Stationary Operator Test

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/99

encourage image

There's no tags or description

Looks like no tags are added yet.

100 Terms

1
New cards

permit one strainer to be cleaned while the other is in service

In a fuel oil system, the purpose of duplex strainers is to…

2
New cards

500

According to the ASME code, a boiler that has more than ___ square feet of heating surface must have two or more safety valves

3
New cards

qualified repair technician

According to the ASME code, any repairs done on a boiler safety valve must be done by a…

4
New cards

heat

Burning fuel produces a chemical reaction that releases…

5
New cards

soot blowers

To ensure good heat transfer in a watertube boiler, the outside of the tubes are kept clean by ____ ______

6
New cards

gate

The thickness of the fuel bed on a chain grate stroker is regulated by a coal ____

7
New cards

heat being carried with the gases of combustion to the atmosphere

A large heat loss in a boiler is caused by…

8
New cards

scale formation on the tubes

A direct cause of overheating of the boiler tubes is…

9
New cards

hydrostatic

The main purpose of conducting a ___________ test is to verify the strength of the boiler shell and any parts under pressure

10
New cards

globe

This type of valve actually offers more resistance to flow than a gate valve

11
New cards

steam strainer

A steam trap usually has a _____ ________ installed on the inlet line

12
New cards

bottom blowdown

The ______ ________ valves are used to remove sludge and sediment from the boiler, while safety valves or pressure regulators are used to lower or control boiler steam pressure

13
New cards

Selective Catalytic Reduction (SCR)

is an emissions control method in which ammonia gas is introduced on a catalyst located in a module that is installed in the boiler exhaust stack

14
New cards

pressure buildup

A vent line on a fuel oil tank prevents ________ _______ when filling the tank with fuel oil and also prevents a vacuum from developing when fuel oil is removed

15
New cards

keeping the superheater drain valve open until the boiler is cut in on-line

Boilers equipped with a superheater must be protected during warmup by…

16
New cards

fuel supply air supply draft

The primary function of a combustion control system is to regulate the ____ ______, ___ ______, and _____

17
New cards

minutes

A steaming boiler can have the water in the gauge glass go from half-full to empty in a matter of _______ if water is not added to the boiler

18
New cards

for closer contact between the coal and oxygen for complete combustion

Pulverizing coal allows…

19
New cards

oxygen pitting in the boiler

Water temperatures that are too low in an open feedwater heater will cause…

20
New cards

than the safety valve on the steam drum

The safety valve on the superheater header should be set to a lower popping pressure…

21
New cards

Dry

___ layup is used when the boiler is expected to be out of service for an extended period of time

22
New cards

scale oxygen pitting caustic embrittlement

Boiler water is treated to prevent _____, ______ _______, and _______ _____________

23
New cards

without modulating the flame to match steam load

ON/OFF control is used to start and stop a burner…

24
New cards

do not

In a closed feedwater heater, steam and water do/do not come in contact with each other

25
New cards

establishes steam flow through

The superheater drain ___________ _____ ____ _______ the superheater during startup and shut down

26
New cards

package

A _______ boiler comes completely assembled with its own feedwater system, fuel system, combustion control, and draft system

27
New cards

steam velocity

Impulse steam turbines use _____ ________ as a force acting in a forward direction on a blade or a bucket mounted on a wheel

28
New cards

two main steam stop valves

The ASME code states that high-pressure boilers in battery (two or more boilers connected to a common heater) and equipped with manhole openings must have…

29
New cards

balanced

A ________ draft system is used to overcome air and gas-flow resistance

30
New cards

oxygen

The three ingredients needed to start a fire are fuel, heat, and ______

31
New cards

accumulation

An ____________ test is used to test the relieving capacity of a safety valve

32
New cards

removes moisture from the steam

A dry pipe…

33
New cards

superheated

A desuperheater is used with ___________ steam, not saturated steam

34
New cards

excess

Air supplied to the burner that is more than the theoretical amount needed to burn a fuel is ______ air

35
New cards

power driven fans

Mechanical draft is produced by _____-______ ____

36
New cards

opening

In a pop-type safety valve, the huddling chamber assists in _______ the valve

37
New cards

primary

Air used to atomize fuel is _______ air

38
New cards

extra hazard

An _____-______ area is a location where class A and class B flammables exceed those expected in ordinary hazard areas

39
New cards

ASME

Boiler tubes are manufactured using materials that meet ____ specifications

40
New cards

steam trap

A _____ ____ automatically removes air and condensate from the steam lines

41
New cards

seven

Neutral on the ph scale is #

42
New cards

Carbon monoxide

______ ________ is produced by incomplete combustion due to poor burner design or firing conditions

43
New cards

100000

One therm of natural gas is equal to ___,___ BTU

44
New cards

does not

Blowing down the water column and gauge glass too frequently does/does not produce a false water level reading, it can cause faster wear and tear on the components

45
New cards

deaerated

Chemical treatment of boiler water is still required even if the water has been _________

46
New cards

steam-driven or water-driven turbine

Scale buildup in the tubes of a watertube boiler can be removed by a…

47
New cards

steam flow feedwater flow water level

In a three-element feedwater regulating system, _____ ____, _________ ____, and _____ _____ are measured

48
New cards

vents

Boiler blowdown tanks require _____ to release flash steam safely into the atmosphere

49
New cards

closed locked tagged

During boiler inspection, the main steam stop valves are ______, ______, and ______

50
New cards

21

Air contains approximately __% oxygen

51
New cards

steam pressure

Single-point positioning uses the _____ ________ as controller input and has only one output

