Comprehensive practice flashcards covering Phase 6 Fire Alarm Systems and Craft Theory, including system architecture, detector principles, Irish Standard IS 3218 compliance, wiring regulations, and maintenance procedures.

38 Terms

1
New cards

What was the primary operational disadvantage of an early normally open fire alarm system?

A broken conductor or connection would render all detector contacts located beyond the break completely inoperative without triggering a fault warning at the panel.

2
New cards

What were the major operational disadvantages of an early normally closed fire alarm circuit?

A short circuit between conductors remained undetected and disabled downstream devices, while an open-circuit break caused an alarm with no discrimination between a true fire alarm and a wiring fault.

3
New cards

What is the typical resistance value of the end-of-line (EOL) resistor in a conventional fire alarm circuit, and what is its purpose?

It is typically 6800 Ω6800\,\Omega (6.8 kΩ6.8\,\text{k}\Omega). Connected across the terminals of the final device on a radial circuit, it allows the control panel to pass a small supervisory current to continuously monitor the wiring for open-circuit and short-circuit faults.

4
New cards

Why is a 470 Ω470\,\Omega to 680 Ω680\,\Omega resistor connected in series within a manual call point?

It creates a partial short circuit when operated, allowing the control panel to differentiate between an intentional manual call point activation and a dead short-circuit wiring fault.

5
New cards
<p>Based on the addressable loop diagram, what is the operational function of the isolator modules when a short circuit occurs?</p>

Based on the addressable loop diagram, what is the operational function of the isolator modules when a short circuit occurs?

The isolators immediately bounding the short circuit latch open to disconnect the faulty wiring section, allowing the panel to maintain bi-directional communication with all remaining devices as two separate radial circuits.

6
New cards
<p>What is the function of the reverse-biased diodes connected in series with the alarm sounders in this monitored circuit?</p>

What is the function of the reverse-biased diodes connected in series with the alarm sounders in this monitored circuit?

During normal standby monitoring, reverse polarity (24 V DC24\,\text{V DC}) is applied; the diodes block fault monitoring current from activating the sounders while current flows through the 6.8 kΩ6.8\,\text{k}\Omega EOL resistor. In alarm mode, polarity reverses at the panel, forward-biasing the diodes to energize the sounders.

7
New cards

How does a conventional fire alarm panel detect an open-circuit fault on a detection zone circuit?

In normal standby, a steady monitoring current flows through the circuit and the end-of-line (EOL) resistor. If a wire breaks or a connection loosens, circuit current drops to 0 A0\,\text{A}, causing the panel to indicate an open-circuit fault.

8
New cards

According to Irish Standard IS 3218, what do fire alarm system categories L, P, and M define?

Category L defines automatic fire detection systems intended for the protection of life. Category P defines automatic fire detection systems intended for the protection of property. Category M defines manual systems relying on call points without automatic fire detectors.

9
New cards

How are Category L life protection fire alarm systems subdivided from L1 through L4?

L1 provides automatic detection throughout every space of the building; L2 provides detection in escape routes, adjoining rooms, and defined high-risk/special areas; L3 provides detection in escape routes and rooms opening onto escape routes; L4 provides detection in escape routes only.

10
New cards

What are the minimum, sleeping area, and maximum permitted sound levels for fire alarm sounders under IS 3218?

The general minimum is 65 dB65\,\text{dB} (or 5 dB5\,\text{dB} above background noise persisting longer than 30 s30\,\text{s}, whichever is greater); the minimum at the bedhead to awaken sleeping persons with doors closed is 75 dB75\,\text{dB}; the maximum permitted sound level anywhere is 118 dB118\,\text{dB}.

11
New cards

What is the minimum number of sounder circuits required to be connected to a building's fire alarm control panel?

At least 22 sounder circuits must be provided so that audible warning capability is maintained even if one circuit or sounder fails.

12
New cards

What are the maximum permitted floor area and visual search distance for a single detection zone under IS 3218?

The floor area of a single detection zone must not exceed 2000 m22000\,\text{m}^2, and the maximum distance a searcher must travel inside the zone to visually locate the fire must not exceed 30 m30\,\text{m}.

13
New cards

Under what building size condition may a single detection zone encompass more than one storey?

A single detection zone may cover more than one storey only if the total floor area of the entire building is 300 m2300\,\text{m}^2 or less. In buildings larger than 300 m2300\,\text{m}^2, detection zones must be restricted to a single storey.

14
New cards
<p>Identify the type of smoke detector shown and explain how it detects smoke particles.</p>

Identify the type of smoke detector shown and explain how it detects smoke particles.

An optical (light-scatter) smoke detector. In clean air, the infrared beam from the LED travels into a light trap and misses the photodiode. When smoke enters the dark chamber, smoke particles scatter the light onto the photodiode, which signals the processing circuitry to initiate an alarm once a threshold is met.

15
New cards

Contrast the detection strengths of optical and ionisation smoke detectors regarding fire profiles.

