AP2 Cheat Sheet: Industrial Electrician (Elektroniker Betriebstechnik)

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/34

flashcard set

Earn XP

Description and Tags

Comprehensive vocabulary and core technical flashcards for the final examination (AP2) of industrial electricians (Elektroniker für Betriebstechnik), covering electrical engineering fundamentals, machines, control systems, power electronics, installations, safety standards, and business operations.

35 Terms

1
New cards

Total Efficiency (ηges\eta_{\text{ges}}) of Multi-Stage Systems

The product of all individual stage efficiencies: ηges=η1×η2×…\eta_{\text{ges}} = \eta_1 \times \eta_2 \times \dots. Each individual efficiency is the ratio of output power to input power (η=PabPzu\eta = \frac{P_{\text{ab}}}{P_{\text{zu}}}).

2
New cards

Balanced Bridge (Abgeglichene Brücke)

A bridge circuit configuration where the diagonal voltage (U12U_{12}) is zero because the resistance ratio of the two divider branches is identical: R1R2=R3R4\frac{R_1}{R_2} = \frac{R_3}{R_4}.

3
New cards

Star-Delta Starting (Stern-Dreieck-Anlauf)

A motor starting method requiring six winding terminals where the winding is rated for delta on the given mains voltage; reduces starting current and torque to one third (IAY≈13IAΔI_{\text{AY}} \approx \frac{1}{3} I_{\text{A}\Delta} and MAY≈13MAΔM_{\text{AY}} \approx \frac{1}{3} M_{\text{A}\Delta}) compared to direct-on-line start.

4
New cards

Motor Slip (ss)

The relative speed difference between synchronous rotating field speed (nsn_{\text{s}}) and actual rotor speed (nn), defined as s=ns−nnss = \frac{n_{\text{s}} - n}{n_{\text{s}}}. In motor operation, the rotor rotates slower than the field, and increasing load leads to larger slip.

5
New cards

Motor Duty Types S1, S2, and S3

Standard operating regimes: S1 denotes continuous operation (Dauerbetrieb); S2 denotes short-time operation (Kurzzeitbetrieb) followed by cooling; S3 denotes periodic intermittent operation (periodischer Aussetzbetrieb) where the duty cycle (ED=tBetriebtZyklus\text{ED} = \frac{t_{\text{Betrieb}}}{t_{\text{Zyklus}}}) must be observed.

6
New cards

87-Hz Characteristic Curve (87-Hz-Kennlinie)

A drive operating mode requiring a suitable motor and frequency inverter configured in delta connection, maintaining a constant voltage-to-frequency ratio (U/fU/f) up to 87 Hz87\,\text{Hz} without field weakening, while observing thermal, current, and mechanical limits.

7
New cards

Dahlander Motor Connection

A pole-changing configuration using a single tapped, switchable winding to achieve two pole numbers, typically resulting in a speed ratio of 1:21:2.

8
New cards

P-Controller (Proportional-Regler)

A controller whose output change is proportional to the control error (Δy=Kp⋅e\Delta y = K_{\text{p}} \cdot e); it responds immediately to deviations but exhibits a permanent steady-state deviation (bleibende Regeldifferenz) when controlling a P-plant under sustained disturbance.

9
New cards

I-Controller (Integral-Regler)

A controller that integrates the control deviation (ee) over time; in stable and unsaturated operation, it completely eliminates steady-state control error.

10
New cards

Derivative Component (D-Anteil)

A control component that reacts solely to the rate of change of the control error (dedt\frac{de}{dt}); it has zero effect under constant deviation and tends to amplify measurement noise.

11
New cards

Two-Point Controller Hysteresis

The difference between the turn-on and turn-off threshold levels of a two-point controller, designed to prevent rapid oscillatory switching around the setpoint.

12
New cards

Reset-Dominant Memory (Rücksetzdominanter Speicher)

A bistable storage element in PLC logic where the reset signal takes priority whenever both set and reset inputs are active simultaneously (S=1S = 1 and R=1R = 1).

13
New cards

GRAFCET Transition Condition

The logic condition between two GRAFCET steps that clears and advances execution to subsequent steps only when the immediately preceding step is active and its condition evaluates to true.

14
New cards

Pt100 Temperature Sensor

A platinum resistance temperature detector with a nominal resistance of 100 Ω100\,\Omega at 0 ∘C0\,^\circ\text{C} and a positive temperature coefficient (PTC), causing resistance to increase as temperature rises.

15
New cards

Live-Zero Standard (4–20 mA4\text{–}20\,\text{mA})

An analog signaling standard where 4 mA4\,\text{mA} represents the lower measurement threshold (xminx_{\text{min}}) and 20 mA20\,\text{mA} represents the upper threshold (xmaxx_{\text{max}}), using the 16 mA16\,\text{mA} span for scaling while distinguishing a valid zero value from a broken wire (0 mA0\,\text{mA}).

16
New cards

Strain Gauge (Dehnungsmessstreifen / DMS)

A sensor that translates mechanical strain (ε\varepsilon) into a proportional change in electrical resistance (ΔRR=k⋅ε\frac{\Delta R}{R} = k \cdot \varepsilon), commonly measured using a Wheatstone bridge circuit.

