1/12
Vocabulary flashcards covering the components of the La Marche A41 Battery Charger schematic, battery charging types, charging rate safety guidelines, and electrolyte temperature limits.

La Marche A41 Battery Charger Schematic
The schematic diagram depicting the circuit layout of the La Marche A41 battery charger, featuring the AC input, power transformer, full-wave rectifier, cutoff relay, and voltage regulation circuitry.
Power Transformer (T1)
The transformer component (labeled B) in the La Marche A41 battery charger circuit that steps down incoming AC voltage for rectification and battery charging.
Full-Wave Rectifier (Rectifier 502)
The component (labeled E) in the La Marche A41 battery charger schematic that converts AC voltage from the secondary winding of the power transformer into DC voltage.
Voltage Regulation Circuitry
The sub-circuit (labeled F / AC1, AC2) in the La Marche A41 battery charger that monitors and regulates charger output voltage to maintain stable charging conditions.
Cutoff Relay
A relay component (labeled C) within the La Marche A41 battery charger circuit that controls or terminates the charging process.
Initial Charge
The first low-rate charge put on a battery before it is placed into service, conducted in accordance with the manufacturer's instructions.
Normal Charge
A routine charge given to replace used energy in accordance with manufacturer's instructions, usually conducted at 10 amps or less.
Boost Charge (Equalizing Charge)
An extended normal charge at a low rate (current) done to ensure sulfate is driven off the plates, continued until the specific gravity, corrected for temperature, has remained constant for 4 hours with readings taken every 1/2 hour.
Float Charge
A low-rate (current) charge that maintains battery readiness at all times, where the charging rate is determined by voltage rather than current, specifically at 2.13 to 2.17 volts per cell.
Fast Charge
A high-rate (current) charge used to charge a battery in a short period; it is used only in an emergency due to the possibility of damaging the battery plates.
Charging Rate
The rate at which electron flow is forced into the battery, with the safest charging rate defined as being below 10 amperes.
Hazards of an Excessive Charging Rate
Damaging the battery by overheating and creating excess gas, which can break down the active material of the plates.
Maximum Electrolyte Temperature Limit
The critical threshold specifying that the electrolyte temperature in any battery cell must never be allowed to rise above 125 degrees.