Power Distribution

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/37

flashcard set

Earn XP

Description and Tags

Comprehensive vocabulary flashcards covering power distribution systems, 33/11 kV substations, transformer construction and testing, switchgear, protective coordination, and installation standards across Irish and Saudi power-sector specifications.

38 Terms

1
New cards

Unified Specific Creepage Distance (USCD)

The total creepage distance of an electrical insulator divided by the highest continuous system phase-to-phase operating voltage (Lcreep≥USCD×UmL_{\text{creep}} \ge \text{USCD} \times U_m), specified by SEC at ≥31 mm/kV\ge 31\,\text{mm/kV} (Class d) for heavy to very heavy desert-coastal pollution and sabkha environments.

2
New cards

Arcing Horns

Paired sacrificial metal electrodes installed at the line and earthed ends of an insulator string forming a calibrated air gap (U50%gap<UwinsulatorU_{50\%}^{\text{gap}} < U_w^{\text{insulator}}) with an air breakdown gradient of approximately 30 kV/cm30\,\text{kV/cm} at STP, designed to divert power-frequency flashover arcs away from the porcelain body.

3
New cards

Metal-Oxide Surge Arrester

A gapless overvoltage protection device constructed from non-linear zinc-oxide (ZnO) varistor blocks that maintains minimal leakage current at continuous operating voltage (Uc≥Us/3U_c \ge U_s / \sqrt{3}) and conducts surge currents to earth, clamping voltage to provide a protective margin PM=Uw−UresUres×100%≥20%PM = \frac{U_w - U_{\text{res}}}{U_{\text{res}}} \times 100\% \ge 20\%.

4
New cards
<p>Metal-Oxide Arrester V-I Characteristic</p>

Metal-Oxide Arrester V-I Characteristic

The non-linear conduction curve of a ZnO surge arrester showing high resistance drawing microampere currents below rated voltage (UrU_r), transitioning sharply at overvoltages to conduct kiloamperes while clamping the voltage to a defined residual level (UresU_{\text{res}}) at a nominal 10 kA10\,\text{kA} (8/20 μs8/20\,\mu\text{s}) discharge.

5
New cards

Gang-Operated Air-Break (GOAB) Isolator

A 3-pole mechanically linked disconnector operated by a single common handle that opens all three phases simultaneously to provide a visible, lockable air gap for maintenance, rated exclusively for off-load operation (I≈0I \approx 0) without arc-extinguishing capability.

6
New cards

Drop-Out Fuse (DDLO)

A high-voltage expulsion fuse cutout where the fuse tube unlatches and drops down under gravity upon element rupture, extinguishing short-circuit faults with de-ionising liner gases while providing a visible air disconnection, typically rated at approximately 1.5×IFL1.5 \times I_{\text{FL}}.

7
New cards

Dyn11 Vector Group

A three-phase transformer connection featuring a delta-connected high-voltage primary (D), a star-connected low-voltage secondary with an earthed neutral (yn), and a phase displacement of 30∘30^\circ where the low-voltage line voltage leads the high-voltage line voltage by 30∘30^\circ (11 o'clock).

8
New cards

Buchholz Relay

A gas- and oil-actuated protective relay installed in an inclined pipe (1.5∘–3∘1.5^\circ\text{--}3^\circ) between the transformer tank and conservator that activates an upper-float alarm upon slow gas accumulation from incipient faults and triggers a lower-flap trip upon rapid oil surges (voil≥0.7–1.5 m/sv_{\text{oil}} \ge 0.7\text{--}1.5\,\text{m/s}).

9
New cards

Pressure Relief Device (PRD)

A spring-loaded safety valve mounted directly on a transformer tank that automatically lifts to release sudden internal overpressures when Ptank>PsetP_{\text{tank}} > P_{\text{set}} (typically ≈0.7 bar\approx 0.7\,\text{bar}) and self-reseals to prevent tank rupture while signaling an alarm or trip contact.

10
New cards

Silica-Gel Breather

A cylindrical desiccant filter through which a transformer conservator breathes air (Vbreath≈V0βΔTdiurnalV_{\text{breath}} \approx V_0 \beta \Delta T_{\text{diurnal}}), utilizing an oil seal cup to capture dust and cobalt-impregnated silica gel that transitions in colour from blue to pink to indicate moisture saturation.