Optical detectors respond faster to large-particle, visible smoke produced by slow-smouldering fires (such as upholstery, foam, and overheated cables). Ionisation detectors respond faster to tiny, invisible particles produced by high-energy, fast-flaming fires (such as flammable liquids and paper).

16
New cards
<p>Why must smoke detectors never be installed within the 'dead air zone' illustrated along the ceiling-wall seam?</p>

Why must smoke detectors never be installed within the 'dead air zone' illustrated along the ceiling-wall seam?

Thermal buoyancy drives rising smoke along the ceiling, but stagnant pockets of air in corners create an air cushion extending 4 inches4\,\text{inches} (100 mm100\,\text{mm}) horizontally and vertically from the seam, preventing smoke from circulating into the detector chamber during the early stages of a fire.

17
New cards
<p>Describe the construction, mounting height, and travel distance parameters for the manual call point shown.</p>

Describe the construction, mounting height, and travel distance parameters for the manual call point shown.

It consists of a red enclosure housing a spring-loaded switch held by a breakable glass or collapsible plastic front; breaking the element releases the switch to signal the panel. It is installed at exits and along escape routes at a height of 0.9 m0.9\,\text{m} to 1.2 m1.2\,\text{m} (or 1.4 m1.4\,\text{m} in older craft practice) above floor level, with a maximum travel distance of 30 m30\,\text{m} (45 m45\,\text{m} in commercial practice).

18
New cards

Distinguish between fixed temperature and rate-of-rise heat detectors, and state where rate-of-rise is unsuitable.

Fixed temperature detectors activate when the sensing element reaches a preset threshold (such as 60∘C60^\circ\text{C}, 65∘C65^\circ\text{C}, or 90∘C90^\circ\text{C}). Rate-of-rise detectors activate when the ambient temperature rises abnormally fast. Rate-of-rise sensors are unsuitable in commercial kitchens and boiler rooms where normal operations cause sudden temperature spikes.

19
New cards

What are the standard coverage areas and spacing rules for smoke and heat detectors on a flat ceiling?

Smoke detectors cover up to 100 m2100\,\text{m}^2 (7.5 m7.5\,\text{m} radius, spaced up to 12 m12\,\text{m} between detectors and 6 m6\,\text{m} from walls). Heat detectors cover up to 50 m250\,\text{m}^2 (5.3 m5.3\,\text{m} radius, spaced up to 10 m10\,\text{m} between detectors and 5 m5\,\text{m} from walls).

20
New cards

What spacing modification applies to smoke detectors in corridors less than 2 m2\,\text{m} wide?

Because radial coverage overlap is not required in narrow corridors, horizontal spacing between smoke detectors may be extended up to 15 m15\,\text{m}, with a maximum distance of 7.5 m7.5\,\text{m} to any end wall. Heat detectors are not recommended in escape corridors.

21
New cards

At what vertical distance below a flat ceiling must the sensing elements of smoke and heat detectors be placed?

Heat detector sensing elements must be positioned between 25 mm25\,\text{mm} and 150 mm150\,\text{mm} below the ceiling. Smoke detector sensing elements must be positioned between 25 mm25\,\text{mm} and 600 mm600\,\text{mm} below the ceiling.

22
New cards

State three mandatory criteria for the installation location of a main fire alarm control panel.

  1. Sited in an area of low fire risk; 2. Located on the ground floor near the primary entrance or access point designated for the fire brigade; 3. Situated in a well-lit area common and accessible to all building services, with a zone plan and an audible sounder adjacent to it.
23
New cards

What are the primary and standby power supply requirements for a fire alarm control panel?

The primary supply must be a dedicated clean 230 V AC230\,\text{V AC}, 50 Hz50\,\text{Hz} single-phase mains supply transformed and rectified to 24 V DC24\,\text{V DC}. Standby power must be provided by rechargeable batteries (lead-acid or nickel-cadmium, minimum 4-year4\text{-year} design life; automotive batteries banned) capable of sustaining the system on standby for 24 hours24\,\text{hours} and then powering full alarm load for at least 30 minutes30\,\text{minutes}.

24
New cards

Outline the routine fire alarm testing tasks for daily, weekly, quarterly, and annual intervals.

Daily: Verify the panel indicates normal operation and check that recorded faults received attention. Weekly: Operate a different call point or detector each week, verify sounders operate, reset, inspect battery connections, and log the test. Quarterly: Review the logbook, examine batteries, test sounders with a trigger device, simulate fault conditions, and check for structural alterations affecting coverage. Annually: Complete all quarterly checks, test every detector in situ, and inspect all cable fittings and equipment for damage and security.

25
New cards

What fire resistance standards and reaction-to-fire classifications must fire alarm cables meet?

Cables must be Low Smoke Zero Halogen (LSOH) and rated at least Class Dca-s2,d2,a2\text{D}_{\text{ca}}\text{-s2,d2,a2}. They must meet standard PH30 (30 minutes30\,\text{minutes} fire resistance under EN 50200) as a minimum, or enhanced PH120 (120 minutes120\,\text{minutes} under EN 50200 and BS 8434-2) for high-risk applications such as buildings over 30 m30\,\text{m} in height, phased evacuation, or critical circuits traversing occupied areas.

