1/38
Vocabulary-style flashcards covering NFPA 72 key acronyms, definitions, device types, circuit classifications, and testing parameters based on the lecture notes.
NFPA 72
National Fire Alarm and Signaling Code
NFPA
National Fire Protection Association
AHJ
Authority Having Jurisdiction: the organization or person (often fire marshal/inspector) who enforces the code and approves equipment and installations
FACP
Fire alarm control panel (control unit)
NAC
Notification appliance circuit: wiring that powers horns, strobes, and speakers
IDC
Initiating device circuit: wiring that connects initiating devices such as detectors and pull stations
SLC
Signaling line circuit: carries data between the panel and addressable devices
EOL
End-of-line device (usually a resistor) that lets the panel supervise the wiring
Alarm Signal
A signal indicating an emergency that requires immediate action, such as a fire
Trouble Signal
A signal indicating a fault in a monitored circuit or component
Supervisory Signal
A signal indicating the need for action related to supervision of fire suppression systems or equipment (e.g., a closed sprinkler valve)
Initiating Device
A device that starts a signal at the panel: smoke detector, heat detector, pull station, waterflow switch, etc.
Notification Appliance
A device that alerts occupants: horn, strobe, speaker, chime, bell
Addressable Device
A device with its own address so the panel identifies exactly which device is in alarm or trouble
Conventional (Zone) System
A system where devices are grouped on zones; the panel shows which zone is in alarm but not the exact device
Annunciator
A remote display showing the status and location of alarm, trouble, and supervisory conditions
Primary Power Supply
Normally commercial AC power from the building
Secondary Power Supply
Batteries (or generator) that power the system if primary power fails
Ground Fault
An unintended connection between a circuit conductor and ground; must be detected and reported as trouble
Class A Circuit
Has a redundant return path; can still operate through a single open or break
Class B Circuit
Single path with no redundancy; a single open stops devices beyond the break from working (trouble is reported)
Central Station
A supervising station that receives alarm, trouble, and supervisory signals and dispatches response
DACT
Digital alarm communicator transmitter: panel's phone/communicator that sends signals to the monitoring company
Photoelectric Smoke Detector
Uses light scattering; generally better at detecting smoldering fires
Ionization Smoke Detector
Uses a small radioactive source; generally better at detecting fast, flaming fires
Fixed-Temperature Heat Detector
Activates when the detecting element reaches a set temperature
Rate-of-Rise Heat Detector
Activates when temperature rises faster than a set rate
Waterflow Switch
Detects water moving in a sprinkler pipe and sends an alarm signal
Valve Tamper Switch
Sends a supervisory signal when a sprinkler control valve is moved from its normal open position
Duct Smoke Detector
Detects smoke in HVAC ductwork, usually to shut down fans/prevent smoke spread
Beam Smoke Detector
Projects a light beam across a space and detects smoke that blocks or reduces it
Manual Pull Station
Manual fire alarm box that a person operates to start an alarm
Record of Completion
Document completed after installation that records the system as installed and tested
Impairment
A condition where a fire protection system or part of it is out of service
Fire Watch
Trained people patrolling a building to look for fire when the system is impaired
Temporal-3
Standard evacuation signal pattern consisting of three pulses, pause, repeat
Public Mode Audible Level
15dB above average ambient, or 5dB above max sound lasting 60+ seconds, whichever is greater
Private Mode Audible Level
10dB above average ambient, or 5dB above max sound lasting 60+ seconds, whichever is greater
Secondary Power Duration
24hours standby plus 5minutes of alarm (15minutes for voice evacuation)