11
New cards
<p>Current Transformer Knee Point ($$V_k$$)</p>

Current Transformer Knee Point (VkV_k)

The point on a CT magnetisation (excitation) curve where a 10%10\% increase in secondary induced EMF (VsV_s) causes a 50%50\% increase in exciting current (IeI_e), marking the threshold between accurate linear transformation and iron core saturation.

12
New cards

Load Break Switch (LBS)

An on-load mechanical switching device rated to make and break normal system load current (ILBS≥IloadI_{\text{LBS}} \ge I_{\text{load}}) within an extinguishing chamber (SF6\text{SF}_6, vacuum, or air), commonly paired with series HRC fuses (LBS-F) to interrupt short-circuit fault currents.

13
New cards

Ring Main Distribution System

A medium-voltage network distribution arrangement where feeders form closed loops supplying each load centre from two independent directions, enabling selective disconnection of faulted cable segments without dropping supply to other substations.

14
New cards

Neozed Fuse

A compact European cartridge fuse (standard VDE 0365) manufactured in sizes D01 (up to 16 A16\,\text{A}), D02 (up to 63 A63\,\text{A}), and D03 (up to 100 A100\,\text{A}), featuring colour-coded adapter gauge rings and calibrated tip diameters to prevent the installation of an over-rated fuse link.

15
New cards

M-Effect (Metallurgical Effect)

An arc-control mechanism in HBC fuses where a tin pellet located in a silver or copper element trough melts at 230∘C230^\circ\text{C} and alloys with silver (melting point 860∘C860^\circ\text{C}), causing the composite eutectic alloy to fuse at 230∘C230^\circ\text{C} to clear sustained overloads at 1.5×In1.5 \times I_n without excessive temperature rise.

16
New cards

Pre-Arcing Time

The duration between the initiation of an overcurrent sufficiently large to cause protective element operation and the exact instant an electric arc is struck across the melting fuse element or opening breaker contacts.

17
New cards

Energy Let-Through (I2tI^2 t)

The total thermal and electrodynamic stress energy passed into an electrical circuit from the instant of fault initiation until total arc extinction, expressed in amperes squared seconds (A2s\text{A}^2\text{s}) or Joules.

18
New cards

Protective Device Discrimination

The coordinated operation of series protective devices ensuring only the device closest to the fault opens, achieved when the total operating energy let-through (I2tI^2 t) of the downstream device is strictly less than the pre-arcing energy (I2tI^2 t) of the upstream device.

19
New cards
<p>Miniature Circuit Breaker (MCB)</p>

Miniature Circuit Breaker (MCB)

An enclosed mechanical switching device providing bimetal thermal overload protection, electromagnetic solenoid short-circuit tripping, and multi-plate arc-splitting chutes to extinguish arcs within 3.5–5 ms3.5\text{--}5\,\text{ms}.

20
New cards

MCB Tripping Characteristics (Types B, C, D)

Standard instantaneous magnetic operating thresholds defined under BS EN 60898: Type B trips at 3–5×In3\text{--}5 \times I_n for resistive and domestic circuits; Type C trips at 5–10×In5\text{--}10 \times I_n for inductive loads and discharge lighting; Type D trips at 10–20×In10\text{--}20 \times I_n (or up to 50×In50 \times I_n) for high inrush currents such as transformers and welders.

21
New cards

Magnetic-Hydraulic Trip Mechanism

A circuit breaker tripping unit comprising an iron slug damped by silicone fluid inside a non-magnetic tube surrounded by an operating coil, providing an inverse-time response for overloads up to seven times rated current (7×In7 \times I_n) and instantaneous tripping above that threshold regardless of slug position.

22
New cards
<p>Explosion Pot</p>

Explosion Pot

A reinforced arcing chamber located inside an oil circuit breaker (OCB) that utilizes the localized pressure of the decomposing oil-gas bubble to force fresh insulating oil across the arc path through side vents and baffles, rapidly cooling and de-ionising the arc.

23
New cards
<p>Vacuum Circuit Breaker (VCB)</p>

Vacuum Circuit Breaker (VCB)

A medium-voltage circuit breaker where contacts part inside a sealed hard-vacuum bottle linked via flexible metal bellows, interrupting fault currents at the first natural current zero across a contact travel of only approximately 10 mm10\,\text{mm} at 11 kV11\,\text{kV}.

