1/33
Looks like no tags are added yet.
Why is sulfite mainly considered a lower-pressure boiler treatment?
It adds dissolved solids and can decompose at higher pressure
AWT Chapter 3 general sulfite pressure limit?
Under about 900 psig
Chapter 3 sulfite residual guideline up to 600 psig?
About 5-50 mg/L
Chapter 3 sulfite residual guideline above 600 psig?
About 5-20 mg/L
At what temperature/pressure can sulfite react with iron oxide?
Above about 430°F / 350 psia
What protective oxide can result from sulfite/iron-oxide reaction?
Magnetite, Fe3O4
Is sulfite considered a strong passivating agent in LP boilers?
No
Why avoid large sulfite overfeeds?
Added TDS and high-pressure decomposition concerns
Advanced boiler training: sulfite residual at 0-150 psi?
30-60 ppm
Advanced boiler training: sulfite residual at 150-300 psi?
20-40 ppm
Advanced boiler training: sulfite residual at 300-600 psi?
20-30 ppm
Advanced boiler training: sulfite residual at 600-900 psi?
10-15 ppm
Advanced boiler training: sulfite residual at 900-1200 psi?
5-10 ppm
Advanced training: sulfite recommendation at 1500 psi?
Not recommended
What happens to acceptable water quality as boiler pressure rises?
Required purity generally becomes more stringent
How often should low-pressure boilers generally be monitored?
Daily
How often should higher-pressure boilers generally be monitored?
About once per shift
How are many high-pressure field-erected boilers monitored?
Continuous online monitoring for many parameters
What pressure does psig reference?
Pressure above atmospheric pressure
What pressure does psia reference?
Absolute pressure from a vacuum
How do you convert psig to psia?
Add about 14.7 psi
How do you convert psia to psig?
Subtract about 14.7 psi
As boiler pressure increases, what happens to required feedwater purity?
It increases
Why does boiler-water treatment become more restrictive as pressure rises?
Higher pressure reduces tolerance for contaminants and dissolved solids
Which boiler class is below about 300 psig?
Low pressure
Which boiler class is about 300-900 psig?
Medium pressure
Which boiler class is about 900-1,200 psig?
High pressure
Which boiler class is above about 1,200 psig?
Very high pressure
In what pressure range is sulfite generally used?
Below about 900 psig
Why does sulfite become less desirable at higher boiler pressure?
It adds dissolved solids and can decompose at elevated pressure/temperature
As boiler pressure increases, what generally happens to allowable sulfite residual?
It decreases
Which can tolerate more conventional internal treatment: LP or HP boilers?
Low-pressure boilers
Which requires greater feedwater purity: LP or HP boilers?
High-pressure boilers
What is the overall pressure-treatment relationship?
Higher pressure = higher purity and tighter chemistry control