Earthing, Bonding, and Testing

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/40

flashcard set

Earn XP

Description and Tags

Comprehensive practice flashcards defining essential vocabulary and technical concepts in earthing, bonding, protective devices, and testing according to Irish and European electrical installation standards.

41 Terms

1
New cards

System Earthing

The intentional connection of a point in the electrical power system, usually the neutral point of a generator or transformer, to earth through a conductor or earthing impedance to provide a reference potential, limit overvoltages, and ensure power system stability.

2
New cards

Equipment Earthing

The intentional connection of all exposed, non-current-carrying conductive metal parts of electrical equipment (such as frames, enclosures, and cable trays) to earth through a low-impedance conductor to ensure safe passage of fault current and protect people from electric shock during an insulation failure.

3
New cards

Main Earthing Terminal (MET)

A terminal or brass bar provided in an installation for connecting together protective conductors, main equipotential bonding conductors, earthing conductors, and functional earthing conductors to the means of earthing.

4
New cards

Earthing Conductor

A protective conductor having green/yellow insulation that connects the Main Earthing Terminal (MET) directly to the earth electrode.

5
New cards

Main Protective Conductor

The neutralizing conductor in a TN-C-S installation that connects the Main Earthing Terminal (MET) to the incoming supply neutral (PEN conductor), typically located within the meter cabinet.

6
New cards

Circuit Protective Conductor (CPC)

A protective conductor connecting the exposed conductive parts of equipment to the Main Earthing Terminal to provide a low-impedance return path for earth fault current.

7
New cards

PEN Conductor

An earthed electrical conductor combining the dual functions of a protective conductor (PE\text{PE}) and a neutral conductor (N\text{N}).

8
New cards

Earth Electrode

A conductive part or group of conductive parts placed in intimate contact with the ground to provide an effective electrical connection with the general mass of earth.

9
New cards

Domestic Earth Electrode Standard

A hot-dip galvanized-steel rod or pipe with a diameter of at least 16 mm16\,\text{mm}, driven vertically into the ground to a depth of at least 1200 mm1200\,\text{mm}.

10
New cards

Resistance Area of an Earth Electrode

The ground area surrounding an earth electrode across which a voltage gradient exists during an earth fault, typically extending outward to approximately 2.5 m2.5\,\text{m} where no further increase in resistance is measured.

11
New cards

Neutral Inversion

A dangerous phenomenon occurring when the supply PEN conductor breaks, causing the installation's neutral conductor and all bonded earthed metalwork to rise to the full phase potential (230 V230\,\text{V}) with respect to earth.

12
New cards

Equipotential Bonding

Electrical connections designed to maintain exposed conductive parts and extraneous conductive parts at substantially the same potential to prevent dangerous touch voltages from appearing between them during a fault.

13
New cards

Main Equipotential Bonding

The bonding of incoming metallic engineering services (gas, water, oil pipes, central heating, air-conditioning ducts, and structural steel) to the MET using copper conductors of not less than 10 mm210\,\text{mm}^2 (or half the CSA of the largest protective conductor).

14
New cards

Supplementary Equipotential Bonding

Local bonding applied within high-risk areas (such as bathrooms) that interconnects all exposed and extraneous conductive parts using insulated copper conductors of at least 2.5 mm22.5\,\text{mm}^2 (if mechanically protected) or 4 mm24\,\text{mm}^2 (if unprotected).

15
New cards

Direct Contact

The contact of persons or livestock with parts of an electrical installation that are normally live.

16
New cards

Indirect Contact

The contact of persons or livestock with exposed conductive parts or extraneous conductive parts that are not normally live, but have become live due to an insulation failure or internal fault.

17
New cards

EEBADS

An acronym standing for Earthed Equipotential Bonding and Automatic Disconnection of Supply, a primary protective method against electric shock.

18
New cards

TN-C-S System

An earthing system where the neutral and protective functions are combined into a single PEN conductor from the supply source to the entry point, and separated into distinct neutral (N\text{N}) and protective (PE\text{PE}) conductors within the consumer installation.

19
New cards

TN-S System

An earthing system having separate protective (PE\text{PE}) and neutral (N\text{N}) conductors throughout both the supply network and the installation.

20
New cards

TN-C System

An earthing arrangement in which the neutral and protective functions are combined into a single conductor (PEN) throughout both the supply network and the installation.

21
New cards

TT System

An earthing system where the source is directly earthed and the exposed conductive parts of the installation are connected to an independent consumer earth electrode with no supply-provided protective path, requiring an RCD for fault protection.

22
New cards

IT System

An earthing system where the source has no connection to earth (isolated) or is connected via a high impedance, while exposed conductive parts are connected to an independent installation earth electrode, ensuring power continuity on a first fault.