52
New cards

brain

A programmer is the safety and sequencing “_____” of a boiler’s burner management system

53
New cards

total force

A safety valve opens when the _____ _____ exerted by the steam exceeds that of the spring

54
New cards

Steam traps

_____ _____ are designed to collect condensate from the steam system so that it can be returned to the boiler through the condensate return tank

55
New cards

gaseous

Dry saturated steam is in a _______ state

56
New cards

water

Priming is dangerous and can lead to _____ hammer

57
New cards

combustion control system

A __________ _______ ______ regulates fuel supply, air supply, air-fuel ratio, and draft in a boiler in order to deliver the required amount of steam to a load

58
New cards

15

A high-pressure steam boiler operates at a steam pressure over __ PSI

59
New cards

a loss of air for combustion and incomplete combustion

If air supplied for combustion mixes with the gases of combustion, it could lead to…

60
New cards

diameter of the steam piston, diameter of the water piston, and the length of the pump stroke

The sequence of three numbers found on the nameplate mounted on a reciprocating feedwater pump refers to the…

61
New cards

condensing

A __________ steam turbine allows condensate to be reclaimed for reuse

62
New cards

through the vent

From teh deaerator, oxygen and other non-condensible gases are separated from the feedwater and directed to the atmosphere…

63
New cards

condensation on the line

Water hammer in steam lines is caused by…

64
New cards

lower pressure than

A superheater header safety valve is set to pop at a _____ ________ ____ the steam drum safety valves

65
New cards

low water fuel cutoff

A ___-_____ ____ ______ protects against loss of boiler water and potential catastrophic explosion

66
New cards

saturated

Superheated steam can be produced at any pressure, including low pressures and atmospheric pressure, by adding more heat to _________ steam once it is no longer in contact with water

67
New cards

both the suction and discharge sides of the fuel oil pump

Duplex strainers are found on…

68
New cards

pyrometer

A _________ is used to measure furnace temperature

69
New cards

the formation of soot and smoke

Gases of combustion that cool on contact with the boiler heater surface before combustion is completed can cause…

70
New cards

opened

If a safety valve leaks after testing, the valve should be ______ again using the test lever

71
New cards

6

#_ fuel oil has the highest BTU content per gallon

72
New cards

Thermal

_______ efficiency is the ration of the heat absorbed by the boiler (output) to the heat available in the fuel (input)

73
New cards

NOWL (normal operating water level)

When beginning a bottom blowdown, it is important to maintain the water at the ____

74
New cards

economizers and air heaters

Boilers can be equipped with ___________ ___ ___ _______ to reduce the heat loss from the gases of combustion going to the chimney

75
New cards

one-to-one and a half times the safety valve setting

When performing a hydrostatic test on a boiler, the pressure is…

76
New cards

above the feedwater pumps

The deaerator is located

77
New cards

surface blowdowns

A safe maximum water concentration of dissolved solids is maintained by

78
New cards

alcohol

The bellows of a thermostatic steam trap is usually filled with a(n) _______ and water solution to increase the sensitivity of the trap

79
New cards

F

T/F: The duty rating of a boiler is the ratio of the heat absorbed by the boiler (output) to the heat available in the fuel (input).

80
New cards

T

T/F: Purging a furnace before firing can prevent a furnace explosion

81
New cards

T

T/F: When conducting a hydrostatic test, all safety valves are either gagged or blanked, and the water pressure is increased to 1-1/2 times the safety valve setting

82
New cards

T

T/F: Steam boilers that are out of service can be laid up wet or dry

83
New cards

try cocks

The ___ _____ is/are a secondary means of determining boiler water level

84
New cards

transmitter

A measuring instrument can use a ___________ to send a signal to a controller.

85
New cards

cold lime-soda, hot lime-soda, or ion-exchange softener

External feedwater treatment conditions the boiler water before it enters the boiler using a(n)

86
New cards

Primary

_______ air is used to atomize fuel oil or convey pulverized coal and control the rate of combustion, thus determining the amount of fuel that can be burned

87
New cards

try lever

A ___ _____ test is used to determine if a safety valve and discharge piping are capable of discharging steam.

88
New cards

thoroughly clean the fire and water sides

Before laying up a boiler, the boiler operator must

89
New cards

soot blower

Soot on the outside of boiler tubes is removed by a ____ ______

90
New cards

closed feedwaterheater

Plant efficiency is increased when a ______ _______________ uses steam that is bled or extracted from a steam turbine

91
New cards

a hydrostatic test

After a boiler has had major repair work done that could affect the boiler internals or has developed a low-water condition, it should be subjected to

92
New cards

F

T/F: A boiler feedwater pump cannot become steambound

93
New cards

deaerator

A _________ is a feedwater heater that separates oxygen and other gases from the steam before releasing the gases into the atmosphere

94
New cards

highest part of the steam

A boiler steam pressure gauge should be connected to the _____ side of the boiler

95
New cards

T

T/F: Standard atmospheric pressure will support a column of mercury approximately 30" high

96
New cards

os&y gate

A main steam stop valve should be a(n) ____ ____ valve

97
New cards

T

T/F: An open feedwater heater vents gases to the atmosphere

98
New cards

T

T/F: An energy audit of a facility identifies how energy is used in a facility, and then recommends ways to improve energy efficiency and reduce energy costs

99
New cards

manual reset

In a low-pressure gas system, the ______ _____ valve is an electric valve that cannot be opened until the gas pilot is lit

100
New cards

T

T/F: A low-water fuel cutoff control should be tested by blowing down the float chamber at least once a shift