Differences between wastewater and water?
Smaller pipes in water system generally 8” or less
Valves and hydrants
Pressure pipes everywhere
No flow direction
Looped
Storage
Characteristics of a Properly Functioning System
Redundancy: water main break or contamination only effects a small portion of the system
Quality: water leaving treatment plant is safe to drink throughout the entire system
Quantity: ability to meet demands at all times
Access
NR 811.70 Water Main Design
Point of entry quality: maintained quality throughout the entire system
Multidirectional flow: redundancy
Adequate shut off valves: allows us to isolate a problem
Adequate fire protection (hydrants)
Adequate flushing
Maximize turnover, minimize dead ends: stagnant water can have bacterial presence, organic matter can form carcinogens or disinfection by-products
Palatability
Deliver code complying pressure and flow
NR 811.70 Pressure
Sized based on hydraulic analysis for flow and pressure
Static pressure must be > 35 psi and < 100 psi
Minimum residual pressure must be above 20 psi at ground level for any flow
Static pressure: demand we see under normal conditions
Residual pressure: remain in the system when there is a high demand during say a fire
NR 811.70 Size and Fire Protection
Water mains that provide fire protection must be greater than or equal to 6 in
Minimum flow requirement is 500 gpm at 20 psi residual pressure
NR 811.70 Dead End and Valves
Dead ends
Minimized by looping
If they occur, they should terminate with a fire hydrant or flushing hydrant
Valving
No more than 500 ft in commercial, 800 ft in other districts
Why does pressure vary during the day?
High pressure at night
Pressure cycles through the day
Drop in pressure around 8 am then recovers mid day and then drops again around 5 pm
Drop because of high demands → draining storage
Then pumps kick on and begin filling tower
Another drop around 5 pm
Why does pressure vary with pipe size?
Q =vA
Small A = high v = higher headloss
small pipes = larger headloss → decreasing pressures

How would an increase in demand affect pressure variation graphs
sharper and deeper declines with high demands

What would the curves look like for an infinite diameter pipe?
It would look similar to the 12 and 16” pipe curve

How many ft does the water level in the storage tank vary?
Look at pipes with no friction losses
High point = 53 psi
Low Point = 40 psi
53- 40 = 13 psi * (2.3 ft/psi) = 30 ft of variation

Pipes in Series
Q1 = Q2 = Q3 = Qn
hL tot = hL1 + hL2 + hL3 + hLn
Pipes in Parallel
Qtot = Q1 + Q2 + Q3 + Qn
hL1 = hL2 = hL3 = hLn
Importance of loops
Water quality
Redundancy
Hydraulic Performance
What do we do when it is not possible to have everyone on ONE zone?
Create Pressure Zones
Pressure Zone
Zone of similar pressure
We can create them through the use of network separation and valves
Pressure reducing valves
How to address water demands on the supply side?
Building a new reservoir
Increasing reservoir size
Increasing height of a dam
Putting pumps in
How to address water demands on the demand side?
Increasing efficiencies through conservation practices
Pricing policy
Effect behavioral changes
Water hammer
Pressure wave phenomenon created by sudden changes in fluid velocity
valve or pumps
vapor pocket collapse
rapid expulsion of air out of vent or partially closed valve
Explain the purpose of the public service commission (PSC)
The mission is to oversee and facilitate the efficient and fair provision of quality utility services in Wi
Excellent information on a utility - specifically financial and physical information
Sectoral breakdown of water usage and sales
Discuss the significance of unaccounted for water and define the different types
Non-revenue water
percentage of water loss
5% is really low
Typically teens or up to 25% ish
Higher is a red flag
Types
Real Losses: These are actual water losses from the system before it reaches the customer (leaks)
Apparent Losses: These are losses that occur but are not due to physical leakage (metering discrepancies, billing anomalies, unauthorized usage)
Explain the danger in cross connections
Actual or potential connections between potable and non-potable water supply, constitute a serious public health hazard
Backflow (non‑potable source at higher pressure forces wastewater into the water main)
Backsiphonage (pressure drop pulls wastewater in
Three fundamental purposes of storage
Emergency supply
~25% of total storage capacity
Fire Protection (Conflagaration)
4h for fire flow more than 4000 gpm, 2h 2750 gpm
Equalizing/Operating Storage
Usually 15-20% of days supply
Fire Hydrants
Shall be provided at each street intersection
Spacing may range from 350 t0 600 ft
Connecting main between the supply main and the hydrant shall be a minimum of 6 in in diameter
500 gpm at 20 psi
Hydrant Test Steps
Locate hydrant(s) to be tested- inform public works
Place gage on hydrant that will be residual hydrant- open valve
Residual hydrant - measures residual pressure during test
Collect static pressure from this hydrant
Flow hydrant for test and measure pressure during test
Slowly close valve on flowed hydrant, close valve on residual hydrant
Why perform hydrant tests?
Provides information about existing pressure and capabilities to meet fire flow needs
Extending line or adding new neighborhood
Adding new industries or other demands
Calibration of hydraulic model
Isolation valves
isolate portions of a system for repair, inspection, or maintenance
fully open or closed (should be operated periodically)
install one less at a junctions than legs coming in or out
gate valves and butterfly valves
Check Valves
Backflow preventors
Control Valves
Pressure reducing valves: establish lower pressure downstream
Pressure Sustaining valves: sustain pressure upstream
Network Modeling Rules
Flow into each junction must equal flow out of each junction
Algebraic sum of head loss around any closed loop must be zero