1/83
Comprehensive review flashcards covering electrical calculations, NEC code requirements, motor controls, and pool wiring from the Michigan Electrical Journeyman Study Guide.
What is the minimum size THHN copper conductor required for six conductors in a raceway connected to 75∘C rated breakers, where each wire carries a 70-amp load?
#4 AWG. Under Table 310.15(C)(1), the 4 to 6 current-carrying conductor adjustment factor is 80%. Calculating 70 A÷0.80=87.5 A; from the 90∘C column of Table 310.16, #4 THHN is rated at 95 A (95 A×0.80=76 A).
According to NEC Ref: 410.116(B), thermal insulation shall not be installed within how many inches of recessed fixtures?
3 inches
A 1-inch conduit contains three 3-wire circuits of #10 TW conductors (six current-carrying phase conductors total). What is the maximum ampacity of each phase conductor?
24 amperes. From Ref: 310.15(B)(5)(a),(b),(c), #10 TW has a base rating of 30 A. Applying an 80% adjustment factor gives 30 A×0.80=24 A.
According to Ohm's Law, what is the power rating of a device that consumes 14.5 amperes on a 230-volt circuit?
3335 watts (P=I×E=14.5 A×230 V=3335 W)
How many amperes does a 208 V, 3-phase heater drawing 3,598 watts consume?
10 amperes (I=V×1.732P=208 V×1.7323598 W≈10 A)
Under NEC Ref: 680.23(A)(5), an underwater pool light fixture shall be installed at least how many inches below the normal water level?
18 inches

Based on the pool layout diagram, why is a general-purpose receptacle prohibited on the metal fence directly south of the pool?
Because the metal fence is located only 3’−9” from the pool wall, and NEC Ref: 680.22(A)(1) requires general-purpose receptacles to be located not less than 6 ft from the inside walls of the pool.
According to NEC Ref: 680.24(A)(2)(a), a junction box for a 120 V wet-niche swimming pool fixture shall be installed at least how many inches above the ground?
4 inches (and not less than 8 inches above maximum water level)
According to NEC Ref: 680.22(A)(1), what type of protection must be provided for a pool pump motor receptacle installed on the south side of a dwelling unit?
GFCI protection
According to NEC Ref: 680.26(B)(7)(1), a metal fence installed within how many feet of the inside wall of a swimming pool must be bonded?
5 feet
Under NEC Ref: 680.23(B)(2)(a), what type of raceway is required for the feed to an underwater wet-niche fixture?
Rigid brass conduit (or approved nonmetallic conduit / rigid metal conduit of brass)
According to NEC Ref: 210.63, a 15- or 20-amp service receptacle must be located within how many feet of rooftop air conditioning equipment?
25 feet
What is the maximum overcurrent protection rating permitted for eight current-carrying #12 THHN conductors in a 21” conduit?
20 amps (Ref: 240.4(D)(5), after applying the 70% derating factor from 30 A×0.70=21 A)
According to NEC Ref: 250.20(B)(1), an AC system of 50 to 1,000 volts shall be grounded if the maximum voltage to ground on the ungrounded conductors does not exceed how many volts?
150 volts
A 10 horsepower, 230 volt, 3-phase motor has a full-load current of 28 A. What is the maximum standard rating inverse-time circuit breaker permitted for branch-circuit short-circuit and ground-fault protection?
70 amps. Under Table 430.52(C)(1), an inverse time breaker is sized at 250% of full-load current: 28 A×2.50=70 A.
According to NEC Ref: 240.53(B), why are Type "S" adapters installed into Edison-base fuseholders?
To limit the size (ampere rating) of the fuse to be installed and prevent overfusing
According to NEC Ref: 210.11(C)(2), what is the minimum required ampere rating for a dwelling unit laundry branch circuit?
20 amps
In a commercial building, what is the minimum size underground copper service-entrance conductor (THWN) for a 120/240-volt, single-phase, 200-amp service?
3/0 THWN copper (Ref: Table 310.15(B)(16) / Table 310.16 at 75∘C)
According to NEC Ref: 230.79(C), what is the minimum service disconnect rating for a one-family dwelling?
100 amps
According to NEC Ref: 340.12(1), which cable type is not permitted to be used as service-entrance cable?
Type UF cable
A 3-phase kiln rated at 4,750 watts and 208 volts draws how many amperes?
13.18 amperes (≈13.2 A), calculated as I=208 V×1.734750 W=13.18 A.
According to NEC Ref: 300.5(D)(4), direct-burial cables emerging from the ground and subject to physical damage shall be installed in what type of raceway?
Rigid metal conduit (RMC), intermediate metal conduit (IMC), or Schedule 80 PVC conduit
According to NEC Ref: 250.36, a high-impedance grounded neutral system is limited to systems operating at what minimum line-to-line voltage?
480 volts or above (operating at 480 to 1000 volts)
When the temperature changes across a span from −15∘F to 105∘F (120∘F span), what is the thermal expansion for 100 feet of rigid nonmetallic conduit?
4.87 inches (Ref: Table 352.44)
According to NEC Ref: 800.179, communications cables shall have a voltage rating of not less than how many volts?
300 volts
How can the direction of rotation of a three-phase induction motor rotor be reversed?
By interchanging any two line leads

