Learner Guide 5: Chimneys - Open and Room Sealed Chimney Terminal Locations

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/27

flashcard set

Earn XP

Description and Tags

Vocabulary flashcards covering the installation rules, minimum clearance dimensions, and regulatory standards for natural draught and fan-assisted chimney terminations (open flued and room-sealed) as detailed in Learner Guide 5.

28 Terms

1
New cards

Flue Outlet Termination Height Measurement Datum

The official measurement reference point for the height of an open chimney termination, which is measured up to the top of the flue outlet (the top of the flue pipe) and not to the top of the terminal itself.

2
New cards
<p>Terminal Locations for Open &amp; Room Sealed Appliances</p>

Terminal Locations for Open & Room Sealed Appliances

A standardized alphanumeric positioning layout (dimensions A through P) used to determine minimum separation distances based on the appliance's net heat input (kW\text{kW}) and draught type, ensuring combustion products do not re-enter buildings through openings.

3
New cards

Terminal Guard (Room Sealed Appliances)

A protective cage required to be installed around any room-sealed terminal located within 2 m2\,\text{m} of finished ground level to prevent mechanical interference, maintaining a clearance of at least 50 mm50\,\text{mm} between the guard and all surfaces of the terminal.

4
New cards

Eaves Ventilator Clearances (Post-1983 / Post-1985 Dwellings)

Mandatory clearance distances required between room-sealed terminals and fresh air intake ventilators installed in the eaves of properties constructed after 1985 in England & Wales and after 1983 in Scotland.

5
New cards

Heat Shield Requirements for Natural Draught Terminals

A protective fitting at least 1 m1\,\text{m} long with a 5 mm5\,\text{mm} air gap that must be installed when a natural draught appliance terminates within 1 m1\,\text{m} of a plastic gutter or within 500 mm500\,\text{mm} of painted eaves (under BS 5440 Part 1:2008, fan flued terminals no longer require eaves or gutter protection unless specified by the manufacturer).

6
New cards
<p>Multiple Open Chimney Terminations (Close Proximity Rule)</p>

Multiple Open Chimney Terminations (Close Proximity Rule)

Regulations governing chimney outlets on shared structures: outlets in close proximity must maintain a minimum spacing of 50 mm50\,\text{mm}, and where 33 or more terminals are less than 300 mm300\,\text{mm} apart, they must terminate at the same height.

7
New cards
<p>Staggered Chimney Termination</p>

Staggered Chimney Termination

An arrangement where chimney pots or prefabricated metal terminals are spaced more than 300 mm300\,\text{mm} apart, permitting them to terminate at different (staggered) heights.

8
New cards

Flat Roof (TOP's Table 5 Definition)

Any roof structure having a slope defined as being within 20∘20^\circ of the horizontal plane.

9
New cards

Pitched Roof Clearance (Not on Ridge)

A flue location standard requiring that no part of the chimney outlet shall be less than 1.5 m1.5\,\text{m} measured horizontally to the roof surface, or less than 600 mm600\,\text{mm} vertically above the ridge.

10
New cards

Ridge Tile Terminal Siting

Terminals positioned on a roof ridge must terminate at or above ridge level, be sited at least 1500 mm1500\,\text{mm} from any adjacent higher structure (such as a gable end wall), and maintain a separation of not less than 300 mm300\,\text{mm} from other four-sided open ridge terminals.

11
New cards

Roof Structure Clearance (Dimension B)

A clearance rule specifying that if the horizontal distance AA from an open chimney terminal to a vertical structure on a pitched roof is less than 1500 mm1500\,\text{mm}, the terminal outlet height BB must be not less than 600 mm600\,\text{mm} above the top of that structure.

12
New cards

Pitched Roof Window and Opening Clearance Zone

A restricted area around openings or windows on pitched roofs (irrespective of pitch) where chimneys may not penetrate: extending A=600 mmA = 600\,\text{mm} to the sides and top, and B=2000 mmB = 2000\,\text{mm} directly below the opening.

13
New cards

Ten Heights (10h10h) Parapet Rule

A flat roof provision allowing the terminal outlet height to be reduced to only 250 mm250\,\text{mm} above the roof when the outlet is positioned at a horizontal distance greater than 1010 times the height (hh) of an adjacent parapet or structure (otherwise 600 mm600\,\text{mm} is required).

14
New cards

Flat Roof Envelope Method

A method used when multiple structures are on a flat roof and the chimney outlet is within 10h110h_1 and 10h210h_2 horizontally; the terminal must terminate not less than 600 mm600\,\text{mm} above an imaginary plane drawn across the roof structures.