24
New cards
<p>RCD Class Types (IEC 60755)</p>

RCD Class Types (IEC 60755)

Residual current device operating classifications: Type AC detects sinusoidal alternating residual currents; Type A detects both sinusoidal AC and pulsating DC residual currents; Type B detects sinusoidal AC, pulsating DC, and smooth direct currents.

25
New cards
<p>Bar Primary Current Transformer</p>

Bar Primary Current Transformer

A current transformer construction where a single through-busbar or heavy conductor serves as a single primary turn (Np=1N_p = 1) passing through the central aperture of a toroidal core carrying the multi-turn secondary winding.

26
New cards

Oil Temperature Indicator (OTI)

A transformer monitoring instrument featuring a sensing bulb filled with volatile liquid immersed in the top oil, communicating vapour pressure through a capillary tube to a Bourdon dial thermometer fitted with mercury tilt contacts (S1S_1 for alarm and S2S_2 for trip).

27
New cards

Crackle Test

A qualitative workshop and field verification procedure for transformer insulating oil where a sample in a test tube is heated over a naked flame; an audible crackling or spitting sound reveals the presence of free or dissolved water.

28
New cards

Maximum Import Capacity (MIC)

The contracted apparent power ceiling in kilovolt-amperes (kVA\text{kVA}) allocated to an electrical consumer by the network operator, forming the basis for daily capacity charges and excess capacity penalties if actual demand exceeds the agreed limit.

29
New cards

Winter Demand Reduction Incentive (WDRI)

An electricity tariff scheme offered to maximum demand customers during November through February that restricts maximum demand billing measurement exclusively to peak system hours (17:00 to 19:00, Monday through Friday) to encourage industrial demand reduction.

30
New cards

Wattless Energy

The reactive energy component measured in reactive kilovolt-ampere-hours (kVARh\text{kVARh}) resulting from inductive magnetising currents; commercial tariffs penalize wattless energy recorded in excess of one-third (1/31/3) of total active kilowatt-hours (kWh\text{kWh}).

31
New cards

Static Power Factor Correction

The practice of connecting power factor correction capacitors directly across the terminals or starter of individual motors, sized below the motor's magnetising current and strictly forbidden on the output side of inverters or variable speed drives.

32
New cards

Bulk Power Factor Correction

A centralized bank of power factor capacitors installed at the main low-voltage switchboard, controlled by an automated microprocessor relay that measures line power factor and switches capacitor steps in or out to maintain the system between 0.920.92 and 0.950.95 lagging.

33
New cards

Adiabatic Equation for Protective Conductors

The thermodynamic equation S=I2tkS = \frac{\sqrt{I^2 t}}{k} used to verify the minimum cross-sectional area of a protective conductor under fault disconnection times up to 5 s5\,\text{s}, where k=51k = 51 for steel wire armour on 70∘C70^\circ\text{C} PVC-insulated cables.

34
New cards

Switchgear Clearances (ETCI Code of Practice)

Physical layout regulations requiring at least 1.2 m1.2\,\text{m} of unobstructed clearance in front of a low-voltage switchgear assembly and at least 1.0 m1.0\,\text{m} clearance with unimpeded egress at both ends behind the panel when rear access is required.

35
New cards

RL Circuit Time Constant (τ\tau)

The time constant τ=LR\tau = \frac{L}{R} (in seconds) defining current growth to 63.2%63.2\% (0.632Imax0.632 I_{\text{max}}) or decay to 36.8%36.8\% (0.368Imax0.368 I_{\text{max}}) in an inductive circuit, with the complete transient state considered accomplished after five time constants (5τ5\tau).

36
New cards

Open-Circuit Test (Transformer)

A diagnostic test performed by leaving the transformer secondary open-circuited while supplying rated voltage and frequency to the primary winding through a variac, with the primary wattmeter reading directly representing the constant core iron losses (hysteresis and eddy currents).

37
New cards

Short-Circuit Test (Transformer)

A diagnostic test where the transformer low-voltage winding is short-circuited and a reduced voltage (5–10%5\text{--}10\% of rated) is applied to the high-voltage winding to circulate rated full-load current, with the wattmeter reading representing total full-load winding copper losses (I2RI^2 R).

38
New cards

Transformer Voltage Regulation

The percentage variation in terminal output voltage from no-load to full-load conditions expressed as Vno-load−Vfull-loadVno-load×100%\frac{V_{\text{no-load}} - V_{\text{full-load}}}{V_{\text{no-load}}} \times 100\%, caused by winding impedance voltage drops and degrading further under lower lagging power factors.