1/99
Looks like no tags are added yet.
permit one strainer to be cleaned while the other is in service
In a fuel oil system, the purpose of duplex strainers is to…
500
According to the ASME code, a boiler that has more than ___ square feet of heating surface must have two or more safety valves
qualified repair technician
According to the ASME code, any repairs done on a boiler safety valve must be done by a…
heat
Burning fuel produces a chemical reaction that releases…
soot blowers
To ensure good heat transfer in a watertube boiler, the outside of the tubes are kept clean by ____ ______
gate
The thickness of the fuel bed on a chain grate stroker is regulated by a coal ____
heat being carried with the gases of combustion to the atmosphere
A large heat loss in a boiler is caused by…
scale formation on the tubes
A direct cause of overheating of the boiler tubes is…
hydrostatic
The main purpose of conducting a ___________ test is to verify the strength of the boiler shell and any parts under pressure
globe
This type of valve actually offers more resistance to flow than a gate valve
steam strainer
A steam trap usually has a _____ ________ installed on the inlet line
bottom blowdown
The ______ ________ valves are used to remove sludge and sediment from the boiler, while safety valves or pressure regulators are used to lower or control boiler steam pressure
Selective Catalytic Reduction (SCR)
is an emissions control method in which ammonia gas is introduced on a catalyst located in a module that is installed in the boiler exhaust stack
pressure buildup
A vent line on a fuel oil tank prevents ________ _______ when filling the tank with fuel oil and also prevents a vacuum from developing when fuel oil is removed
keeping the superheater drain valve open until the boiler is cut in on-line
Boilers equipped with a superheater must be protected during warmup by…
fuel supply air supply draft
The primary function of a combustion control system is to regulate the ____ ______, ___ ______, and _____
minutes
A steaming boiler can have the water in the gauge glass go from half-full to empty in a matter of _______ if water is not added to the boiler
for closer contact between the coal and oxygen for complete combustion
Pulverizing coal allows…
oxygen pitting in the boiler
Water temperatures that are too low in an open feedwater heater will cause…
than the safety valve on the steam drum
The safety valve on the superheater header should be set to a lower popping pressure…
Dry
___ layup is used when the boiler is expected to be out of service for an extended period of time
scale oxygen pitting caustic embrittlement
Boiler water is treated to prevent _____, ______ _______, and _______ _____________
without modulating the flame to match steam load
ON/OFF control is used to start and stop a burner…
do not
In a closed feedwater heater, steam and water do/do not come in contact with each other
establishes steam flow through
The superheater drain ___________ _____ ____ _______ the superheater during startup and shut down
package
A _______ boiler comes completely assembled with its own feedwater system, fuel system, combustion control, and draft system
steam velocity
Impulse steam turbines use _____ ________ as a force acting in a forward direction on a blade or a bucket mounted on a wheel
two main steam stop valves
The ASME code states that high-pressure boilers in battery (two or more boilers connected to a common heater) and equipped with manhole openings must have…
balanced
A ________ draft system is used to overcome air and gas-flow resistance
oxygen
The three ingredients needed to start a fire are fuel, heat, and ______
accumulation
An ____________ test is used to test the relieving capacity of a safety valve
removes moisture from the steam
A dry pipe…
superheated
A desuperheater is used with ___________ steam, not saturated steam
excess
Air supplied to the burner that is more than the theoretical amount needed to burn a fuel is ______ air
power driven fans
Mechanical draft is produced by _____-______ ____
opening
In a pop-type safety valve, the huddling chamber assists in _______ the valve
primary
Air used to atomize fuel is _______ air
extra hazard
An _____-______ area is a location where class A and class B flammables exceed those expected in ordinary hazard areas
ASME
Boiler tubes are manufactured using materials that meet ____ specifications
steam trap
A _____ ____ automatically removes air and condensate from the steam lines
seven
Neutral on the ph scale is #
Carbon monoxide
______ ________ is produced by incomplete combustion due to poor burner design or firing conditions
100000
One therm of natural gas is equal to ___,___ BTU
does not
Blowing down the water column and gauge glass too frequently does/does not produce a false water level reading, it can cause faster wear and tear on the components
deaerated
Chemical treatment of boiler water is still required even if the water has been _________
steam-driven or water-driven turbine
Scale buildup in the tubes of a watertube boiler can be removed by a…
steam flow feedwater flow water level
In a three-element feedwater regulating system, _____ ____, _________ ____, and _____ _____ are measured
vents
Boiler blowdown tanks require _____ to release flash steam safely into the atmosphere
closed locked tagged
During boiler inspection, the main steam stop valves are ______, ______, and ______
21
Air contains approximately __% oxygen
steam pressure
Single-point positioning uses the _____ ________ as controller input and has only one output