15
New cards

Prohibited Zone (Flat Roof Extension / Adjacent Buildings)

A restricted clearance envelope extending horizontally up to 10,000 mm10{,}000\,\text{mm} (10 m10\,\text{m}) from an adjacent wall, within which a chimney terminal must maintain at least 600 mm600\,\text{mm} clearance above an inclined line starting 2300 mm2300\,\text{mm} (2.3 m2.3\,\text{m}) above the roof level.

16
New cards

Sloping Hill or Embankment Height Adjustment

A mandatory requirement to increase open chimney terminal heights by 500 mm500\,\text{mm} when an embankment or sloping hill is within 44 times the height of the building and has an elevation between 12\frac{1}{2} and 11 times the building's height.

17
New cards

Severe Circumstances Termination Specification

Special operating criteria for extreme conditions (such as external chimneys, steep pitch, high efficiency appliances, complex roof geometry, or nearby hills), requiring terminal heights of at least 2 m2\,\text{m} and the installation of an extractive terminal.

18
New cards

Boundary (Gas Appliance Siting Definition)

The legal boundary of the land or buildings belonging to and under the control of the property owner, which can be considered to extend to the centre line of adjacent public waterways or routes (such as streets, paths, railways, or canals).

19
New cards
<p>Boundary and Adjacent Terminal Dimensions (X, Y, and Z)</p>

Boundary and Adjacent Terminal Dimensions (X, Y, and Z)

Clearance rules for fanned draught room-sealed terminals near boundaries: Dimension X is 300 mm300\,\text{mm} parallel to a boundary; Dimension Y is 600 mm600\,\text{mm} discharging at an angle to a boundary; Dimension Z is 2000 mm2000\,\text{mm} (2 m2\,\text{m}) directly opposite an opening in an adjacent building.

20
New cards

Dimension J

The minimum clearance measured from the end face of a terminal to an opposing surface, facing wall, or facing property boundary, specified as 600 mm600\,\text{mm} for both room-sealed natural draught and fanned draught appliances.

21
New cards

Dimension K

The minimum clearance between two opposing terminals facing directly towards each other, requiring 600 mm600\,\text{mm} for natural draught room-sealed appliances and 1200 mm1200\,\text{mm} for fanned draught appliances.

22
New cards

Dimension A (Room-Sealed Opening Below)

The minimum clearance required directly below an openable window, air brick, or door: 300 mm300\,\text{mm} for fanned draught; for natural draught it scales by input: 300 mm300\,\text{mm} (0–7 kW0\text{--}7\,\text{kW}), 600 mm600\,\text{mm} (>7–14 kW>7\text{--}14\,\text{kW}), 1500 mm1500\,\text{mm} (>14–32 kW>14\text{--}32\,\text{kW}), and 2000 mm2000\,\text{mm} (>32–70 kW>32\text{--}70\,\text{kW}).

23
New cards

Dimension H

The minimum clearance from an internal or external corner, or to a boundary running alongside the terminal: 600 mm600\,\text{mm} for room-sealed natural draught appliances and 300 mm300\,\text{mm} for fanned draught appliances (200 mm200\,\text{mm} for open flue fanned draught).

24
New cards

Dimension M and Dimension N

Separation distances between multiple terminals installed on the same wall: Dimension M requires at least 1500 mm1500\,\text{mm} vertically, while Dimension N requires at least 300 mm300\,\text{mm} horizontally.

25
New cards

Building Extrusion Exemption (450 mm450\,\text{mm} Rule)

An exception stating that corner separation distances (Dimension H) do not apply to external building extrusions not exceeding 450 mm450\,\text{mm} (such as disused chimney breasts on external walls) for fanned draught appliances or natural draught appliances up to 7 kW7\,\text{kW} net input.

26
New cards

End Ventilation Slate Upstand

A weatherproofing component used where a chimney passes through a roof structure, requiring an upstand of at least 150 mm150\,\text{mm} above the roof intersection.

27
New cards

Dimension L

The minimum clearance from a flue terminal to an opening into a dwelling situated inside a carport (such as a door or window), fixed at 1200 mm1200\,\text{mm} for both fanned draught and natural draught room-sealed appliances.

28
New cards

Dimension D and Dimension E

Clearance distances below structural projections for fanned draught appliances: Dimension D requires 75 mm75\,\text{mm} below gutters, soil pipes, or drain pipes; Dimension E requires 200 mm200\,\text{mm} below eaves (300 mm300\,\text{mm} for natural draught room-sealed).