23
New cards

Earth Fault Loop Impedance (ZsZ_s or ZLZ_L)

The total impedance of the complete closed path traversed by fault current during a phase-to-earth fault, determined by the formula Zs=Ze+(R1+R2)Z_s = Z_e + (R_1 + R_2).

24
New cards

External Earth Fault Loop Impedance (ZeZ_e)

The impedance of the supply network external to the installation, comprising the supply transformer secondary winding, the phase service conductor, and the supply return path/PEN conductor.

25
New cards

Class I Equipment

Electrical equipment having basic insulation throughout that relies on the earthing of exposed conductive parts via a protective conductor for protection against indirect contact.

26
New cards
<p>Class II Equipment</p>

Class II Equipment

Electrical equipment constructed with double or reinforced insulation throughout that does not require and must not be connected to a protective earth conductor.

27
New cards

Class III Equipment

Equipment designed to operate exclusively from a Separated Extra-Low Voltage (SELV\text{SELV}) supply in which internal voltages higher than extra-low voltage are not generated.

28
New cards

Separated Extra-Low Voltage (SELV)

An extra-low voltage system (≤50 V a.c.\le 50\,\text{V a.c.} or ≤120 V d.c.\le 120\,\text{V d.c.}) fed from a safety isolating transformer, completely electrically isolated from earth and other electrical systems.

29
New cards

Protective Extra-Low Voltage (PELV)

An extra-low voltage system (≤50 V a.c.\le 50\,\text{V a.c.} or ≤120 V d.c.\le 120\,\text{V d.c.}) electrically separated from higher voltages by double or reinforced insulation, but having one point on the circuit intentionally connected to earth for functional purposes.

30
New cards

Functional Extra-Low Voltage (FELV)

An extra-low voltage system that does not meet the safety requirements of SELV or PELV, such as lacking double or reinforced insulation between its secondary circuit and low-voltage primary windings.

31
New cards

Reduced Low Voltage (RLV)

A site safety supply system operating at 110 V a.c.110\,\text{V a.c.} supplied from a double-wound transformer with an earthed secondary centre-tap, limiting maximum shock exposure to 55 V a.c.55\,\text{V a.c.} to earth on single-phase outlets.

32
New cards

Residual Current Device (RCD)

A mechanical switching device intended to interrupt supply when the vector algebraic sum of the instantaneous live currents (the residual operating current IΔnI_{\Delta n}) reaches a set threshold.

33
New cards

Type S RCD

A time-delayed residual current device installed upstream to achieve selectivity and prevent tripping before downstream general-type RCDs operate.

34
New cards

Arc Fault Detection Device (AFDD)

A microprocessor-based protective device fitted at the origin of a final circuit to analyse current waveforms and disconnect the circuit upon detecting series or parallel electrical arcing signatures, mitigating fire risk.

35
New cards

Surge Protection Device (SPD)

A device designed to protect consumer units, electrical wiring, and sensitive electronic equipment against transient overvoltages by limiting voltage spikes and diverting surge currents safely to earth.

36
New cards

Calculated Risk Level (CRL)

A risk-assessment formula value for transient overvoltages; protection against atmospheric surges is mandatory if CRL<1000CRL < 1000, but not required if CRL≥1000CRL \ge 1000.

37
New cards

Fall of Potential Method

An earth electrode resistance measurement method (Annex 6C, Method C1) utilizing two auxiliary test electrodes (potential spike and current spike) placed at specified distances from the main electrode under test.

38
New cards

Denso Tape

A waterproof petrolatum-impregnated tape applied over the earth electrode clamp connection to prevent chemical degradation, electrolytic corrosion, and moisture ingress.

39
New cards

Safety Electrical Connection Label

A permanent embossed metallic label bearing the inscription 'SAFETY ELECTRICAL CONNECTION - DO NOT REMOVE' that must be affixed to all main and supplementary bonding pipe clamps and electrode inspection boxes.

<p>A permanent embossed metallic label bearing the inscription 'SAFETY ELECTRICAL CONNECTION - DO NOT REMOVE' that must be affixed to all main and supplementary bonding pipe clamps and electrode inspection boxes.</p>
40
New cards

Bathroom Zone 0

The interior space of a bathtub or shower tray where installed equipment must achieve an ingress protection rating of at least IPX7 (protection against temporary immersion).

41
New cards

Adiabatic Equation for Protective Conductors

The formula S=I2tkS = \frac{\sqrt{I^2 t}}{k} used to determine the minimum cross-sectional area (SS) of a protective conductor based on prospective fault current (II), disconnection time (tt), and conductor material factor (kk).