EPA Section 608 Core Certification Exam: Refrigerant Rules, Recovery, and Safety

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/81

encourage image

There's no tags or description

Looks like no tags are added yet.

82 Terms

1
New cards

What is the ozone layer?

It is part of Earth's protective shield that protects Earth from harmful ultraviolet (UV) radiation.

2
New cards

What does Ozone Depletion Potential (ODP) measure?

ODP measures a substance's ability to destroy ozone in the stratosphere.

3
New cards

Name one effect of ozone depletion.

Increased skin cancer.

4
New cards

What is a major contributor to ozone depletion?

Chlorine found in CFC and HCFC refrigerants.

5
New cards

How long can a chlorine atom last in the stratosphere?

120 years.

6
New cards

How many ozone molecules can one chlorine atom destroy?

Up to 100,000.

7
New cards

What is Global Warming Potential (GWP)?

GWP compares the global warming impact of different gases over a period of time.

8
New cards

What is the GWP of carbon dioxide (CO₂)?

1.

9
New cards

What refrigerant family has high ozone depletion potential?

CFC (Chlorofluorocarbon).

10
New cards

What does HCFC stand for?

Hydrochlorofluorocarbon.

11
New cards

What is the characteristic of HFC refrigerants?

They contain hydrogen, fluorine, and carbon, and have no ozone depletion potential.

12
New cards

What is the main feature of HFO refrigerants?

They have no ODP and very low GWP.

13
New cards

What does ASHRAE stand for?

American Society of Heating, Refrigerating and Air-Conditioning Engineers.

14
New cards

What does an A1 ASHRAE classification indicate?

Lower toxicity and no flammability.

15
New cards

What is the difference between azeotropic and zeotropic refrigerants?

Azeotropic mixtures evaporate and condense at a constant temperature, while zeotropic mixtures have different boiling points.

16
New cards

What is temperature glide?

The temperature difference that occurs during evaporation or condensation of a blended refrigerant.

17
New cards

What is the bubble point used for?

Charging by condenser subcooling.

18
New cards

What is the dew point used for?

Charging by suction or evaporator superheat.

19
New cards

What is fractionation in refrigerants?

Uneven leakage of refrigerant components, changing the composition of the remaining blend.

20
New cards

What is the classification of refrigerants based on pressure at a condensing temperature of 104°F?

Low, medium, high, and very high-pressure refrigerants.

21
New cards

What is an important safety point regarding propane cylinders?

Never use propane cylinders intended for grilling as refrigerant due to potential impurities.

22
New cards

What is the environmental impact of HFC refrigerants?

They do not destroy the ozone layer but can contribute significantly to global warming.

23
New cards

What is the example of a refrigerant with very low GWP?

HFO refrigerants.

24
New cards

What is the importance of R-407C?

It has high temperature glide and can experience fractionation.

25
New cards

What is the pressure classification for low pressure refrigerants?

30 psig or lower

26
New cards

What refrigerants are classified as low pressure?

R-11, R-123, R-245fa, R-1233zd

27
New cards

What is the pressure classification for medium pressure refrigerants?

Above 30 to 155 psig

28
New cards

What refrigerants are classified as medium pressure?

R-12, R-134a, R-600a, R-1234yf

29
New cards

What is the pressure classification for high pressure refrigerants?

Above 155 to 340 psig

30
New cards

What refrigerants are classified as high pressure?

R-22, R-404A, R-407C, R-410A, R-717

31
New cards

What is the pressure classification for very high pressure refrigerants?

Above 340 psig

32
New cards

What refrigerant is classified as very high pressure?

CO₂ (R-744)

33
New cards

What are the two important types of refrigerant oils?

Alkylbenzene and POE (Polyolester)

34
New cards

What is a key characteristic of POE oil?

It is highly hygroscopic, meaning it absorbs moisture from the air.

35
New cards

What does the Montreal Protocol address?

Ozone-depleting substances and their alternatives.

36
New cards

What does Section 608 of the Clean Air Act establish?

Rules and regulations for refrigerant handling in the HVACR industry.

37
New cards

What is required for technicians handling regulated refrigerants?

Section 608 certification.

38
New cards

What is the penalty for knowingly releasing CFC, HCFC, or HFC refrigerants?

It is illegal and can result in fines and loss of certification.

39
New cards

What is the maximum fine per day for violations as of 2017?

$44,539 per day, per violation.

40
New cards

What does the EPA's SNAP program do?

Identifies refrigerant alternatives with lower overall risks to human health and the environment.

41
New cards

What must be done before disposing of an appliance containing refrigerant?

Recover the refrigerant to the required EPA recovery or evacuation level.

42
New cards

What is the difference between recovering, recycling, and reclaiming refrigerants?

Recover = Remove, Recycle = Clean, Reclaim = Restore to virgin specifications.

