Comprehensive vocabulary and core technical flashcards for the final examination (AP2) of industrial electricians (Elektroniker für Betriebstechnik), covering electrical engineering fundamentals, machines, control systems, power electronics, installations, safety standards, and business operations.
Total Efficiency (ηges) of Multi-Stage Systems
The product of all individual stage efficiencies: ηges=η1×η2×…. Each individual efficiency is the ratio of output power to input power (η=PzuPab).
Balanced Bridge (Abgeglichene Brücke)
A bridge circuit configuration where the diagonal voltage (U12) is zero because the resistance ratio of the two divider branches is identical: R2R1=R4R3.
Star-Delta Starting (Stern-Dreieck-Anlauf)
A motor starting method requiring six winding terminals where the winding is rated for delta on the given mains voltage; reduces starting current and torque to one third (IAY≈31IAΔ and MAY≈31MAΔ) compared to direct-on-line start.
Motor Slip (s)
The relative speed difference between synchronous rotating field speed (ns) and actual rotor speed (n), defined as s=nsns−n. In motor operation, the rotor rotates slower than the field, and increasing load leads to larger slip.
Motor Duty Types S1, S2, and S3
Standard operating regimes: S1 denotes continuous operation (Dauerbetrieb); S2 denotes short-time operation (Kurzzeitbetrieb) followed by cooling; S3 denotes periodic intermittent operation (periodischer Aussetzbetrieb) where the duty cycle (ED=tZyklustBetrieb) must be observed.
87-Hz Characteristic Curve (87-Hz-Kennlinie)
A drive operating mode requiring a suitable motor and frequency inverter configured in delta connection, maintaining a constant voltage-to-frequency ratio (U/f) up to 87Hz without field weakening, while observing thermal, current, and mechanical limits.
Dahlander Motor Connection
A pole-changing configuration using a single tapped, switchable winding to achieve two pole numbers, typically resulting in a speed ratio of 1:2.
P-Controller (Proportional-Regler)
A controller whose output change is proportional to the control error (Δy=Kp⋅e); it responds immediately to deviations but exhibits a permanent steady-state deviation (bleibende Regeldifferenz) when controlling a P-plant under sustained disturbance.
I-Controller (Integral-Regler)
A controller that integrates the control deviation (e) over time; in stable and unsaturated operation, it completely eliminates steady-state control error.
Derivative Component (D-Anteil)
A control component that reacts solely to the rate of change of the control error (dtde); it has zero effect under constant deviation and tends to amplify measurement noise.
Two-Point Controller Hysteresis
The difference between the turn-on and turn-off threshold levels of a two-point controller, designed to prevent rapid oscillatory switching around the setpoint.
Reset-Dominant Memory (Rücksetzdominanter Speicher)
A bistable storage element in PLC logic where the reset signal takes priority whenever both set and reset inputs are active simultaneously (S=1 and R=1).
GRAFCET Transition Condition
The logic condition between two GRAFCET steps that clears and advances execution to subsequent steps only when the immediately preceding step is active and its condition evaluates to true.
Pt100 Temperature Sensor
A platinum resistance temperature detector with a nominal resistance of 100Ω at 0∘C and a positive temperature coefficient (PTC), causing resistance to increase as temperature rises.
Live-Zero Standard (4–20mA)
An analog signaling standard where 4mA represents the lower measurement threshold (xmin) and 20mA represents the upper threshold (xmax), using the 16mA span for scaling while distinguishing a valid zero value from a broken wire (0mA).
Strain Gauge (Dehnungsmessstreifen / DMS)
A sensor that translates mechanical strain (ε) into a proportional change in electrical resistance (RΔR=k⋅ε), commonly measured using a Wheatstone bridge circuit.
Power Factor (Total) vs. Displacement Factor
The displacement factor cos(φ) accounts only for the phase angle between fundamental current and voltage, whereas the total power factor λ=SP accounts for harmonic distortion as well; with distorted currents, λ=cos(φ).
