1/94
Looks like no tags are added yet.
A cascade refrigeration system operates between 105 kPa and 820 kPa. Find the cascade condenser pressure.
293 kPa
A test was conducted on a twin-cylinder, single-acting 16 cm x 22 cm, 400 rpm ammonia compressor. The refrigerant volume flow rate at the compressor inlet was measured to be 42 L/s. Determine the volumetric efficiency.
71.2%
A refrigeration system is designed to cool bread loaves of 650 g each from 24°C to -10°C at a rate of 480 loaves per hour using refrigerated air. The average specific heat of bread is 3.0 kJ/kg.°C, and the latent heat is 105 kJ/kg. Determine the product load.
1076.4 kJ/min
A 14-ton beef batch is cooled from 22°C to -28°C in 16 hrs. Freezing temp = -4°C, cp above freezing = 2.9 kJ/kg K, cp below freezing = 1.6 kJ/kg K, latent heat = 230 kJ/kg. If miscellaneous losses are 15%, find the tons of refrigeration.
27.3
A refrigeration system is used to cool 6 kg/s of water in the evaporator from 32°C to 4°C. Find the tons of refrigeration (TR) required. (1 TR = 3.517 kW).
200.1 TR
A simple R-12 refrigeration cycle operates at Te = -8°C and Tc = 38°C. For a refrigerating capacity of 12 kW, determine the compressor work. Given: At 38°C, hf = 240 kJ/kg. At -8°C, hg = 348 kJ/kg. Enthalpy at condenser inlet = 372 kJ/kg.
2.67 kW
A refrigerator has COP = 2.0. If it rejects 1200 kJ of heat, how much work input is required?
400 kJ
A manufacturer claims its refrigerator has COP = 10 when cooling at 5°C using ambient air at 25°C as heat sink. Is the claim valid?
YES
A refrigerator's 50 W light bulb stays on continuously due to a faulty switch. If COP = 2.0 and electricity costs 12 cents/kWh, determine the annual extra energy cost.
P26.3
A refrigerator with EER = 11 removes heat from the compartment at a rate of 120 kJ/min. Determine the heat rejected to the kitchen air.
157 kJ/min
A refrigeration system consumes 32,000 kWh/month. If 18% energy is lost to compressor cooling and motor efficiency is 92%, with COP = 5.5, find the tons of refrigeration.
52.4 TR
A 55 TR system has COP = 4.0. Find the cooling water flow rate in gpm if condenser water rises by 11°C.
83.2 gpm
A two-stage reciprocating air compressor with perfect intercooling operates at the optimum intermediate pressure. Air enters the low-pressure cylinder at 1 bar and 27°C and leaves the high-pressure cylinder at 9 bar. If the index of compression in each stage is 1.4 and R = 286.7 J/kg-K, what is the work done per kg of air in the high-pressure cylinder?
111 kJ/kg
A single-acting two-stage compressor with complete intercooling delivers air at 16 bar. If the intake pressure is 1 bar at 15°C, what is the pressure ratio per stage?
4
A reversed Carnot system operates between -3°C and 48°C. If compressor power = 50 kW, determine the system capacity in TR.
75.3 TR
A cold storage plant operates at -5°C while the surrounding temperature is 35°C. If the heat leakage into the cold storage is 28 kW and the actual COP is one-eighth of the maximum possible COP, calculate the power required to maintain the storage temperature.
33.43 kW
An R-12 reciprocating compressor operates between a condensing temperature of 30°C and an evaporator temperature of -20°C. The clearance volume ratio of the compressor is 0.03. The specific heat ratio of the vapor is 1.15 and the specific volume at suction is 0.1089 m³/kg. If the refrigerating effect is 111 kJ/kg, what is the actual volume displacement rate required to produce 2 tons of refrigeration, considering the effect of clearance?
6.26 x 10^-3 m³/s
A refrigeration plant has a refrigerating efficiency of 0.75, a condenser temperature of 45°C, an evaporator temperature of −15°C, and a cooling capacity of 3 kW. What work is required?
0.93 kW
A reversed Brayton refrigeration cycle maintains a space at 250 K. Air is cooled to 300 K at constant pressure, then rises by 50 K in the refrigerator. What is the net compression work per kg? Take cp = 1 kJ/kg-K.
