List the components of a typical natural draft venting system
Vent pipe
Supports
Fire stop spacers
Roof Flashing
Storm collar
Vent Cap
What are the four functions of a venting system
Removes the flue products to the outdoors
Prevents damage from condensation
Protects the building from fire hazard
Provides air circulation
Name two products produced by complete combustion of natural gas or propane
Carbon Dioxide
Water Vapour
What are the conditions that provide a natural draft venting system with the greatest amount of draft
High stack temperature
Low outdoor temperature
High stack height
What type of venting system relies on the upward movement of hot gases
Natural draft vent
What device allows dilution air to enter the venting system of an atmospherically fired appliance
Draft hoods
Which type of vent is required when flue gas temperatures exceed 470F
Chimney Type A
Which type of vent has a double-wall construction with a dead air space between the walls
Type B Vent
Type BW vent
Type L vent
Which type of vent draws in combustion air emits flue gases from the same vent
Direct Vent
List four common venting problems
Excessive laterals
Blockage
Excessive change of direction
Incorrect or missing vent caps
Describe the function of the following type B vent components
Supports vent stack
Maintains clearance from combustion material
Fire stop spacer
Block stack effect during a fire and maintains clearances from combustible material
Roof flashing/storm collar
Prevents moisture from entering home
Vent cap
Prevents moisture or foreign object from entering vent system
How does increasing vent temperature or height affect the draft of a natural draft venting system
It increases the draft
Term for steel or masonry chimney
Type A
Term for double wall vent with aluminum inside
Type B
Term for double wall vent with stainless steel inside
Type L
Term for double wall(oval) with aluminum inside
Type BW
Term for single thickness of galvanized or aluminum
Single wall or Type C
Term for venting system under positive pressure
Type BH
To what ULC standard must all plastic material used in type BH venting system be approved
U.L.C standard S636
Can a chimney with a clay tile liner be lined with a metallic liner system
Yes Some types of applications and situation requires a liner to be installed to prevent condensation
Direct vent appliance
(a) Where does it take it's air from
Outside
How is this accomplished
The unit is sealed and a seperate pipe is used for the exhaust and the intake and there are no openings to the interior of the building
State three situations where they are used
When a hazardous atmosphere exists in a building
When a building may experience negative pressure
When it is not favorable to use a natural draft Vent
List styles of draft hoods
Vertical
Horizontal
Describe the functions of a draft hood with respect to Temperature and humidity of the flue products
Dilutes the flue products to reduce the temperature and humidity
Describe the functions of a draft hood with respect to Stack effect on the combustion chamber
Negates the effect of the chimney draft to stabilize the combustion process
Describe the functions of a draft hood with respect to Handling of down draft
Diverts the down-draft away from the combustion chamber to reduce the chances of (Co) production during a down draft condition
Explain the operation of the following barometric dampers Double Acting
Swings into regulate the stack draft and also swing s out to relieve a down daft into the room
Explain the operation of the following barometric dampers Single Acting
Only swing into regulate the stack draft and closes shut when a double draft is present to prevent soot or ashes from entering
When is a single acting barometric damper allowed on a propane or natural draft appliance
For an incinerator only
What determines the adjustment of a barometric damper
-The type of burner
-Combustion chamber
- Manufacturer's literature
Describe the effect on an appliance with a barometric damper if, The stack draft is increased
-It will raise
- Neutral pressure pointed
-Lowers the efficiency
Describe the effect on an appliance with a barometric damper if, The stack is decreased
Will lower the neutral pressure point
Increase the efficiency to a point (Co) can be produce
How many screws are required at each joint of single wall material
Three
Why do designed boiler and water heater manufacturers stamp the distance from the draft hood skirt to the top of the boiler on the draft hood and why is this extremely important
-Prevents Shortening of Flue pipe to accommodate the installed.
