Description and Tags

Vocabulary practice flashcards covering lightning protection fundamentals, system components, earthing arrangements, risk assessment principles, and Irish and European compliance standards (I.S. EN 62305 and ET 101).

34 Terms

1
New cards
<p>Lightning Protection System (LPS)</p>

Lightning Protection System (LPS)

A complete system comprising external components (air terminals, roof conductors, down conductors, and earth rods) and internal components (surge protection devices and equipotential bonding) designed to intercept a strike and safely conduct its electrical energy to the earth.

2
New cards

Air Termination Network

The strike point component positioned at the highest points, edges, and corners of a structure to capture lightning before it hits the building, consisting of air rods, finials, stretched wires, or mesh conductors.

3
New cards

Roof Conductor

Bare copper or aluminium tape installed on flat or pitched roofs that links individual air terminals together and provides the initial path for lightning current toward down conductors.

4
New cards

Down Conductor

A low-impedance vertical cable or tape running straight from the roof system to the ground with minimal bends (bend radius ≥200 mm\ge 200\,\text{mm}) to safely convey lightning current down a building's side.

5
New cards

Equipotential Bonding Conductor

A conductive cable (minimum cross-section 16 mm216\,\text{mm}^2 copper or equivalent) that permanently interconnects structural metalwork, incoming pipes, and electrical services to eliminate dangerous potential differences and prevent internal side-flashes.

6
New cards

Test Point (Test Joint)

A bolted clamp within an accessible enclosure positioned 1 m1\,\text{m} to 1.5 m1.5\,\text{m} above ground level on each down conductor, allowing disconnection to measure individual earth electrode resistance independently.

7
New cards

Earth Termination System (ETS)

The network of buried metal components, including rods, plates, or buried conductors, that safely disperses lightning discharge energy into the general mass of the soil.

8
New cards

Target Earth Resistance

The maximum recommended overall electrical resistance to earth for an effective lightning protection system under I.S. EN 62305, specified as ≤10 Ω\le 10\,\Omega.

9
New cards
<p>Earth Termination Arrangements (Types A, B, and C)</p>

Earth Termination Arrangements (Types A, B, and C)

The three earthing configurations recognized under I.S. EN 62305: Type A uses discrete vertical rods or horizontal radial strips; Type B uses a continuous buried ring conductor around the structure; Type C (Foundation Earth) utilizes the concrete-encased steel reinforcement in building footings.

10
New cards

Type A Earth Arrangement

An earthing arrangement employing vertical earth rods driven vertically to depths of 2.4 m2.4\,\text{m} or more, or horizontal strips driven at the base of each individual down conductor.

11
New cards

Type B Earth Arrangement (Ring Earth)

A continuous loop conductor buried in soil around the perimeter of a building in contact with the ground for at least 80%80\% of its length to promote uniform current dispersion and minimize step voltage.

12
New cards

Type C Foundation Earth Electrode

A grounding arrangement embedded directly within the concrete foundations using reinforced steel rebar to achieve permanent, highly conductive contact with the ground.

13
New cards

Plate Earth Electrode

A solid copper plate measuring 600×600×3 mm600 \times 600 \times 3\,\text{mm} buried at a minimum depth of 600 mm600\,\text{mm}, utilized where rocky terrain prevents the vertical driving of standard earth rods.

14
New cards
<p>Reference Earth Electrode</p>

Reference Earth Electrode

An auxiliary earth electrode placed away from the primary grounding network used specifically during periodic testing to provide a stable, isolated reference point for verifying the system's 10 Ω10\,\Omega earth resistance.

15
New cards

Surge Protection Device (SPD)

An internal device fitted at main distribution panels and sub-boards that detects transient overvoltages and diverts electrical surges safely to ground, shielding sensitive electronics.