25 kJ/kg
A refrigeration compressor has a swept volume of 0.18 m³/s, 7% clearance, and a compression ratio of 5.5. Bore equals stroke and speed is 400 rpm. Find the bore.
325 mm
A heat pump consumes 12 kW and rejects 55 kW to the heated space. If the high temperature is 42°C, find the low-temperature region.
-26.7°C
A 12 m × 8 m × 5 m cold room is maintained at −10°C while outside is 32°C. The overall heat transfer coefficient is 0.32 W/m²-K. Find the heat gain through the walls and ceiling.
3.98 kW
An ice plant produces 18 tons of ice per day from water initially at 25°C. Calculate the refrigeration load in TR.
26.05
A walk-in freezer requires a total refrigeration load of 42 kW. If the desired evaporator temperature difference is 8°C and the evaporator has an overall heat transfer coefficient of 28 W/m²-K, calculate the required evaporator area.
188 m²
One thousand pounds of fresh lean beef enters a cooler at 55°F and is chilled to 35°F in 24 hours. If the specific heat of lean beef above freezing is 0.75 Btu/lb-°F, what is the product load in Btu/24 hr?
15,000 Btu/24 hr
A walk-in cooler measuring 8 ft x 15 ft x 10 ft is constructed with 4 in. corkboard insulation and 1 in. wood on each side. The outside temperature is 95°F with 50% relative humidity, while the cooler is maintained at 35°F. If the number of air changes per 24 hr for a cooler volume of approximately 900 cu ft is 19 and the heat gain is 2.49 Btu/cu ft, what is the air change load in Btu/24 hr?
41,727 Btu/24 hr
An ammonia simple saturation refrigeration cycle operates between an evaporator temperature of -20°C and a condenser temperature of 35°C. The plant is designed to produce 5000 kg of ice at -12°C from water initially at 29°C in 20 hours. If losses are 20% of the heat absorbed from the water, calculate the refrigerant mass flow rate. Note: h₁ = 1437.2 kJ/kg, h₂ = 1735 kJ/kg, h3 = h4 = 366.1 kJ/kg
0.03747 kg/s
A six-cylinder R-22 compressor has a bore of 6.70 cm and stroke of 5.70 cm and operates at 30 r/s. The compressor produces a refrigerating capacity of 96.4 kW and requires 19.4 kW of power. It operates at an evaporating temperature of 5°C and condensing temperature of 35°C. If the clearance volume is 5%, calculate the actual volumetric efficiency. Note: h₁ = 407.1 kJ/kg, h₂ = 428 kJ/kg, h3 = h4 = 243.1 kJ/kg, v₁ = 40.36 L/kg, v2 = 20 L/kg
65.58%
A refrigerator operating on a reversed Carnot cycle works between two temperature limits such that the ratio of the low temperature to the high temperature is 0.75. If a heat pump operates within the same temperature range, what is the coefficient of performance of the heat pump?
4
Air enters a compressor at 27°C. The pressure ratio of the compressor is 4. If cp = 1 kJ/kg-K, k = 1.4, and the compressor efficiency is 80%, what is the actual compressor work required?
182 kJ/kg
Which equation defines the coefficient of performance (COP) of a refrigerator?
COP = Refrigeration effect/Work input
What improves the efficiency of a refrigeration system?
Increase evaporator temperature
What causes slugging in a compressor?
Liquid refrigerant entering suction
What is the purpose of a suction accumulator?
Prevent liquid from entering compressor
Which component compresses the refrigerant in VCRS?
Compressor
What does TXV stand for?
Thermostatic expansion valve
What type of ice is used in the fish industry that requires portability?
Flake
What material is used in ammonia service valves?
Stainless steel
Which type of compressor is widely used in small refrigerators?
Hermetic reciprocating compressor
What type of compressor is used in large refrigeration plants?
Centrifugal compressor
Which refrigerant is eco-friendly and has zero ODP?
R134a
Which natural refrigerant is commonly used in food preservation?
Ammonia
Which refrigerant is flammable but eco-friendly?
R600a (isobutane)
Which factor contributes to latent heat load in cooling load?
Moisture in infiltration air
What does CLTD stand for in cooling load calculations?
