What is the ozone layer?
It is part of Earth's protective shield that protects Earth from harmful ultraviolet (UV) radiation.
What does Ozone Depletion Potential (ODP) measure?
ODP measures a substance's ability to destroy ozone in the stratosphere.
Name one effect of ozone depletion.
Increased skin cancer.
What is a major contributor to ozone depletion?
Chlorine found in CFC and HCFC refrigerants.
How long can a chlorine atom last in the stratosphere?
120 years.
How many ozone molecules can one chlorine atom destroy?
Up to 100,000.
What is Global Warming Potential (GWP)?
GWP compares the global warming impact of different gases over a period of time.
What is the GWP of carbon dioxide (CO₂)?
1.
What refrigerant family has high ozone depletion potential?
CFC (Chlorofluorocarbon).
What does HCFC stand for?
Hydrochlorofluorocarbon.
What is the characteristic of HFC refrigerants?
They contain hydrogen, fluorine, and carbon, and have no ozone depletion potential.
What is the main feature of HFO refrigerants?
They have no ODP and very low GWP.
What does ASHRAE stand for?
American Society of Heating, Refrigerating and Air-Conditioning Engineers.
What does an A1 ASHRAE classification indicate?
Lower toxicity and no flammability.
What is the difference between azeotropic and zeotropic refrigerants?
Azeotropic mixtures evaporate and condense at a constant temperature, while zeotropic mixtures have different boiling points.
What is temperature glide?
The temperature difference that occurs during evaporation or condensation of a blended refrigerant.
What is the bubble point used for?
Charging by condenser subcooling.
What is the dew point used for?
Charging by suction or evaporator superheat.
What is fractionation in refrigerants?
Uneven leakage of refrigerant components, changing the composition of the remaining blend.
What is the classification of refrigerants based on pressure at a condensing temperature of 104°F?
Low, medium, high, and very high-pressure refrigerants.
What is an important safety point regarding propane cylinders?
Never use propane cylinders intended for grilling as refrigerant due to potential impurities.
What is the environmental impact of HFC refrigerants?
They do not destroy the ozone layer but can contribute significantly to global warming.
What is the example of a refrigerant with very low GWP?
HFO refrigerants.
What is the importance of R-407C?
It has high temperature glide and can experience fractionation.
What is the pressure classification for low pressure refrigerants?
30 psig or lower
What refrigerants are classified as low pressure?
R-11, R-123, R-245fa, R-1233zd
What is the pressure classification for medium pressure refrigerants?
Above 30 to 155 psig
What refrigerants are classified as medium pressure?
R-12, R-134a, R-600a, R-1234yf
What is the pressure classification for high pressure refrigerants?
Above 155 to 340 psig
What refrigerants are classified as high pressure?
R-22, R-404A, R-407C, R-410A, R-717
What is the pressure classification for very high pressure refrigerants?
Above 340 psig
What refrigerant is classified as very high pressure?
CO₂ (R-744)
What are the two important types of refrigerant oils?
Alkylbenzene and POE (Polyolester)
What is a key characteristic of POE oil?
It is highly hygroscopic, meaning it absorbs moisture from the air.
What does the Montreal Protocol address?
Ozone-depleting substances and their alternatives.
What does Section 608 of the Clean Air Act establish?
Rules and regulations for refrigerant handling in the HVACR industry.
What is required for technicians handling regulated refrigerants?
Section 608 certification.
What is the penalty for knowingly releasing CFC, HCFC, or HFC refrigerants?
It is illegal and can result in fines and loss of certification.
What is the maximum fine per day for violations as of 2017?
$44,539 per day, per violation.
What does the EPA's SNAP program do?
Identifies refrigerant alternatives with lower overall risks to human health and the environment.
What must be done before disposing of an appliance containing refrigerant?
Recover the refrigerant to the required EPA recovery or evacuation level.
What is the difference between recovering, recycling, and reclaiming refrigerants?
Recover = Remove, Recycle = Clean, Reclaim = Restore to virgin specifications.
What are the two basic types of recovery devices?
System-dependent (passive) and self-contained (active).