43
New cards

What are the two basic types of recovery devices?

System-dependent (passive) and self-contained (active).

44
New cards

What increases recovery time for refrigerants?

Low ambient temperatures, long hoses, and long small-diameter hoses.

45
New cards

What is the purpose of using dry nitrogen in leak detection?

To pressurize a newly installed system for leak testing.

46
New cards

What should be done after repairing a leak?

Install a new filter-drier.

47
New cards

What is dehydration in the context of refrigerants?

The process of removing moisture from refrigerant systems.

48
New cards

What is a critical safety rule after transferring liquid refrigerant?

Prevent liquid from becoming trapped in a service hose between closed service valves.

49
New cards

Why should separate recovery cylinders be used?

To avoid mixing refrigerants, which may be impossible to reclaim.

50
New cards

What must reclaimed refrigerant meet before it can be resold?

AHRI Standard 700.

51
New cards

What is dehydration in refrigeration?

Removing water and water vapor from a refrigeration system.

52
New cards

Why is dehydration important?

Moisture can cause hydrochloric acid and hydrofluoric acid to form in an operating refrigeration system.

53
New cards

What is the most important evacuation number for dehydration?

500 microns or lower.

54
New cards

What tool measures the vacuum level during evacuation?

A micron gauge.

55
New cards

What factors affect evacuation speed?

Size of the equipment, ambient temperature, amount of moisture, size of the vacuum pump, and size of the vacuum hoses.

56
New cards

What is a proper vacuum setup for evacuation?

Use hoses equal to or larger than the pump intake, keep connections short, use large diameter hoses, and place the vacuum gauge far from the pump.

57
New cards

What indicates that a refrigeration system has a leak?

If the system won't hold a vacuum.

58
New cards

How can dehydration time be decreased?

Heating the refrigeration system or tapping the compressor with a rubber mallet.

59
New cards

What does it mean if the micron gauge reaches and holds 500 microns or lower?

Dehydration is complete.

60
New cards

What should you never do with refrigerant during evacuation?

Never evacuate refrigerant directly into the atmosphere.

61
New cards

What personal protective equipment should be worn when handling refrigerants?

Safety glasses, protective gloves, and equipment-specific protection.

62
New cards

What should be done when pressurizing a system with nitrogen?

Use a pressure regulator and install a relief valve downstream.

63
New cards

Why should oxygen or compressed air never be used to pressurize a refrigeration system?

It can cause an explosion when mixed with certain refrigerants or compressor oil.

64
New cards

What can high temperatures do to refrigerants?

They can decompose refrigerants and create dangerous acids.

65
New cards

What acids can be formed from chlorine and fluorine in refrigerants?

Chlorine forms hydrochloric acid, and fluorine forms hydrofluoric acid.

66
New cards

What is the danger of flammable refrigerants?

An explosion can occur when concentrations are between the Lower and Upper Flammability Limits with an ignition source.

67
New cards

What is required for refrigerant cylinders carrying flammable refrigerants?

They must have red markings extending at least one inch from service connection points.

68
New cards

What are the possible effects of inhaling high concentrations of refrigerant vapor?

Heart irregularities, unconsciousness, oxygen deprivation, and death by asphyxiation.

69
New cards

What should be done in case of a large refrigerant release?

Immediately vacate and ventilate the area; properly equipped personnel should use SCBA to enter.

70
New cards

What are the requirements for recovery cylinders?

They must have a yellow top, gray body, be free of rust, and properly labeled.

71
New cards

What is the maximum filling capacity for recovery cylinders?

80% by weight.

72
New cards

How can you control the fill level of a recovery cylinder?

Using a mechanical float device, electronic shut-off device, or measuring gross cylinder weight.

73
New cards

How often must reusable high-pressure refrigerant containers be hydrostatically tested?

Every five years.

74
New cards

What should be done with disposable refrigerant cylinders?

Recover remaining vapor and reduce pressure to 0 psig before scrapping.

75
New cards

What should never be done to a refrigerant cylinder?

Never heat it with an open flame.

76
New cards

What is required when transporting used refrigerants?

Attach the appropriate DOT classification tag and label, and use portable refillable tanks that meet DOT standards.

77
New cards

Why is it important to label refrigerant cylinders?

To prevent accidental mixing, allow recyclers to identify contents, and help track the quantity of refrigerant recovered.

78
New cards

What is the ozone molecule's chemical formula?

O₃.

79
New cards

What is the Global Warming Potential (GWP) of CO₂?

1.

80
New cards

What is the chlorine lifetime in the atmosphere?

120 years.

81
New cards

How many ozone molecules can be destroyed by one chlorine molecule?

Up to 100,000.

82
New cards

What is the standard evacuation level for refrigeration systems?

500 microns or lower.