UPS Systems

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/18

flashcard set

Earn XP

Description and Tags

Vocabulary practice flashcards covering rotary versus solid-state UPS systems, power quality anomalies, power conditioning devices, and IT earthing and cable segregation standards.

19 Terms

1
New cards

Uninterruptible Power Supply (UPS)

A device that provides backup power when the mains supply fails and conditions power quality for sensitive loads such as IT equipment.

2
New cards

Rotary UPS System

A mechanical UPS system using a motor-generator set and a flywheel (sometimes paired with a diesel engine) to store kinetic energy and bridge power gaps.

3
New cards

Solid State UPS System

An all-electronic UPS system consisting of a rectifier, battery bank, inverter, and static bypass switch that provides instant transfer with no moving parts except cooling fans.

4
New cards

Transient

A very short, high-voltage spike lasting <1<1 cycle caused by lightning, switching inductive loads, or faults, risking component damage and data corruption.

5
New cards

RFI / EMI

Radio Frequency or Electromagnetic Interference produced by motors, welders, and radio transmitters that causes data errors and communication failures.

6
New cards

Electrical Noise

Unwanted signals on a power supply, appearing either in normal mode (between live and neutral) or common mode (between live/neutral and earth).

7
New cards

Voltage Surge

A voltage increase exceeding 110%110\% of nominal voltage lasting for >1>1 cycle, leading to overheating and insulation breakdown.

8
New cards

Voltage Sag / Brownout

A voltage drop to 80–90%80\text{--}90\% of nominal voltage lasting for >1>1 cycle (termed a brownout when sustained over a long duration), causing system resets and data loss.

9
New cards

Blackout

A complete loss of electrical mains power, resulting in total equipment shutdown and data loss.

10
New cards

Metal Oxide Varistor (MOV)

A fast-acting component utilized inside surge suppressors to divert excess high voltage to earth during spike events.

11
New cards

Power Line Conditioner

A power conditioning device that utilizes transformers and filters to correct sags, surges, and electrical noise without offering battery backup during mains failure.

12
New cards

Off-line (Standby) UPS

A UPS topology where the load normally runs directly from mains and switches to battery and inverter power in 2–10 ms2\text{--}10\,\text{ms} upon mains failure or sag.

13
New cards

On-line (Double Conversion) UPS

A UPS topology where power continuously flows from mains through a rectifier to a DC bus and then through an inverter to the load, providing zero transfer time and total mains isolation.

14
New cards

Very Clean Wiring Category

Wiring dedicated to sensitive data circuits (such as Ethernet, fiber, RS232, and analog signals) that must be run separately, often in metal conduit or trunking.

15
New cards

Clean Wiring Category

Wiring carrying UPS outputs and conditioned power to IT loads; can be run alongside very clean cabling but must remain segregated from dirty cabling.

16
New cards

Dirty Wiring Category

Wiring circuits supplying mains, motors, lifts, fluorescent lighting, and welders that must be segregated from clean circuits by ≥300 mm\ge 300\,\text{mm} or a metallic partition.

17
New cards

Circuit Protective Conductor (CPC)

The safety earth conductor designed to carry electrical fault currents, which becomes electrically noisy during faults and must never be used as a communication signal reference.

18
New cards

Technical Earth Conductor (TEC)

A dedicated, quiet functional earth run directly from the main earth terminal and bonded at only one point to provide a noise-free signal reference for data systems.

19
New cards

Earth Loop

A condition occurring when equipment is grounded at two separate points with a potential difference between them, producing circulating 50 Hz50\,\text{Hz} current that induces noise and data errors.