brain
A programmer is the safety and sequencing “_____” of a boiler’s burner management system
total force
A safety valve opens when the _____ _____ exerted by the steam exceeds that of the spring
Steam traps
_____ _____ are designed to collect condensate from the steam system so that it can be returned to the boiler through the condensate return tank
gaseous
Dry saturated steam is in a _______ state
water
Priming is dangerous and can lead to _____ hammer
combustion control system
A __________ _______ ______ regulates fuel supply, air supply, air-fuel ratio, and draft in a boiler in order to deliver the required amount of steam to a load
15
A high-pressure steam boiler operates at a steam pressure over __ PSI
a loss of air for combustion and incomplete combustion
If air supplied for combustion mixes with the gases of combustion, it could lead to…
diameter of the steam piston, diameter of the water piston, and the length of the pump stroke
The sequence of three numbers found on the nameplate mounted on a reciprocating feedwater pump refers to the…
condensing
A __________ steam turbine allows condensate to be reclaimed for reuse
through the vent
From teh deaerator, oxygen and other non-condensible gases are separated from the feedwater and directed to the atmosphere…
condensation on the line
Water hammer in steam lines is caused by…
lower pressure than
A superheater header safety valve is set to pop at a _____ ________ ____ the steam drum safety valves
low water fuel cutoff
A ___-_____ ____ ______ protects against loss of boiler water and potential catastrophic explosion
saturated
Superheated steam can be produced at any pressure, including low pressures and atmospheric pressure, by adding more heat to _________ steam once it is no longer in contact with water
both the suction and discharge sides of the fuel oil pump
Duplex strainers are found on…
pyrometer
A _________ is used to measure furnace temperature
the formation of soot and smoke
Gases of combustion that cool on contact with the boiler heater surface before combustion is completed can cause…
opened
If a safety valve leaks after testing, the valve should be ______ again using the test lever
6
#_ fuel oil has the highest BTU content per gallon
Thermal
_______ efficiency is the ration of the heat absorbed by the boiler (output) to the heat available in the fuel (input)
NOWL (normal operating water level)
When beginning a bottom blowdown, it is important to maintain the water at the ____
economizers and air heaters
Boilers can be equipped with ___________ ___ ___ _______ to reduce the heat loss from the gases of combustion going to the chimney
one-to-one and a half times the safety valve setting
When performing a hydrostatic test on a boiler, the pressure is…
above the feedwater pumps
The deaerator is located
surface blowdowns
A safe maximum water concentration of dissolved solids is maintained by
alcohol
The bellows of a thermostatic steam trap is usually filled with a(n) _______ and water solution to increase the sensitivity of the trap
F
T/F: The duty rating of a boiler is the ratio of the heat absorbed by the boiler (output) to the heat available in the fuel (input).
T
T/F: Purging a furnace before firing can prevent a furnace explosion
T
T/F: When conducting a hydrostatic test, all safety valves are either gagged or blanked, and the water pressure is increased to 1-1/2 times the safety valve setting
T
T/F: Steam boilers that are out of service can be laid up wet or dry
try cocks
The ___ _____ is/are a secondary means of determining boiler water level
transmitter
A measuring instrument can use a ___________ to send a signal to a controller.
cold lime-soda, hot lime-soda, or ion-exchange softener
External feedwater treatment conditions the boiler water before it enters the boiler using a(n)
Primary
_______ air is used to atomize fuel oil or convey pulverized coal and control the rate of combustion, thus determining the amount of fuel that can be burned
try lever
A ___ _____ test is used to determine if a safety valve and discharge piping are capable of discharging steam.
thoroughly clean the fire and water sides
Before laying up a boiler, the boiler operator must
soot blower
Soot on the outside of boiler tubes is removed by a ____ ______
closed feedwaterheater
Plant efficiency is increased when a ______ _______________ uses steam that is bled or extracted from a steam turbine
a hydrostatic test
After a boiler has had major repair work done that could affect the boiler internals or has developed a low-water condition, it should be subjected to
F
T/F: A boiler feedwater pump cannot become steambound
deaerator
A _________ is a feedwater heater that separates oxygen and other gases from the steam before releasing the gases into the atmosphere
highest part of the steam
A boiler steam pressure gauge should be connected to the _____ side of the boiler
T
T/F: Standard atmospheric pressure will support a column of mercury approximately 30" high
os&y gate
A main steam stop valve should be a(n) ____ ____ valve
T
T/F: An open feedwater heater vents gases to the atmosphere
T
T/F: An energy audit of a facility identifies how energy is used in a facility, and then recommends ways to improve energy efficiency and reduce energy costs
manual reset
In a low-pressure gas system, the ______ _____ valve is an electric valve that cannot be opened until the gas pilot is lit
T
T/F: A low-water fuel cutoff control should be tested by blowing down the float chamber at least once a shift