Texas Residential Fire Alarm (v17.3)

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/24

flashcard set

Earn XP

Description and Tags

Vocabulary practice flashcards covering regulations, codes, installation standards, and definitions from the Texas Residential Fire Alarm examination.

Last updated 4:10 PM on 10/8/26
Name
Mastery
Learn
Test
Matching
Spaced
Call with Kai
Chat

No analytics yet

Send a link to your students to track their progress

25 Terms

1
New cards

Functional Test

The test required to be performed upon completing preventative or corrective maintenance before leaving the customer's premises.

2
New cards

Listed

A term indicating that an item shares certain qualities and meets certain tests.

3
New cards

White Label

A label used to indicate installation of service.

4
New cards

Red Label

A label required for a fire alarm system found to be defective or inoperable.

5
New cards

Blue Label

A label that must remain attached to a system for at least 5 years.

6
New cards

ESA Minimum Installation Standard (Circuit Wiring)

Standard specifying that all circuit wiring shall have conductors not smaller than #22 AWG.

7
New cards

UL 985

The standard for residential fire alarm system panels, allowing household control panels to combine fire alarm and security alarm functions.

8
New cards

System Maintenance Responsibility (NFPA 72)

According to NFPA 72, the customer is the person or persons responsible for keeping a residential fire alarm system in good working order once installed.

9
New cards

Photoelectric Smoke Detectors (Residential Types)

The two primary types of photoelectric smoke detectors utilized in homes: light scattering and light obscuration.

10
New cards

NFPA 72 Chapter 29

The primary starting point chapter in NFPA 72 for single- and multiple-station alarms and household fire alarm systems, which may refer the user to other chapters for specific rules.

11
New cards

FPL

The required wire rating for fire wire used on a residential fire alarm system.

12
New cards

Smoke Alarms

Self-contained units powered by springs, batteries, or AC with dry cell standby battery, intended to be either stand-alone or interconnected to each other.

13
New cards

Fire Alarm Grounding Exemption

Grounding is not required for alarm systems operating at less than 50 volts, unless explicitly specified by the manufacturer.

14
New cards

Side Wall Smoke Detector Mounting (NFPA 72)

Mounting requirement stating that some portion of the smoke detector must be at or above the point 12 inches below the ceiling level.

15
New cards

Peaked or Sloped Ceiling Smoke Detector Mounting (NFPA 72)

Requirement stating that devices must be placed within 3 feet of the peak horizontally, but no closer than 4 inches to the top of the peak.

16
New cards

Ceiling Jet

The lateral spread of rising heat and smoke along a ceiling after reaching the highest level of a room during a fire.

17
New cards

International Building Code (IBC)

A code that defines minimum regulations and is founded on broad-based principles that enable the use of new materials.

18
New cards

Factory Mutual

An organization that reviews product safety and verifies that products will meet stated conditions of performance and quality.

19
New cards

Overcurrent Protection (Non-Power-Limited Systems)

Protection standard requiring no more than 7 amps for 18 AWG conductors, and 10 amps for 16 AWG conductors.

20
New cards

Heat Detector Types

Fire detection device categories that include rate-of-rise, rate compensation, and fixed temperature mechanisms (ionization is a smoke detection principle, not heat).

21
New cards

Forced Air Supply Register Clearance (NFPA 72)

Spacing rule mandating that a smoke detector must not be mounted within 36 inches of a forced air supply register.

22
New cards

Split-Level Home Detection Requirement

NFPA 72 guideline driving the requirement for additional smoke detection between levels if there is an intervening door between the levels.

23
New cards

NFPA 70

The National Electrical Code (NEC).

24
New cards

Power-Limited Fire Alarm Cable Minimum Size

National code specification requiring that individual cables used in power-limited fire alarm systems cannot be smaller than 18 AWG.

25
New cards

Any arrangement of materials whose sole function is to detect fire, smoke, or combustion.

Fire Detection Device