1/34
Comprehensive practice flashcards for EPA Section 608 Type III certification covering low-pressure appliance fundamentals, leak detection, recovery/evacuation levels, charging procedures, and safety requirements.
What types of systems does an EPA Section 608 Type III certification allow a technician to service or dispose of?
Low-pressure appliances.
Which refrigerant has historically been commonly associated with low-pressure centrifugal chillers?
R-123.
During normal operation, at what pressure level does the evaporator of a low-pressure centrifugal chiller commonly operate?
Below atmospheric pressure.
Because portions of a low-pressure chiller operate below atmospheric pressure, what commonly occurs when a leak develops on the low side?
Air and moisture leak into the system.
What is the primary purpose of a purge unit on a low-pressure chiller?
To remove noncondensable gases that enter the system.
What is excessive operation of a purge unit on a low-pressure chiller a strong indication of?
An air leak into the system.
Why is moisture entering a low-pressure chiller undesirable?
It can contribute to corrosion and the formation of acids.
When checking a low-pressure chiller for leaks, what is generally the preferred first method of raising system pressure?
Use controlled hot water or the system's built-in heating/pressurization device.
If controlled heating cannot raise system pressure sufficiently for leak testing a low-pressure chiller, which gas may be used carefully to increase pressure?
Dry nitrogen.
Why should oxygen or compressed air never be used to pressure-test a refrigeration system?
They can create a fire or explosion hazard when mixed with refrigerant or oil.
How must nitrogen be introduced when adding it to a low-pressure appliance for leak testing?
Through a pressure regulator.
What must technicians be especially careful not to exceed when pressurizing a low-pressure centrifugal chiller for a leak test?
The manufacturer's allowable test pressure.
Which operational condition most strongly suggests that air is continually entering a low-pressure chiller?
The purge unit operates excessively.
A low-pressure appliance containing 500lb of R-123 is used for comfort cooling and has an annualized leak rate of 12%. Under EPA leak-repair rules for ozone-depleting refrigerants, what action is triggered?
The appliance exceeds the 10% comfort-cooling trigger rate and requires repair.
Before opening a low-pressure appliance for a major repair, what is the generally required evacuation level?
25mmHg absolute.
To which recovery equipment manufacturing dates does the EPA evacuation requirement of 25mmHg absolute apply for low-pressure appliances?
Either pre- or post-November 15, 1993 recovery equipment.
What is the fastest general approach during refrigerant recovery from a low-pressure chiller?
Recover liquid first, then recover the remaining vapor.
Why must vapor also be recovered after most of the liquid refrigerant has been removed from a low-pressure chiller?
A significant amount of refrigerant can remain as vapor.
Why should water be circulated through the tubes or removed during the evacuation of a water-cooled low-pressure chiller?
Water may freeze as pressure is reduced.
During refrigerant recovery from a low-pressure chiller, why can reducing pressure cause water in the tubes to freeze?
Because its boiling temperature drops as pressure decreases.
After the required evacuation level is reached on a low-pressure appliance and the recovery machine is shut off, the system pressure rises. What does this most likely mean?
Refrigerant may still be trapped in oil or another part of the appliance and is vaporizing.
To what temperature should oil generally be heated before removing it from a low-pressure appliance?
Approximately 130∘F.
What is the primary benefit of heating oil before removing it from a low-pressure appliance?
It helps minimize the amount of refrigerant released with the oil.
When recharging an evacuated low-pressure centrifugal chiller, in what state should refrigerant initially be introduced?
Vapor.
Why is refrigerant vapor introduced before liquid when charging an evacuated low-pressure chiller?
To raise system pressure and reduce the chance of water freezing in the tubes.
When may liquid refrigerant normally be introduced into a low-pressure centrifugal chiller during charging?
After the system pressure has been raised sufficiently with refrigerant vapor to reduce the risk of freezing.
Through which valve are centrifugal chillers normally charged?
The evaporator charging valve.
For a non-major repair on a low-pressure appliance that will not be evacuated to the environment after the repair, to what pressure must the appliance generally be brought before opening?
0psig.
What is an acceptable method for bringing a low-pressure appliance to 0psig for certain non-major repairs?
Controlled hot water or a built-in heating/pressurization device.
What is the applicable annual leak-rate trigger for a comfort-cooling low-pressure chiller containing more than 50lb of an ozone-depleting refrigerant?
10%.
What is the applicable annual leak-rate trigger for an industrial process refrigeration low-pressure chiller containing more than 50lb of an ozone-depleting refrigerant?
30%.
Under ASHRAE Standard 15 topics identified for the Type III exam, when does an equipment room require an oxygen-deprivation sensor?
With all refrigerants.
For an equipment room containing an R-123 chiller, what specific detection device is required under Type III safety topics?
A refrigerant sensor.
Why are low-pressure chillers particularly vulnerable to contamination from air and moisture?
Much of the refrigerant side can operate below atmospheric pressure.
After a technician reaches the required 25mmHg absolute during recovery from a low-pressure appliance, what should be done before assuming recovery is complete?
Wait several minutes and watch for a pressure rise.