17
New cards

Power Factor (Total) vs. Displacement Factor

The displacement factor cos⁡(φ)\cos(\varphi) accounts only for the phase angle between fundamental current and voltage, whereas the total power factor λ=PS\lambda = \frac{P}{S} accounts for harmonic distortion as well; with distorted currents, λ≠cos⁡(φ)\lambda \neq \cos(\varphi).

18
New cards

Frequency Inverter Architecture

A three-stage power converter composed of a Rectifier (Gleichrichter), DC intermediate circuit (Zwischenkreis), and Inverter (Wechselrichter) that controls motor speed by adjusting the output frequency and voltage.

19
New cards

Soft Starter (Sanftanlauf)

A solid-state starting device that lowers starting current and mechanical stress by providing a voltage ramp; it also reduces starting torque and does not allow permanent variable speed control.

20
New cards

Free-Wheeling Diode (Freilaufdiode)

A diode connected antiparallel across a DC inductive load (coil) to safely clamp and discharge the self-induction voltage spike produced when switching off.

21
New cards

Short-Circuit Voltage (uku_{\text{k}} / Kurzschlussspannung)

The primary voltage applied during a transformer short-circuit test to drive rated nominal current, expressed as a percentage of nominal voltage (uk=UKUN×100 %u_{\text{k}} = \frac{U_{\text{K}}}{U_{\text{N}}} \times 100\,\%); a smaller uku_{\text{k}} yields a higher prospective short-circuit current (Ik≈IN×100uk [%]I_{\text{k}} \approx \frac{I_{\text{N}} \times 100}{u_{\text{k}}\,[\%]}).

22
New cards

Vector Group Clock-Hour Number (Schaltgruppenuhrzahl)

A transformer designation indicating the phase shift angle between primary and secondary windings in discrete steps of 30∘30^\circ (φ=k×30∘\varphi = k \times 30^\circ).

23
New cards

Five Safety Rules (Fünf Sicherheitsregeln)

The five binding steps for working on de-energized electrical installations: 1. Disconnect completely (Freischalten); 2. Secure against re-connection; 3. Verify absence of voltage; 4. Ground and short-circuit; 5. Cover or barrier adjacent live parts.

24
New cards

Electrical Protection Classes (Schutzklassen I, II, III)

Class I utilizes protective bonding via the protective earth conductor (PE); Class II provides protection by double or reinforced insulation without PE; Class III relies on safety extra-low voltage (SELV/PELV).

25
New cards

Residual Current Device (RCD / Fehlerstrom-Schutzeinrichtung)

A safety device that monitors the sum of currents across all active conductors through a summation transformer to disconnect on leakage/differential currents; the protective earth (PE) must never pass through its core.

26
New cards

Type B Circuit Breaker Instantaneous Trip

The magnetic instantaneous tripping threshold used for verifying loop impedance disconnection compliance (ZS≤U0IaZ_{\text{S}} \le \frac{U_0}{I_{\text{a}}}), evaluated at the upper characteristic limit of Ia=5×InI_{\text{a}} = 5 \times I_{\text{n}}.

27
New cards

EMERGENCY STOP vs. EMERGENCY OFF (NOT-HALT und NOT-AUS)

NOT-HALT is designed to bring a dangerous motion or mechanical process to a halt; NOT-AUS is intended to de-energize electrical energy to eliminate electrical hazards. Unlocking neither may trigger an automatic restart.

28
New cards

IP Ingress Protection Code (IP-Schutzart)

A standard enclosure rating where the first digit indicates protection against ingress of foreign solid objects and access to hazardous parts, and the second digit indicates protection against water; 'X' signifies no declared specification.

29
New cards

Tandem Connection (Tandemschaltung)

A fluorescent lighting arrangement running two fluorescent tubes in series using a single compatible ballast/choke and two specialized tandem starters.

30
New cards

Shuttle Valve vs. Dual-Pressure Valve (Pneumatik)

In pneumatics, a shuttle valve (Wechselventil) functions as an OR logic element, while a dual-pressure valve (Zweidruckventil) functions as an AND logic element.

31
New cards

DIN Maintenance Categories (Wartung, Inspektion, Instandsetzung, Verbesserung)

Four defined maintenance measures: Wartung (servicing to delay wear), Inspektion (inspection to assess condition), Instandsetzung (repair to restore function), and Verbesserung (improvement to raise reliability without altering primary function).

32
New cards

Lastenheft vs. Pflichtenheft

A Lastenheft is compiled by the client defining 'what' is required and the scope of demand; a Pflichtenheft is prepared by the contractor detailing 'how' the requirements will technically be implemented.

33
New cards

Works Council Election Cycle (Betriebsrat)

The regular statutory term and general election interval for the works council (Betriebsrat), occurring every 4 years4\,\text{years}.

34
New cards

Minimum Share Capital: GmbH vs. AG

Statutory minimum share capital required under German corporate law: 25,000 €25{,}000\,\text{€} (Stammkapital) for a GmbH and 50,000 €50{,}000\,\text{€} (Grundkapital) for an AG.

35
New cards

Productivity vs. Economic Efficiency (Produktivität vs. Wirtschaftlichkeit)

Productivity is a physical quantity ratio (Output QuantityInput Quantity\frac{\text{Output Quantity}}{\text{Input Quantity}}, e.g., ProduktionsmengeArbeitszeit\frac{\text{Produktionsmenge}}{\text{Arbeitszeit}}), whereas economic efficiency is a monetary value ratio (ErtragAufwand\frac{\text{Ertrag}}{\text{Aufwand}}).