How must continuous loads be factored when sizing branch-circuit conductors and OCPDs?

Continuous loads must be calculated at 125% of their rating for conductor ampacity and OCPD sizing.

OCPD = Overcurrent Protection Device (e.g., circuit breaker or fuse).

NEC: 210.19(A)(1), 210.20(A).

2
New cards

At what percentage are noncontinuous loads calculated?

100% of the noncontinuous load is used in sizing conductors and OCPDs.

NEC: 210.19(A)(1), 210.20(A).

3
New cards

When may you use the next higher standard-sized OCPD?

When the calculated ampacity falls between standard sizes listed in NEC 240.6(A), you may use the next higher standard rating.

OCPD = Overcurrent Protection Device.

NEC: 240.6(A).

4
New cards

Where do you find ampacities for insulated copper conductors like THW?

Table 310.16.

THW = Thermoplastic Heat- and Water-resistant copper conductor insulation.

Use: Determines minimum AWG size after applying NEC multipliers.

NEC: Table 310.16.

5
New cards

What is the maximum rating of a single cord-and-plug-connected utilization equipment on a branch circuit?

It cannot exceed 80% of the branch-circuit ampere rating.

NEC: 210.23(A)(1).

Utilization equipment = equipment that consumes electric power (e.g., appliances).

6
New cards

What is the maximum rating for fastened-in-place, cord-and-plug-connected equipment when the branch circuit also supplies lighting?

Cannot exceed 50% of the circuit rating.

Fastened-in-place = mechanically secured (not portable).

NEC: 210.23(A)(2).

7
New cards

Are luminaires with heavy-duty lampholders permitted on a 40 A branch circuit?

Yes. Heavy-duty lampholders may be supplied by circuits over 20 A.

Heavy-duty lampholder = 660 W or 250 V rating.

NEC: 210.23(B); definition in Article 100.

8
New cards

What counts as “wall space” when applying the 6-ft/12-ft receptacle rules?

What counts as “wall space” when applying the 6-ft/12-ft receptacle rules?

9
New cards

What is the distance rule for receptacles in dwelling living areas?

No point along the floor line may be more than 6 ft from a receptacle → effectively requires receptacles every 12 ft of wall space.

NEC: 210.52(A)(1).

10
New cards

Do doorways or sliding glass doors count as wall space?

No. Openings do not count. Only solid wall sections ≥2 ft count.

NEC: 210.52(A)(2).

11
New cards

How do you determine the minimum number of required receptacles in a room?


  1. Add up all qualifying (≥2 ft) wall spaces.

  2. Divide by 12 ft.

  3. Round up to determine minimum required receptacles.
    NEC: Based on 210.52(A)(1)–(A)(2).


12
New cards

What is the difference between cord-and-plug equipment and fastened-in-place equipment?


  • Cord-and-plug: Portable or movable, connected via flexible cord.

  • Fastened-in-place: Mechanically attached to building structure — not readily movable.
    NEC: Implied in 210.23(A)(1) and 210.23(A)(2).


13
New cards

Are multiwire Branch circuits required to be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates?

Yes, NEC 210.4(B)

14
New cards

Determine the distance from ground permitted for aux equipment of electric-discharge luminaires used to illuminate a parking lot, The luminaires operate at 480 V to ground.

22ft minimum. NEC 210.6(D)(1)

15
New cards

A 240 V, 9kW household electric range is installed in the basement of a one family dwelling. Determine the minimum branch circuit rating for the circuit that supplies that range. 

40A. 210.19(A)(3)


I = 9000W/240V = 37.5A

16
New cards

Determine the max rating for a single cord-and-plug connected piece of utilization equipment that is fastened in place on a 30A branch circuit,

80(30A) = 24A Maximum. NEC 210.23

17
New cards

Determine the max rating for a single cord-and-plug connected piece of utilization equipment that is fastened in place on a 20A branch circuit. The branch circuit also supplies lighting units in addition to the utilization equipment.

50(20A) = 100A Max. NEC 210.23(B)(2)

18
New cards

Feeder

All the circuit conductors between the device equipment, the source of a separately derived system, or other supply source, and the final branch circuit overcurrent device.