Practice flashcards covering vocabularies and definitions from the EPA Section 608 Preparatory Manual regarding refrigerant regulations, types, recovery techniques, and safety.
Section 608 of the Clean Air Act
A federal regulation that requires all persons who maintain, service, repair, or dispose of appliances containing regulated refrigerants (CFC, HCFC, HFC, and HFO) to be certified in proper refrigerant handling techniques.
Small appliance
A pre-assembled unit, hermetically sealed and factory charged with 5lbs or less of refrigerant, such as water coolers, window units, and refrigerators.
Type II Technician
A person certified to maintain, service, repair, or dispose of appliances containing more than 5lbs of refrigerant, or if the installation requires refrigerant charging, excluding small appliances or MVAC systems.
Type III Technician
A person certified to maintain, service, repair, or dispose of low-pressure appliances, such as centrifugals and chillers.
Universal Technician
A person certified to maintain, service, or repair low-pressure equipment, high-pressure equipment, and small appliances.
Ozone Depletion Potential (ODP)
A measurement of the ability of a substance to destroy ozone in the stratosphere.
Global Warming Potential (GWP)
A value established to provide comparisons of the global warming impacts of different gases over a span of time, using Carbon Dioxide (CO2), which has a value of 1, as the baseline.
Chlorofluorocarbons (CFCs)
Refrigerants containing chlorine, fluorine, and carbon; they have the highest ODP and include examples like R−11 and R−12.
Hydrochlorofluorocarbons (HCFCs)
Refrigerants containing hydrogen, chlorine, fluorine, and carbon; they are less harmful to stratospheric ozone than CFCs and include R−22 and R−123.
Hydrofluorocarbons (HFCs)
Refrigerants containing hydrogen, fluorine, and carbon; they have zero ODP but often have high GWP. Examples include R−134a and R−410A.
Hydrofluoroolefins (HFOs)
Refrigerants that contain at least one double bond between carbon atoms, having no ODP and very low GWP. Examples include R−1234yf.
Hydrocarbons (HCs)
Elementary compounds of hydrogen and carbon with zero ODP and very low GWP (values less than 10), such as isobutane (R−600a) and propane (R−290).
Azeotropic refrigerant mixture
A mixture of two or more refrigerants that evaporates and condenses at a constant temperature and acts as a pure compound.
Zeotropic/Non-azeotropic mixture
A blend of refrigerants with different boiling points that experiences temperature glide and may experience fractionation.
Temperature glide
The range of temperatures over which a zeotropic or non-azeotropic refrigerant blend evaporates and condenses at a constant pressure.
Bubble point
The liquid values on a pressure-temperature chart used when charging a system by condenser subcooling.
Dew point
The vapor values on a pressure-temperature chart used for charging by suction or evaporator superheat.
Fractionization
Refrigerant leaking from a system at uneven rates due to different vapor pressures within a blended refrigerant.
Low-pressure refrigerants
Refrigerants that have a pressure of 30psig or lower at a liquid-phase temperature of 104∘F.
Recover
To remove refrigerant in any condition from a system and store it in an approved external cylinder or container without necessarily testing or processing it.
Recycle
To extract refrigerant from an appliance and clean it for reuse in equipment of the same owner by using oil separation and filter-driers to reduce moisture and acidity.
Reclaim
To process refrigerant to a level equal to new (virgin) product specifications as determined by chemical analysis, meeting AHRI700 Standards.
De−minimis
A minor release of refrigerant when connecting or disconnecting hoses for service or recovery, which is not considered an unlawful violation of the venting prohibition.
Self-contained (Active) recovery device
A recovery device that has its own means to draw the refrigerant out of the appliance.
System-dependent (Passive) recovery device
A recovery device that captures refrigerant with the assistance of components in the appliance, such as the system's own compressor or pressure.
Dehydration
The process of removing water and water vapor from a system by evacuating it to a minimum of 500microns.
Comfort Cooling
Air-conditioning appliances used to supply cooling to control heat and/or humidity in occupied facilities like residential or office buildings.
Commercial Refrigeration
Appliances used to preserve products, such as those found in the retail food and cold storage warehouse sectors.
Industrial Process Refrigeration (IPR)
Appliances where 55% or more of the cooling capacity is used for manufacturing lines or industrial processes.
Major Repair
As defined by the EPA, the replacement or repair of a compressor, condenser coil, evaporator coil, or other system heat exchanger.
Purge Unit
A device on low-pressure chillers used to remove non-condensables (air and moisture) that leak into the system.
Rupture disc
A safety device located on the evaporator of a centrifugal chiller that relieves pressure at 15psig to prevent system over-pressurization.