NEC 220.14 - each outlet has an assigned load of ___
180VA
NEC Table 310.16 covers conductors rated up to ___
0-2000V
NEC 220.14(I) each receptacle is assigned a value of ___
180VA
NEC 220.54 the load for household electric dryers must be calculated at ____ or ____
5000VA or the nameplate rating of the dryer — whichever is larger
When space heating equipment utilizes electric resistance heating elements, protection for the resistance elements shall not exceed 60A.
NEC 424.22(B)
If breaker is not sufficient to hold the starting current of the motor, the rating is permitted to be increased but cannot exceed ___ or the branch circuit selection current, whichever is greater.
225% of the motor rated load current
Show window loads are ___
Always continuous
NEC 220.14 (G) provided two options for calculating branch circuit loads for show window lighting: either using the computed receptacle load of ___ (300mm) of show window.
180VA per receptacle or 200VA per linear foot
The actual sign load cannot exceed ___
80% of the branch circuit rating
NEC 220.14(E), outlets for heavy duty lamp holders are calculated at a minimum of ___ each
600VA
NEC table 220.56 lists demand factor for ___
Commercial kitchen equipment
NEC table 430.248 is used to determine
Full load current for single phase AC motors
NEC Table 430.250
Used to determine full load current for 3 phase AC motors
NEC table 310.16 used to determine
Branch circuit conductor size
table 430.52 used for
Motor short circuit and ground fault protection
NEC section 630.32(A) is for resistance welders it provides the rating or setting for the over current protection device shall not exceed ___ of the welder
300% of the primary current rating
The reciprocal of 125% (1.25) is 1/1.25 which is equivalent to ___ at the over current protection device
80% of the rating
NEC 210.11(C)(2) and 210.52(F) require the installation of at least one receptacle to ___
Supply laundry equipment
NEC section 210.14 (H)(1) each ___ is considered as one outlet of at least 180VA capacity. In locations where many appliances are likely to be used at one time, each 1' of multi outlet assembly is considered as one outlet of at least 180VA capacity
5' of the multi outlet assembly