DC Generators: Comparison & Applications

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/17

flashcard set

Earn XP

Description and Tags

Vocabulary practice flashcards covering induced EMF formulas, operation, characteristics, circuit diagrams, and practical applications of separately excited, shunt, series, and compound DC generators.

18 Terms

1
New cards

Basic DC Generator Induced Voltage Equation

The fundamental relationship Eo=Znϕ60=kϕωE_o = \frac{Z n \phi}{60} = k \phi \omega, where EoE_o is induced voltage, ZZ is total armature turns, nn is rotor rotation speed in rpm, ϕ\phi is flux per pole, kk is the induced voltage constant, and ω\omega is rotational speed in rad/s\text{rad/s}.

2
New cards

Separately Excited DC Generator

A DC generator in which the field winding is powered by an independent external DC source, making the field flux ϕ\phi constant and independent of load current so that for a fixed rotational speed, EoE_o and terminal voltage V12V_{12} remain almost constant with varying load.

3
New cards
<p>Separately Excited 2-Pole Generator Diagram (Figure 17)</p>

Separately Excited 2-Pole Generator Diagram (Figure 17)

A machine diagram illustrating how external exciting current IxI_x fed into terminals aa and bb magnetizes the field coils to form the North (N\text{N}) and South (S\text{S}) poles, producing induced voltage EoE_o across armature terminals xx and yy.

4
New cards
<p>Load Characteristic of a Separately Excited Generator (Figure 24)</p>

Load Characteristic of a Separately Excited Generator (Figure 24)

A curve showing terminal voltage E12E_{12} versus load current II, demonstrating a slight downward slope described by V12=Eo−Ro⋅IV_{12} = E_o - R_o \cdot I where voltage decreases from 100 V100\,\text{V} at no load to 90 V90\,\text{V} at 10 A10\,\text{A} due to armature internal resistance RoR_o.

5
New cards
<p>Flux per Pole versus Exciting Current Curve (Figure 18a)</p>

Flux per Pole versus Exciting Current Curve (Figure 18a)

A plot depicting magnetic flux per pole (in per-unit, p.u.) versus exciting current IxI_x, showing an initial linear magnetic rise up to point aa, the knee and rated flux (1.00 p.u.1.00\,\text{p.u.} at 1 A1\,\text{A}) at point bb, and magnetic saturation leading toward point cc.

6
New cards
<p>Saturation Curve of a DC Generator (Figure 18b)</p>

Saturation Curve of a DC Generator (Figure 18b)

An open-circuit magnetization characteristic curve showing induced voltage EoE_o versus exciting current IxI_x at fixed speed, demonstrating a linear initial rise up to rated voltage of approximately 120 V120\,\text{V} at 1 A1\,\text{A} before entering the saturation region.

7
New cards
<p>Shunt DC Generator (Figure 19)</p>

Shunt DC Generator (Figure 19)

A self-excited generator configuration where the field winding is connected in parallel (shunt) across the armature winding, using its own output voltage across terminals xx and yy to establish the exciting current IxI_x.

8
New cards

Voltage Drop Mechanism in Shunt DC Generators

A four-step cumulative voltage drop process: an increase in load current increases armature current IaI_a, raising internal resistance drop (V=E−IaRaV = E - I_a R_a); the resulting decrease in terminal voltage VV reduces field current (If=VRfI_f = \frac{V}{R_f}) and field flux Φ\Phi, causing generated EMF EE to drop (E∝ΦE \propto \Phi) and terminal voltage to decline even further.

9
New cards
<p>Series DC Generator (Figure 2)</p>

Series DC Generator (Figure 2)

A generator configuration in which the field winding (RfseR_{fse}) is wired directly in series with the armature and the load, resulting in the series field carrying the full load current (If=ILI_f = I_L).

10
New cards

Terminal Voltage Characteristic of a Series DC Generator

The behavior wherein an increase in load current ILI_L increases field current IfI_f and field flux Φ\Phi, increasing generated EMF EE (E∝ΦE \propto \Phi); because the increase in EE outweighs the internal IaRaI_a R_a drop, terminal voltage V=E−IaRaV = E - I_a R_a net increases with load.

11
New cards
<p>Long Shunt DC Generator (Figure 5)</p>

Long Shunt DC Generator (Figure 5)

A compound DC generator circuit layout where the shunt field winding (RfshR_{fsh}) is connected across the outer terminals, placing it in parallel with the series combination of the armature and the series field winding (RfseR_{fse}).

12
New cards

Compound DC Generator

A generator combining two separate field windings: a shunt field connected in parallel with the armature and a series field connected in series with the load, designed to balance and stabilize voltage under changing loads.

13
New cards

Cumulative Compounding Voltage Stabilization

A design where load current increases series field current (Ise=ILI_{se} = I_L) and series flux (Φse∝IL\Phi_{se} \propto I_L), raising total flux (Φ=Φsh+Φse\Phi = \Phi_{sh} + \Phi_{se}) and generated EMF (E∝ΦE \propto \Phi) to precisely compensate for armature resistance drop and armature reaction, keeping terminal voltage nearly constant.

14
New cards

Voltage Booster

A specialized application of series DC generators where the machine is placed in series with electrical feeders to automatically raise terminal voltage and compensate for line resistance drops as transmission load current increases.

15
New cards

Applications of Separately Excited DC Generators

Used where precise and stable voltage or speed regulation is required, such as in research laboratories, testing and calibration setups, and DC motor speed control; rarely used in broader industry due to the high cost and complexity of an external DC supply.

16
New cards

Applications of Shunt DC Generators

Used for lighting systems, battery charging, and general laboratory DC power supplies where loads are light to medium and can tolerate minor voltage variations, but unsuitable for heavy loads due to progressive voltage drop.

17
New cards

Applications of Compound DC Generators

Used in DC power distribution systems, elevators, cranes, hoists, workshops, and factories where sudden, heavy, and variable loads switch on and off and require a stable, constant terminal voltage.

18
New cards

Efficiency Equation of a DC Generator

The formula η=PoutPin×100=PoutPout+Parmature+Pf+other losses×100\eta = \frac{P_{out}}{P_{in}} \times 100 = \frac{P_{out}}{P_{out} + P_{armature} + P_f + \text{other losses}} \times 100, where electrical losses are calculated using P=RI2P = R I^2.