Frequency Inverter Architecture
A three-stage power converter composed of a Rectifier (Gleichrichter), DC intermediate circuit (Zwischenkreis), and Inverter (Wechselrichter) that controls motor speed by adjusting the output frequency and voltage.
Soft Starter (Sanftanlauf)
A solid-state starting device that lowers starting current and mechanical stress by providing a voltage ramp; it also reduces starting torque and does not allow permanent variable speed control.
Free-Wheeling Diode (Freilaufdiode)
A diode connected antiparallel across a DC inductive load (coil) to safely clamp and discharge the self-induction voltage spike produced when switching off.
Short-Circuit Voltage (uk / Kurzschlussspannung)
The primary voltage applied during a transformer short-circuit test to drive rated nominal current, expressed as a percentage of nominal voltage (uk=UNUK×100%); a smaller uk yields a higher prospective short-circuit current (Ik≈uk[%]IN×100).
Vector Group Clock-Hour Number (Schaltgruppenuhrzahl)
A transformer designation indicating the phase shift angle between primary and secondary windings in discrete steps of 30∘ (φ=k×30∘).
Five Safety Rules (Fünf Sicherheitsregeln)
The five binding steps for working on de-energized electrical installations: 1. Disconnect completely (Freischalten); 2. Secure against re-connection; 3. Verify absence of voltage; 4. Ground and short-circuit; 5. Cover or barrier adjacent live parts.
Electrical Protection Classes (Schutzklassen I, II, III)
Class I utilizes protective bonding via the protective earth conductor (PE); Class II provides protection by double or reinforced insulation without PE; Class III relies on safety extra-low voltage (SELV/PELV).
Residual Current Device (RCD / Fehlerstrom-Schutzeinrichtung)
A safety device that monitors the sum of currents across all active conductors through a summation transformer to disconnect on leakage/differential currents; the protective earth (PE) must never pass through its core.
Type B Circuit Breaker Instantaneous Trip
The magnetic instantaneous tripping threshold used for verifying loop impedance disconnection compliance (ZS≤IaU0), evaluated at the upper characteristic limit of Ia=5×In.
EMERGENCY STOP vs. EMERGENCY OFF (NOT-HALT und NOT-AUS)
NOT-HALT is designed to bring a dangerous motion or mechanical process to a halt; NOT-AUS is intended to de-energize electrical energy to eliminate electrical hazards. Unlocking neither may trigger an automatic restart.
IP Ingress Protection Code (IP-Schutzart)
A standard enclosure rating where the first digit indicates protection against ingress of foreign solid objects and access to hazardous parts, and the second digit indicates protection against water; 'X' signifies no declared specification.
Tandem Connection (Tandemschaltung)
A fluorescent lighting arrangement running two fluorescent tubes in series using a single compatible ballast/choke and two specialized tandem starters.
Shuttle Valve vs. Dual-Pressure Valve (Pneumatik)
In pneumatics, a shuttle valve (Wechselventil) functions as an OR logic element, while a dual-pressure valve (Zweidruckventil) functions as an AND logic element.
DIN Maintenance Categories (Wartung, Inspektion, Instandsetzung, Verbesserung)
Four defined maintenance measures: Wartung (servicing to delay wear), Inspektion (inspection to assess condition), Instandsetzung (repair to restore function), and Verbesserung (improvement to raise reliability without altering primary function).
Lastenheft vs. Pflichtenheft
A Lastenheft is compiled by the client defining 'what' is required and the scope of demand; a Pflichtenheft is prepared by the contractor detailing 'how' the requirements will technically be implemented.
Works Council Election Cycle (Betriebsrat)
The regular statutory term and general election interval for the works council (Betriebsrat), occurring every 4years.
Minimum Share Capital: GmbH vs. AG
Statutory minimum share capital required under German corporate law: 25,000€ (Stammkapital) for a GmbH and 50,000€ (Grundkapital) for an AG.
Productivity vs. Economic Efficiency (Produktivität vs. Wirtschaftlichkeit)
Productivity is a physical quantity ratio (Input QuantityOutput Quantity, e.g., ArbeitszeitProduktionsmenge), whereas economic efficiency is a monetary value ratio (AufwandErtrag).