What increases recovery time for refrigerants?
Low ambient temperatures, long hoses, and long small-diameter hoses.
What is the purpose of using dry nitrogen in leak detection?
To pressurize a newly installed system for leak testing.
What should be done after repairing a leak?
Install a new filter-drier.
What is dehydration in the context of refrigerants?
The process of removing moisture from refrigerant systems.
What is a critical safety rule after transferring liquid refrigerant?
Prevent liquid from becoming trapped in a service hose between closed service valves.
Why should separate recovery cylinders be used?
To avoid mixing refrigerants, which may be impossible to reclaim.
What must reclaimed refrigerant meet before it can be resold?
AHRI Standard 700.
What is dehydration in refrigeration?
Removing water and water vapor from a refrigeration system.
Why is dehydration important?
Moisture can cause hydrochloric acid and hydrofluoric acid to form in an operating refrigeration system.
What is the most important evacuation number for dehydration?
500 microns or lower.
What tool measures the vacuum level during evacuation?
A micron gauge.
What factors affect evacuation speed?
Size of the equipment, ambient temperature, amount of moisture, size of the vacuum pump, and size of the vacuum hoses.
What is a proper vacuum setup for evacuation?
Use hoses equal to or larger than the pump intake, keep connections short, use large diameter hoses, and place the vacuum gauge far from the pump.
What indicates that a refrigeration system has a leak?
If the system won't hold a vacuum.
How can dehydration time be decreased?
Heating the refrigeration system or tapping the compressor with a rubber mallet.
What does it mean if the micron gauge reaches and holds 500 microns or lower?
Dehydration is complete.
What should you never do with refrigerant during evacuation?
Never evacuate refrigerant directly into the atmosphere.
What personal protective equipment should be worn when handling refrigerants?
Safety glasses, protective gloves, and equipment-specific protection.
What should be done when pressurizing a system with nitrogen?
Use a pressure regulator and install a relief valve downstream.
Why should oxygen or compressed air never be used to pressurize a refrigeration system?
It can cause an explosion when mixed with certain refrigerants or compressor oil.
What can high temperatures do to refrigerants?
They can decompose refrigerants and create dangerous acids.
What acids can be formed from chlorine and fluorine in refrigerants?
Chlorine forms hydrochloric acid, and fluorine forms hydrofluoric acid.
What is the danger of flammable refrigerants?
An explosion can occur when concentrations are between the Lower and Upper Flammability Limits with an ignition source.
What is required for refrigerant cylinders carrying flammable refrigerants?
They must have red markings extending at least one inch from service connection points.
What are the possible effects of inhaling high concentrations of refrigerant vapor?
Heart irregularities, unconsciousness, oxygen deprivation, and death by asphyxiation.
What should be done in case of a large refrigerant release?
Immediately vacate and ventilate the area; properly equipped personnel should use SCBA to enter.
What are the requirements for recovery cylinders?
They must have a yellow top, gray body, be free of rust, and properly labeled.
What is the maximum filling capacity for recovery cylinders?
80% by weight.
How can you control the fill level of a recovery cylinder?
Using a mechanical float device, electronic shut-off device, or measuring gross cylinder weight.
How often must reusable high-pressure refrigerant containers be hydrostatically tested?
Every five years.
What should be done with disposable refrigerant cylinders?
Recover remaining vapor and reduce pressure to 0 psig before scrapping.
What should never be done to a refrigerant cylinder?
Never heat it with an open flame.
What is required when transporting used refrigerants?
Attach the appropriate DOT classification tag and label, and use portable refillable tanks that meet DOT standards.
Why is it important to label refrigerant cylinders?
To prevent accidental mixing, allow recyclers to identify contents, and help track the quantity of refrigerant recovered.
What is the ozone molecule's chemical formula?
O₃.
What is the Global Warming Potential (GWP) of CO₂?
1.
What is the chlorine lifetime in the atmosphere?
120 years.
How many ozone molecules can be destroyed by one chlorine molecule?
Up to 100,000.
What is the standard evacuation level for refrigeration systems?
500 microns or lower.