Cooling Load Temperature Difference
Which method uses CLTD and CLF to calculate cooling load?
ASHRAE method
Which load results from outside air intentionally supplied indoors?
Ventilation load
Which factor reduces cooling load in building design?
Insulation
Which is the cooling load due to food products stored?
Product load
What does ETD stand for?
Equivalent Temperature Difference
Which method estimates infiltration by number of air changes per hour?
Air change method
Which factor is critical in designing air conditioning for auditoriums?
Occupancy load
Which factor determines the cooling load in cold storages for vegetables?
Respiration load
Which factor reduces respiration load in cold storages?
Lower temperature
What is aseptic packaging?
Sterile packaging process
Which type of ice is commonly produced in traditional ice plants?
Block ice
Which load occurs when doors of cold storage are opened frequently?
Infiltration load
Which refrigerant is commonly used in large ice rinks?
Ammonia (NH3)
Which factor reduces infiltration load in cold storages?
Air locks and vestibules
Refrigerant pipe systems are constructed of pipe for freons.
copper
Which flooring prevents moisture migration into cold storage slabs?
Vapor barrier flooring
Which type of ice is produced continuously and has hollow cylindrical shape?
Tube ice
What is the purpose of the condenser in a refrigeration system?
to cool hot refrigerant vapor
Which insulation is widely used in rink floors?
Polystyrene foam
Which factor prevents moisture penetration in cold storage walls?
Vapor barriers
Which compressor type is best suited for large industrial refrigeration plants?
Screw or centrifugal compressor
Which expansion device automatically adjusts refrigerant flow to match load?
Thermostatic expansion valve
Which expansion device is most common in small domestic refrigerators?
Capillary tube
Which refrigerant is classified as A1 (low toxicity, low flammability)?
R134a
Which factor reduces condenser size requirements?
Lower condensing temperature
Which type of condenser is preferred in regions with water scarcity?
Air-cooled condenser
Which property of refrigerants is critical for safety classification?
Flammability and toxicity
Which compressor type is compact and widely used in residential and commercial air-conditioning?
Scroll compressor
Which expansion device offers highest precision in large modern systems?
Electronic expansion valve (EEV)
Which device is commonly used to prevent short cycling of compressors?
Time delay relay
Which device prevents refrigerant migration during compressor off-cycle?
Crankcase heater
Which device is used for measuring relative humidity in cold storage?
Hygrometer
Which instrument is essential for measuring airflow across evaporator coils?
Anemometer
Which device prevents compressor startup during low oil differential pressure?
Oil safety switch
Which device prevents system start if condenser water flow is insufficient?
Flow switch interlock
Which instrument is used to measure suction and discharge line current simultaneously?
Clamp-on ammeter
Which instrument is used to measure the temperature of refrigerant lines?
Thermocouple
Which control device regulates refrigerant flow into evaporators?
Expansion valve
A thermostat in a refrigeration system primarily functions to:
Maintain desired temperature
In a refrigeration plant, what happens to the compressor power input when the condenser temperature increases?
Increases
For a vapor compression refrigeration system used in ice production, the condensing temperature for achieving higher COP should:
Be much lower than the critical temperature of the refrigerant
Periodic defrosting is necessary in domestic reirigerators because frosting:
Reduces heat transfer rate
When the lower temperature limit is fixed, the COP of a refrigeration machine can be improved by:
Lowering condenser temperature
In a vapor compression refrigeration system, what is the primary purpose of a liquid-to-suction heat exchanger?
Subcool the liquid refrigerant leaving the condenser
Why is air cooling commonly used for Freon compressors while water jacketing is preferred for ammonia compressors?
Because ammonia has a higher latent heat than Freon
A desirable refrigerant should possess which of the following properties?
Large latent heat of vaporization and low operating pressures
Which of the following refrigerants contributes the most to ozone depletion in the stratosphere?
Fluorine
In milk chilling plants, which of the following is commonly used as the secondary refrigerant?
Brine
Leakage in a Freon-based refrigeration system is commonly detected using a:
Oxy-acetylene torch
Which of the following statements does NOT apply to the volumetric efficiency of a reciprocating air compressor?
It decreases with increase in inlet temperature