16
New cards
<p>Lightning Protection Zones (LPZ)</p>

Lightning Protection Zones (LPZ)

A zoned risk hierarchy defined by I.S. EN 62305: LPZ 0 is the unshielded exterior vulnerable to direct strikes; LPZ 1 is an interior zone attenuated by external LPS and main SPDs; LPZ 2 is a further sheltered internal area housing sensitive computing or lab equipment.

17
New cards
<p>Zone of Protection (Protective Angle Method)</p>

Zone of Protection (Protective Angle Method)

The cone-shaped volume of three-dimensional space projected beneath an elevated air termination rod (often evaluated using a 45∘45^{\circ} angle) within which objects and building elements are protected from direct lightning impact.

18
New cards

Rolling Sphere Method

A standard geometric calculation technique under I.S. EN 62305 where a sphere of defined radius is rolled across a structure to map out the external boundaries and areas vulnerable to lightning contact.

19
New cards

Franklin Rod

A solid metal pointed rod mounted at roof peaks and elevated building projections to serve as a designated, low-resistance interception point for lightning strikes.

20
New cards

Meshed Conductor System

A rooftop grid network of horizontal bare conductors (spanning dimensions such as 5×5 m5 \times 5\,\text{m} for LPL I up to 20×20 m20 \times 20\,\text{m} for LPL IV) ideal for protecting expansive flat or complex roof profiles.

21
New cards

Side-Flashing

An uncontrolled electrical discharge or spark jumping across an air gap between an energized lightning conductor and nearby unbonded metal piping, frames, or human occupants.

22
New cards

Separation Distance (s)

The calculated physical space required between external lightning protection conductors and internal metallic services or wiring to prevent hazardous arcing and side-flashing inside a structure.

23
New cards

Bimetallic Connector

A specialized mechanical connection fitting designed to join dissimilar metals, such as copper and aluminium, without triggering galvanic corrosion.

24
New cards

Thermal Effect of Lightning

The extreme generation of heat resulting from high lightning currents passing through resistance, reaching temperatures as high as 30,000 ∘C30{,}000\,^{\circ}\text{C} and potentially melting metals or igniting structural materials.

25
New cards

Mechanical Effect of Lightning

The explosive shock waves caused by the rapid expansion of superheated air and moisture vaporization during a strike, capable of fracturing concrete, splitting masonry, and dislodging roof tiles.

26
New cards

Touch Voltage

The dangerous electrical potential difference that can bridge between a person's hand contacting a conductive surface or down conductor and their feet on the ground during a lightning discharge.

27
New cards

Step Voltage

The hazardous voltage gradient created across the earth's surface between the two feet of a person standing or walking near a dispersing earth electrode during a lightning strike.

28
New cards

I.S. EN 62305

The governing European and Irish engineering standard series establishing rules for risk assessment, design, installation, testing, and maintenance of lightning protection systems.

29
New cards

ET 101

The National Rules for Electrical Installations in Ireland requiring that all new building installations include surge protection devices at the main distribution board.

30
New cards

Lightning Flash Density in Ireland

The average rate of annual lightning strikes in Ireland, which typically ranges from 0.50.5 to 1 strike/km2/year1\,\text{strike/km}^2/\text{year}.

31
New cards
<p>LPS Design Process</p>

LPS Design Process

The standardized four-stage workflow for lightning protection engineering consisting of: 1. Risk Assessment, 2. System Selection, 3. Material Sizing, and 4. Compliance Check with Irish Standards.

32
New cards

Class I LPS Testing Frequency

The mandatory inspection and maintenance schedule for high-risk installations (such as hospitals and fuel depots), requiring full visual inspection and electrical testing every year.

33
New cards

Class II LPS Testing Frequency

The inspection and maintenance schedule for medium-risk commercial buildings, requiring a visual check every year and full electrical testing every 2 years2\,\text{years}.

34
New cards

Class III LPS Testing Frequency

The maintenance interval for lower-risk installations (such as residential dwellings), requiring a visual inspection every 2 years2\,\text{years} and full electrical testing every 3 years3\,\text{years}.