EPA Section 608 — Type III Practice Exam: Low-Pressure Appliances

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/34

flashcard set

Earn XP

Description and Tags

Comprehensive practice flashcards for EPA Section 608 Type III certification covering low-pressure appliance fundamentals, leak detection, recovery/evacuation levels, charging procedures, and safety requirements.

35 Terms

1
New cards

What types of systems does an EPA Section 608 Type III certification allow a technician to service or dispose of?

Low-pressure appliances.

2
New cards

Which refrigerant has historically been commonly associated with low-pressure centrifugal chillers?

R-123.

3
New cards

During normal operation, at what pressure level does the evaporator of a low-pressure centrifugal chiller commonly operate?

Below atmospheric pressure.

4
New cards

Because portions of a low-pressure chiller operate below atmospheric pressure, what commonly occurs when a leak develops on the low side?

Air and moisture leak into the system.

5
New cards

What is the primary purpose of a purge unit on a low-pressure chiller?

To remove noncondensable gases that enter the system.

6
New cards

What is excessive operation of a purge unit on a low-pressure chiller a strong indication of?

An air leak into the system.

7
New cards

Why is moisture entering a low-pressure chiller undesirable?

It can contribute to corrosion and the formation of acids.

8
New cards

When checking a low-pressure chiller for leaks, what is generally the preferred first method of raising system pressure?

Use controlled hot water or the system's built-in heating/pressurization device.

9
New cards

If controlled heating cannot raise system pressure sufficiently for leak testing a low-pressure chiller, which gas may be used carefully to increase pressure?

Dry nitrogen.

10
New cards

Why should oxygen or compressed air never be used to pressure-test a refrigeration system?

They can create a fire or explosion hazard when mixed with refrigerant or oil.

11
New cards

How must nitrogen be introduced when adding it to a low-pressure appliance for leak testing?

Through a pressure regulator.

12
New cards

What must technicians be especially careful not to exceed when pressurizing a low-pressure centrifugal chiller for a leak test?

The manufacturer's allowable test pressure.

13
New cards

Which operational condition most strongly suggests that air is continually entering a low-pressure chiller?

The purge unit operates excessively.

14
New cards

A low-pressure appliance containing 500 lb500\,\text{lb} of R-123 is used for comfort cooling and has an annualized leak rate of 12%12\%. Under EPA leak-repair rules for ozone-depleting refrigerants, what action is triggered?

The appliance exceeds the 10%10\% comfort-cooling trigger rate and requires repair.

15
New cards

Before opening a low-pressure appliance for a major repair, what is the generally required evacuation level?

25 mm Hg25\,\text{mm}\,\text{Hg} absolute.

16
New cards

To which recovery equipment manufacturing dates does the EPA evacuation requirement of 25 mm Hg25\,\text{mm}\,\text{Hg} absolute apply for low-pressure appliances?

Either pre- or post-November 15, 1993 recovery equipment.

17
New cards

What is the fastest general approach during refrigerant recovery from a low-pressure chiller?

Recover liquid first, then recover the remaining vapor.

18
New cards

Why must vapor also be recovered after most of the liquid refrigerant has been removed from a low-pressure chiller?

A significant amount of refrigerant can remain as vapor.

19
New cards

Why should water be circulated through the tubes or removed during the evacuation of a water-cooled low-pressure chiller?

Water may freeze as pressure is reduced.

20
New cards

During refrigerant recovery from a low-pressure chiller, why can reducing pressure cause water in the tubes to freeze?

Because its boiling temperature drops as pressure decreases.

21
New cards

After the required evacuation level is reached on a low-pressure appliance and the recovery machine is shut off, the system pressure rises. What does this most likely mean?

Refrigerant may still be trapped in oil or another part of the appliance and is vaporizing.

22
New cards

To what temperature should oil generally be heated before removing it from a low-pressure appliance?

Approximately 130∘F130^\circ\text{F}.

23
New cards

What is the primary benefit of heating oil before removing it from a low-pressure appliance?

It helps minimize the amount of refrigerant released with the oil.

24
New cards

When recharging an evacuated low-pressure centrifugal chiller, in what state should refrigerant initially be introduced?

Vapor.

25
New cards

Why is refrigerant vapor introduced before liquid when charging an evacuated low-pressure chiller?

To raise system pressure and reduce the chance of water freezing in the tubes.

26
New cards

When may liquid refrigerant normally be introduced into a low-pressure centrifugal chiller during charging?

After the system pressure has been raised sufficiently with refrigerant vapor to reduce the risk of freezing.

27
New cards

Through which valve are centrifugal chillers normally charged?

The evaporator charging valve.

28
New cards

For a non-major repair on a low-pressure appliance that will not be evacuated to the environment after the repair, to what pressure must the appliance generally be brought before opening?

0 psig0\,\text{psig}.

29
New cards

What is an acceptable method for bringing a low-pressure appliance to 0 psig0\,\text{psig} for certain non-major repairs?

Controlled hot water or a built-in heating/pressurization device.

30
New cards

What is the applicable annual leak-rate trigger for a comfort-cooling low-pressure chiller containing more than 50 lb50\,\text{lb} of an ozone-depleting refrigerant?

10%10\%.

31
New cards

What is the applicable annual leak-rate trigger for an industrial process refrigeration low-pressure chiller containing more than 50 lb50\,\text{lb} of an ozone-depleting refrigerant?

30%30\%.

32
New cards

Under ASHRAE Standard 15 topics identified for the Type III exam, when does an equipment room require an oxygen-deprivation sensor?

With all refrigerants.

33
New cards

For an equipment room containing an R-123 chiller, what specific detection device is required under Type III safety topics?

A refrigerant sensor.

34
New cards

Why are low-pressure chillers particularly vulnerable to contamination from air and moisture?

Much of the refrigerant side can operate below atmospheric pressure.

35
New cards

After a technician reaches the required 25 mm Hg25\,\text{mm}\,\text{Hg} absolute during recovery from a low-pressure appliance, what should be done before assuming recovery is complete?

Wait several minutes and watch for a pressure rise.