Vocabulary practice flashcards covering lightning protection fundamentals, system components, earthing arrangements, risk assessment principles, and Irish and European compliance standards (I.S. EN 62305 and ET 101).

Lightning Protection System (LPS)
A complete system comprising external components (air terminals, roof conductors, down conductors, and earth rods) and internal components (surge protection devices and equipotential bonding) designed to intercept a strike and safely conduct its electrical energy to the earth.
Air Termination Network
The strike point component positioned at the highest points, edges, and corners of a structure to capture lightning before it hits the building, consisting of air rods, finials, stretched wires, or mesh conductors.
Roof Conductor
Bare copper or aluminium tape installed on flat or pitched roofs that links individual air terminals together and provides the initial path for lightning current toward down conductors.
Down Conductor
A low-impedance vertical cable or tape running straight from the roof system to the ground with minimal bends (bend radius ≥200mm) to safely convey lightning current down a building's side.
Equipotential Bonding Conductor
A conductive cable (minimum cross-section 16mm2 copper or equivalent) that permanently interconnects structural metalwork, incoming pipes, and electrical services to eliminate dangerous potential differences and prevent internal side-flashes.
Test Point (Test Joint)
A bolted clamp within an accessible enclosure positioned 1m to 1.5m above ground level on each down conductor, allowing disconnection to measure individual earth electrode resistance independently.
Earth Termination System (ETS)
The network of buried metal components, including rods, plates, or buried conductors, that safely disperses lightning discharge energy into the general mass of the soil.
Target Earth Resistance
The maximum recommended overall electrical resistance to earth for an effective lightning protection system under I.S. EN 62305, specified as ≤10Ω.

Earth Termination Arrangements (Types A, B, and C)
The three earthing configurations recognized under I.S. EN 62305: Type A uses discrete vertical rods or horizontal radial strips; Type B uses a continuous buried ring conductor around the structure; Type C (Foundation Earth) utilizes the concrete-encased steel reinforcement in building footings.
Type A Earth Arrangement
An earthing arrangement employing vertical earth rods driven vertically to depths of 2.4m or more, or horizontal strips driven at the base of each individual down conductor.
Type B Earth Arrangement (Ring Earth)
A continuous loop conductor buried in soil around the perimeter of a building in contact with the ground for at least 80% of its length to promote uniform current dispersion and minimize step voltage.
Type C Foundation Earth Electrode
A grounding arrangement embedded directly within the concrete foundations using reinforced steel rebar to achieve permanent, highly conductive contact with the ground.
Plate Earth Electrode
A solid copper plate measuring 600×600×3mm buried at a minimum depth of 600mm, utilized where rocky terrain prevents the vertical driving of standard earth rods.

Reference Earth Electrode
An auxiliary earth electrode placed away from the primary grounding network used specifically during periodic testing to provide a stable, isolated reference point for verifying the system's 10Ω earth resistance.
Surge Protection Device (SPD)
An internal device fitted at main distribution panels and sub-boards that detects transient overvoltages and diverts electrical surges safely to ground, shielding sensitive electronics.

Lightning Protection Zones (LPZ)
A zoned risk hierarchy defined by I.S. EN 62305: LPZ 0 is the unshielded exterior vulnerable to direct strikes; LPZ 1 is an interior zone attenuated by external LPS and main SPDs; LPZ 2 is a further sheltered internal area housing sensitive computing or lab equipment.

Zone of Protection (Protective Angle Method)
The cone-shaped volume of three-dimensional space projected beneath an elevated air termination rod (often evaluated using a 45∘ angle) within which objects and building elements are protected from direct lightning impact.
Rolling Sphere Method
A standard geometric calculation technique under I.S. EN 62305 where a sphere of defined radius is rolled across a structure to map out the external boundaries and areas vulnerable to lightning contact.
Franklin Rod
A solid metal pointed rod mounted at roof peaks and elevated building projections to serve as a designated, low-resistance interception point for lightning strikes.
Meshed Conductor System
A rooftop grid network of horizontal bare conductors (spanning dimensions such as 5×5m for LPL I up to 20×20m for LPL IV) ideal for protecting expansive flat or complex roof profiles.
Side-Flashing
An uncontrolled electrical discharge or spark jumping across an air gap between an energized lightning conductor and nearby unbonded metal piping, frames, or human occupants.
Separation Distance (s)
The calculated physical space required between external lightning protection conductors and internal metallic services or wiring to prevent hazardous arcing and side-flashing inside a structure.
Bimetallic Connector
A specialized mechanical connection fitting designed to join dissimilar metals, such as copper and aluminium, without triggering galvanic corrosion.
Thermal Effect of Lightning
The extreme generation of heat resulting from high lightning currents passing through resistance, reaching temperatures as high as 30,000∘C and potentially melting metals or igniting structural materials.
Mechanical Effect of Lightning
The explosive shock waves caused by the rapid expansion of superheated air and moisture vaporization during a strike, capable of fracturing concrete, splitting masonry, and dislodging roof tiles.
Touch Voltage
The dangerous electrical potential difference that can bridge between a person's hand contacting a conductive surface or down conductor and their feet on the ground during a lightning discharge.
Step Voltage
The hazardous voltage gradient created across the earth's surface between the two feet of a person standing or walking near a dispersing earth electrode during a lightning strike.
I.S. EN 62305
The governing European and Irish engineering standard series establishing rules for risk assessment, design, installation, testing, and maintenance of lightning protection systems.
ET 101
The National Rules for Electrical Installations in Ireland requiring that all new building installations include surge protection devices at the main distribution board.
Lightning Flash Density in Ireland
The average rate of annual lightning strikes in Ireland, which typically ranges from 0.5 to 1strike/km2/year.

LPS Design Process
The standardized four-stage workflow for lightning protection engineering consisting of: 1. Risk Assessment, 2. System Selection, 3. Material Sizing, and 4. Compliance Check with Irish Standards.
Class I LPS Testing Frequency
The mandatory inspection and maintenance schedule for high-risk installations (such as hospitals and fuel depots), requiring full visual inspection and electrical testing every year.
Class II LPS Testing Frequency
The inspection and maintenance schedule for medium-risk commercial buildings, requiring a visual check every year and full electrical testing every 2years.
Class III LPS Testing Frequency
The maintenance interval for lower-risk installations (such as residential dwellings), requiring a visual inspection every 2years and full electrical testing every 3years.