26
New cards

State four approved methods for segregating fire alarm wiring from low-voltage (LV) electrical circuits.

  1. Installation in separate conduit, ducting, trunking, or cable tray; 2. Enclosure behind rigid, continuous non-combustible partitions within multi-compartment trunking; 3. Use of continuous metallic sheathed cable such as mineral-insulated copper-clad (MICC); 4. Maintaining an air spacing of at least 300 mm300\,\text{mm} along parallel cable runs, which may be reduced to 15 mm15\,\text{mm} at 90∘90^\circ crossovers.
27
New cards

Why must the feed and return paths of an addressable detector loop follow separate physical routes?

If the outgoing and return legs share the same cable or route, a single mechanical impact or fire incident could sever both conductors simultaneously, bypassing loop isolator protection and disabling the entire loop.

28
New cards

What precautions are required when fire alarm wiring systems penetrate fire compartment walls or floors?

Openings must be internally and externally sealed to reinstate the fire resistance rating of the penetrated construction element using compliant fire-stopping materials. Cable supports must be installed within 750 mm750\,\text{mm} of the seal so that no mechanical strain transfers to the seal during a fire.

29
New cards

State the key requirements for a firefighter's switch installed for high-voltage discharge-lighting circuits.

It must be coloured red, labelled 'Fireman's Switch', clearly indicate ON and OFF positions, incorporate a lock to prevent accidental return to ON, and be mounted in a conspicuous position no more than 2.75 m2.75\,\text{m} above the ground or floor.

30
New cards

What fire safety precaution is required when electrical equipment contains flammable liquid exceeding 25 litres25\,\text{litres}?

Under IS 10101 Clause 421.5, a retention pit to contain liquid leakage or installation within an adequately fire-resistant chamber equipped with sills and ventilated exclusively to the external atmosphere must be provided.

31
New cards

How do fire door release circuits differ from evacuation door release circuits during an alarm activation?

Fire door release circuits de-energize hold-open magnets, releasing self-closing fire doors to prevent smoke and fire spread. Evacuation door release circuits de-energize electronic security locks, allowing escape doors to open immediately for emergency egress.

32
New cards

What is a backdraft, and how does the standard door-checking procedure mitigate this risk during evacuation?

A backdraft is an explosive deflagration caused when fresh oxygen is suddenly introduced to an oxygen-depleted, superheated space containing flammable pyrolysis gases. Touching the door with the back of the hand checks for severe heat, warning occupants not to open it and create a fatal ventilation pathway.

33
New cards

Under the Fire Safety Act 2021 in Ireland, what are the legal requirements and penalties regarding domestic smoke alarms?

Working smoke alarms must be installed on every floor of all domestic residences. Failure to comply can result in landlord/owner liability, court fines of up to €50005000, potential imprisonment, and invalidation of property insurance policies.

34
New cards

How much sound attenuation occurs when fire alarm sounders are separated from rooms by standard doors versus fire doors?

A standard single door reduces alarm sound levels by at least 20 dB20\,\text{dB}, while a solid fire door reduces sound levels by at least 30 dB30\,\text{dB}. Because of this attenuation, rooms separated from sounders by more than one closed door generally require dedicated internal sounders.

35
New cards

Name four types of fire alarm warning devices and state a suitable application for each.

  1. Bell: Offices and schools; 2. Horn: Factories; 3. Siren: Noisy factories or heavy engineering workshops (100–105 dB100\text{--}105\,\text{dB}); 4. Warbler: Mines, quarries, or loud industrial sites; 5. Strobe: Noisy areas where workers wear ear protection or buildings occupied by the hard of hearing; 6. Voice Evacuation: Airports, hotels, and arenas.
36
New cards

What is the correct four-step operational sequence of a fire alarm system during an emergency?

  1. Sensor detects physical fire indicators (smoke or heat) or a call point is activated; 2. An electrical input signal is transmitted to the control panel; 3. Control panel processes the signal and activates warning outputs (sounders, strobes, relays); 4. Occupants receive notification and execute safe evacuation.
37
New cards
<p>Explain how the ionisation chamber shown detects the outbreak of a fire.</p>

Explain how the ionisation chamber shown detects the outbreak of a fire.

A radioactive source ionises air inside the chamber, establishing a steady ion flow and electrical current between charged plates. When smoke enters, smoke particles attach to ions and neutralize them, reducing current flow; the control circuitry detects this drop in current and triggers a fire alarm.

38
New cards

What is the purpose of a Main Isolating Switch in emergency electrical installations, and where must it be sited?

It provides complete disconnection of the electrical supply to an installation in the event of a fire (either directly or via a remote trip mechanism). It must be prominently displayed, clearly marked, and positioned at the entrance designated for fire service access.