July 1 2005, service techs shall possess or work under someone who has a current certification indicating he or she has passed the ?

California UST service technician exam

2
New cards

ICC cert must be renewed every?

24 months

3
New cards

Service techs must posses or be employed by a person who has the appropriate contractors license unless?

The individual has a Tank testing licens

4
New cards

Service tech is defined by any individual who?

Test UST monitoring equipment

Trouble shoots UST systems

Installs UST monitoring equipment

5
New cards

If the manufacturer training no longer exist , the local angency may?

Approve comparable alternat training .

6
New cards

UST includes?

Tank and connected piping

7
New cards

What is considered and UST

petroleum storage tank

8
New cards

What UST system meets the requirements for secondary containment?

Doubled wall tanks

9
New cards

According to title 23; the following piping components if installed after July 1 1987 must have secondary containment

Pressured product piping

10
New cards

Considered "pipe" on tanks installed after July 1 2003

Pressured product piping and below ground vapor recovery

11
New cards

Under dispenser containment (UDC) was required for all UST systems by

December 31 2003

12
New cards

System for exchanging gas vapors in a storage tank and product in a fuel delivery truck

Stage 1 vapor recovery

13
New cards

An approved method for non visual monitoring for existing UST systems.

Statistical Inventory Reconciliation (SIR)

14
New cards

ATG must be capable for detecting a release of ?

.2 gallons per hour

15
New cards

Manual inventory reconciliation.

No longer an approved method for non visual monitoring on existing UST systems

16
New cards

Automatic line leak detectors installed on underground piping with secondary containment shall be capable of tetecting a leak of ?

3 gallons per hour at 10 psi

17
New cards

ATG should be programmed to test the tank ?

At least monthly

18
New cards

According to PEI RP 300 a combustible gas can be used to ?

Detect vapor leaks in a vapor recovery system.

19
New cards

According to PEI RP 300. A written scope of work for vapor recovery installation should include?

Construction plans

20
New cards

Positive shut off overfill protection device must stop the flow of fuel when the tank is no more then ?

95% full

21
New cards

According to EO VR 201 A What could cause a nozzle shut off mechanism or malfunction?

Depended filter seal damage

22
New cards

According to VR 201 A Breakaway reconnection must be ?

Logged in GDF log

23
New cards

According to PEI RP 300 the following method of documenting piping location is NOT to ?

Sketch a diagram on the inside cover of vapor recovery equipment manual

24
New cards

According to PEI RP 300 as built drawing or pictures of the underground pipping and other components shall be ?

Maintained as long as UST is in service

25
New cards

According to EO VR 101 E maintance records are required to include?

Name and designated UST operator .

26
New cards

The Phil-Tite EVR phase 1 system require that vapor vent pipes at any UST system be

Used with no more then 3 p/v valves

27
New cards

According to EO VR 2010 after installing a new spout assembly in the Healy 900 nozzle the following test must be conducted ?

Nozzle dispensing shut off test

28
New cards

According to Healy EO VR 201 A a vapor recovery record are to be maintained by?

Gasoline dispensing facility operator

(GDF)

29
New cards

how many feet within a public drinking well require an enhanced leak detection test

1000 feet

30
New cards

What are the components of the Fire Triangle ?

Fuel Ignition source oxygen

31
New cards

If equipped with an over fill alarm, it must be located?

So it can be seen or heard from the delivery location.

32
New cards

UDC was required at time of installation for all systems installed after?

Januarary 1 2000

33
New cards

If installed, the following requires independent 3rd party certification to prove compliance with established regulations.

Automatic Tank Gauge

Liquid Product Detectors

SIR

34
New cards

Where are ATG's installed ?

Opening in top of the tank

35
New cards

What is true about ATG's

They're capable of alarming operator of low product level

36
New cards

The following types of releases must be reported to the local Agency.

Releases greater than 25 gallons that escape secondary containment.

Release that escape primary containment.

Releases less then 25 gallons which escape secondary containment

37
New cards

If an unauthorized product release meets the requirements for reporting to the local agency, verbal notification must be made within ____hours, followed by a written notification within ____days.

24, 5

38
New cards

The following unusual conditions shall be reported to the local agency, EXCEPT:

Water in spill buckets

39
New cards

If the monitoring system detects a leak that has occurred, the local agency must be notified.

Unless the monitoring device is found to be defective and is immediately repaired.

40
New cards

The written report submitted to the local agency after an unauthorized release is required to include the following EXCEPT:

Cause of release

41
New cards

An unauthorized release which does not escape secondary containment, requires only recordation on the Operators Manual Report provided.

It did not cause deterioration of secondary containment.

It did not increase the hazard of fire.

It was cleaned up within eight hours addicti it was cleaned up within eight hours detection.

42
New cards

Recording of an authorized release in the operators monitoring records shall include?

Actions taken to prevent further releases.

43
New cards

If An authorize release meets reporting requirements of title 23 section 2652 the report must be filed within the?

Local agency

44
New cards

Which statement concerning the annual monitor certification is most correct?

Local agencies must be notified 48 hours prior to certification in results must be submitted within 30 days of certification.

45
New cards

The annual monitor certification may be performed by ?

A person possessing the appropriate contractors license.

An individual trained and certified by the manufacture of the monitoring equipment.

46
New cards

The following is true of secondary containment EXCEPT:

Must be tested every 24 months.

47
New cards

Enhanced the detections results must be submitted to ___ within ___days

The local agency and State water resources control Board.

60

48
New cards

The EPA recommends that monthly the operator should conduct a walk-through inspection of the following EXCEPT :

Facility lighting

49
New cards

Cathodic protection systems must be tested within ____Months of installation and every ____months thereafter.

6, 36

50
New cards

Impressed current catholic protection systems shall be expected no less then every ?

30 days

51
New cards

The EPA suggested list of supplies for spill containment and clean up include all the following EXCEPT:

Wet dry shop vacuum

52
New cards

According to the health and safety code the owner of a new tank must conduct a one time ELD test if the tank is located within 1000 ft of a public drinking water well. This test must accomplished by ?

January 1, 2005

53
New cards

The following is true of SIR data.

Must be submitted monthly to reconciliation provider.

54
New cards

Records of protection systems maintenance must be kept on file for?

6.5 years

55
New cards

Tank repair and upgrade records that Demonstrate compliance with title 23 regulations must be maintained?

For the life of a tank

56
New cards

Records for performance on release detection systems must be kept on file for ?

5 years

57
New cards

Monthly monitoring data must be kept on file For?

3 years

58
New cards

UST systems records must be maintained on site or ?

At a location approved with the local agency

59
New cards

A written statement indicating SIR results must be submitted to the ____every____

Local agency , 12 months

60
New cards

The following are overfill protection systems EXCEPT:

Spill buckets