ or lower.10


6
New cards

Part 3: Meet inorganic gases:

  • Carbon monoxide: 7 mg/m³ [6 ppm] or lower.11

  • Nitrogen dioxide: 40 µg/m³ [21 ppb] or lower.11


7
New cards

A06 ENHANCED VENTILATION DESIGN (OPTIMIZATION)(3PTS)

Increased supply of outdoor air or increased ventilation efficiency

8
New cards

Part 1: Increase Outdoor air supple (2 points) options

Option1: increased air supple

Option 2: Demand control ventilation

Optoon3: enhanced natural ventailation

9
New cards

Option 1: Increased air supply

  1. Exceed outdoor air supply rate in ASHRAE 62.1-2010:

  • Threshold 30%-1 points

  • Threshold 60%- 2 points


10
New cards

Option 2: demand control ventilation:

Met in at least 90% of regulary occupied spaces:

  1. A deman control ventilation(DCV) system regulates the outdoor air ventilation to keep CO2 level less than threshold:

Threshold 900ppm-or threshold 500 ppm above outdoor level-point 1

Threshold 750 ppm-or 350 ppm above outdoor levels- point 2

  1. Carbon dioxide is measured at the return air diffusers or in breathing zone at least 3.3 ft away from doors,windows, air supply. One sensor in each occupancy zone


11
New cards

Option 3: Enhanced natural ventilation

  1. Implement an engineered natural ventilation system that sufficient to keep CO2 level in breathing zone

  • Same thresholds as part 2


12
New cards

Part 2: Improve ventilation effectivness ( 1 point) for echanced ventilation design options:

Option1: Displacement ventilation system

Option 2: personalized ventilation system

13
New cards

Option1: Displacement ventilation system

  • ASHRAE Guidelines RP-949.9

  • ASHRAE 62.1-2019, "Stratified Air Distribution Systems (Section 6.2.1.2.1).10

  • REHVA Guidebook No. 01 (Displacement Ventilation in non-industrial premises).11


14
New cards

Option 2: personalized ventilation system

  • For at least 50% of workstation is requriement:

Outdoor air is supplied in the breathing zone, with an airspeed of no greater than 50 fpm at the occupant's head.10

The return air diffusers are located more than 9.8 ft above the floor.10

15
New cards
16
New cards
17
New cards
18
New cards
19
New cards
20
New cards
21
New cards
22
New cards
23
New cards
24
New cards
25
New cards
26
New cards
27
New cards
28
New cards
29
New cards
30
New cards
31
New cards
32
New cards
33
New cards
34
New cards