LEVEL 3 MODULE 1 Load Calculations-Branch and Feeder Circuits

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/18

encourage image

There's no tags or description

Looks like no tags are added yet.

Last updated 7:10 PM on 9/22/26
Name
Mastery
Learn
Test
Matching
Spaced
Call with Kai
Chat

No analytics yet

Send a link to your students to track their progress

19 Terms

1
New cards

NEC 220.14 - each outlet has an assigned load of ___

180VA

2
New cards

NEC Table 310.16 covers conductors rated up to ___

0-2000V

3
New cards

NEC 220.14(I) each receptacle is assigned a value of ___

180VA

4
New cards

NEC 220.54 the load for household electric dryers must be calculated at ____ or ____

5000VA or the nameplate rating of the dryer — whichever is larger

5
New cards

When space heating equipment utilizes electric resistance heating elements, protection for the resistance elements shall not exceed 60A.

NEC 424.22(B)

6
New cards

If breaker is not sufficient to hold the starting current of the motor, the rating is permitted to be increased but cannot exceed ___ or the branch circuit selection current, whichever is greater.

225% of the motor rated load current

7
New cards

Show window loads are ___

Always continuous

8
New cards

NEC 220.14 (G) provided two options for calculating branch circuit loads for show window lighting: either using the computed receptacle load of ___ (300mm) of show window.

180VA per receptacle or 200VA per linear foot

9
New cards

The actual sign load cannot exceed ___

80% of the branch circuit rating

10
New cards

NEC 220.14(E), outlets for heavy duty lamp holders are calculated at a minimum of ___ each

600VA

11
New cards

NEC table 220.56 lists demand factor for ___

Commercial kitchen equipment

12
New cards

NEC table 430.248 is used to determine

Full load current for single phase AC motors

13
New cards

NEC Table 430.250

Used to determine full load current for 3 phase AC motors

14
New cards

NEC table 310.16 used to determine

Branch circuit conductor size

15
New cards

table 430.52 used for

Motor short circuit and ground fault protection

16
New cards

NEC section 630.32(A) is for resistance welders it provides the rating or setting for the over current protection device shall not exceed ___ of the welder

300% of the primary current rating

17
New cards

The reciprocal of 125% (1.25) is 1/1.25 which is equivalent to ___ at the over current protection device

80% of the rating

18
New cards

NEC 210.11(C)(2) and 210.52(F) require the installation of at least one receptacle to ___

Supply laundry equipment

19
New cards

NEC section 210.14 (H)(1) each ___ is considered as one outlet of at least 180VA capacity. In locations where many appliances are likely to be used at one time, each 1' of multi outlet assembly is considered as one outlet of at least 180VA capacity

5' of the multi outlet assembly