-The burner neutral pressure point will lower
-Excess air will lower to the point of producing carbon Monoxide
Describe the undesirable effects of a vent connector coming loose and falling off a gas appliance
Flue products could have (Co)
Recirculation of Flue products could cause (Co)
Resulting personal injury or death to the building occupants
How will the following appliances react to a block vent
Will spill flue products into the room
Appliance with a fan assisted combustion system
A shut off switch will activate to shut down the burner
Natural draft appliance equipped with a spill switch
The spill switch will shut the appliance down and require resetting
Air is drawn in by the vacuum created by the injection of gas to the burner
Inspirator
Air moving through the burner creates a negative pressure that draws the gas into the burner to be mixed
Aspirator
Gas is drawn in by the negative pressure created by a blower that is also drawing in air for combustion
Blower Mix
A regulator designed to supply gas at or atmospheric pressure when a vacuum is induced on it
Zero Govenor
Air drawn into burner by Venting action
Atmospheric Burner
Air is supplied to burner under enough pressure to overcome resistance of burner only
Fan Assist Burner
Air is supplied to burner under enough pressure to overcome the resistance of the burner and the appliance
Force Draft Power burner
Air and gas are mixed completely before introduction to the chamber by inspiration aspiration or blower mix methods
Pre-mix Burner
Which atmospheric burners are the most susceptible to flashback
Mono Port
What helps to keep the flame retained at the burner port of a mono port burner
Crimped ring
What is multi port burner susceptible to
Clogging with lint from the inside
What term is used to describe a burner flame that moves back through the burner nozzle
Flashback
Through which device is fuel discharged to an atmospheric burner
Orifice
Which type of atmospheric burner produces a single large flame
Single or mono port burner
List four common types of multi port atmospheric burners
Drilled Port
Drilled Pipe
Slotted Port
Ribbon Port
What are the recommended minimum and maximum port diameters for drilled port atmospheric burners
Maximum No 29 Drill
Minimum No 42 Drill
Which type of burner has combustion air supplied by a fan or blower under sufficient pressure to overcome the restriction of the burner and the appliance
Force Draft Burner
Which type of burner has a fan located downstream of the combustion zone
Induced Draft burner
What provides the kinetic energy to entrain the gas required for a premixing inspritor burner
The gas coming out of the orifice into a gas jet mixer
What device is used to regulate gas supply to an aspirator type burner
Zero Governor
Which type of burner provides complete premixing using mechanical mixers
Blow Mix
How do you correct Lifting flame with an atmospheric burner
Reduce primary Air
Reduce appliance input rate
Only if higher than specified on the appliance rating plate
How do you correct Yellow tipping with an atmospheric burner
Clean burners thoroughly
Adjust primary air opening
How do you correct Flame roll-out(Steady) with an atmospheric burner
Heat exchanger blocked or cracked on a forced air furnace
if not check appliance input rate
How do you correct Flame roll-out (Upon ignition)with an atmospheric burner
Check for correct manifold pressure settings and that the proper types of gas controls are used for the appliance
What are the two basic types of pilot burners?
-Aerated Pilots
-Non aerating pilots
What is the most common problem associated with aerated pilots
Clogging due to dust or lint
When you discover a noisy, lifting, blowing flame on a non-aerating pilot,what is the cause of the problem and remedy?
Cause high gas pressure
Reduce gas pressure
Explain the term proved pilot
A pilot flame supervised by a flame safeguard control
-Detects the pressure of a flame before allowing the main fuel valves to open
How is a piezoelectric voltage generated
Through a mechanical force
How has the use of modern automatic ignition systems affected the time in which a flame failure is detected
Flame failure is detected much faster
What causes the bi-metal strip to curve with changes in temperature?
The two metals that are joined have different temperature coefficients of expasion
What causes the resistance of a thermistor to change
A temperature change
Describe a constant pilot?
Remains on all the time
Describe a Intermittent pilot
Remains on during the firing cycle
Describe a Interrupted pilot
-Turns on to light the main flame
-Extinguished after the flame has been proved
Describe a Standing Pilot
Pilot remains on all the time regardless of whether sensed or not.
Describe 100% Safety
Pilot and Main Burners are shut off if flame is not sensed
Describe a spark ignited pilot
Pilot is lit, or re-lit by a spark
Describe a Hot surface ignition
Pilot or main burner is ignited by hot surface device(Glow Bar)
Flame sensing method: Constant Supervision
Supervises the flame and must be in constant attendance
Flame sensing method: Bi-metal
Two different metals are bonded
Warps in change to temperature
Warping activates a switch to gas valve
Flame sensing method: Bulb and Bellows
-A Bulb filled with fluid senses medium temperature
-Bellows that will expand or contract when temperature changes
-Expanding Bellows activates a switch to control gas flow to Burner
Flame sensing method: Thermistor
-Electrical resistance changes in response to temperature
-Control responds to resistance which operates a switch to control gas flow to burner
Flame sensing method: Thermocouple
Hot junction is heated by the pilot flame
Voltage is generated closing a pilot valve/Switch
Flame sensing method: Optical sensors
Allows gas to conduct electricity
What is the purpose of an operating aqua-stat
Energize or D-energize the main gas valve in response to the water temperature (180F)
Is the temperature setting of a high-limit aqua-stat higher or lower than the setting of the operating aqua-stat?
Higher
Does the furnace fan continue to run if the high-limit switch opens the furnace control circuit?
Yes
What causes the contacts of a steam boiler operating pressure control to open
A rise in steam pressure
Name two types of low water cut-off switches used on gas-fired boilers
-Probe Type
-Float Type
What activates a flame roll-out switch
A raise in temperature
Senses the operation of a circulating pump
Flow Switch!
A water temperature sensing device that will shut off the burner if the temperature exceeds the desired operating range of the boiler or water heater
High Limit Aqua-Stat!
Shuts off the burner in the event that the pressure in a boiler exceed it's desired operating range
High Limit Pressure Switch!
Turns a steam boiler on and off to maintain a desired steam pressure
Operating Pressure Switch!
Turns a boiler or water heater on and off to maintain a desired water temperature
Operating Aqua-Stat!
Shuts the burner off if the water level in a system falls below a desired point
Lower-Water Cut Off Switch!