Identify the low-voltage circuit classification depicted in the transformer diagram featuring an input, a secondary of 30 volts or less, and a transformer capacity of 1000 VA or less.
Class 1 power-limited circuit
According to NEC Ref: 210.52(B)(2) Exception No. 1, which specific receptacle is permitted to be installed on a small-appliance branch circuit?
An electric clock receptacle
Under NEC Ref: 314.27(A)(2), a luminaire (light fixture) that weighs more than how many pounds shall be supported independently of the outlet box?
50 pounds
According to NEC Ref: 240.40, a disconnecting means must be provided on the supply side of cartridge fuses of any voltage where they are:
Accessible to other than qualified persons
According to NEC Ref: 422.12, central heating furnaces shall be supplied by what type of branch circuit?
An individual branch circuit
According to NEC Article 100, what is the screw called that connects the grounded neutral bar of a grounded electrical system to the service equipment enclosure?
Main bonding jumper
What is the minimum size rigid metal conduit (RMC) required for a 150-amp, 120/240-volt, 3-wire single-phase commercial service using THWN copper wire?
121 inch (Ref: Annex C Table C.9 and Table 310.16)
According to NEC Ref: 314.2, round outlet boxes shall not be used where conduits or connectors fasten to which part of the box?
The side of the box
Under NEC Ref: 422.16(B)(1), an in-sink household waste disposer (garbage disposal) may be cord-and-plug connected provided the cord is terminated with what type of plug?
A grounding-type attachment plug (grounded)
According to NEC Ref: 315.36, direct-burial conductors and cables rated above how many volts shall be shielded?
2000 volts
Under NEC Ref: 250.53(B), when two or more ground rod electrodes are installed, they shall be separated by a minimum distance of how many feet?
6 feet
According to NEC Ref: 230.24(B)(1), what is the minimum vertical clearance required for overhead service-drop conductors above pedestrian walkways?
10 feet
Under NEC Ref: 210.23(C), fixed lighting units may be supplied by a 30-amp branch circuit only if they are equipped with what type of lampholders?
Heavy-duty lampholders
According to NEC Ref: 314.27(B), floor boxes used for receptacles installed in the floor shall be:
Listed specifically for the installation (listed floor boxes)
According to NEC Ref: 210.50(C), a laundry equipment receptacle shall be installed within how many feet of the intended location of the appliance?
6 feet
Under NEC Ref: 338.10(B)(4)(b)(2), which insulated conductor type is identified and permitted for direct burial in earth?
Type USE (Underground Service Entrance)
According to NEC Ref: 240.51(A), plug fuses of the Edison-base type shall not exceed what maximum rating?
30 amperes
According to NEC Ref: Table 352.30(B), what is the maximum distance between supports for a 1-inch rigid nonmetallic conduit (PVC)?
3 feet

In the motor control ladder logic diagram, what component is labeled "B"?
The normally open (NO) Start push button
Under NEC Ref: 250.52(A)(4), what is the smallest copper conductor size permitted to be installed as an encircling ground ring electrode?
#2 AWG bare copper
Under NEC Ref: 422.11(E)(3), a single non-motor-operated electric appliance rated at 13.4 A shall have branch-circuit overcurrent protection not exceeding what percentage of the appliance rating?
150%
According to NEC Ref: 410.30(B)(1), metal poles supporting lighting luminaires must have an accessible handhole measuring not less than what dimensions?
2”×4”
Under NEC Ref: 430.109(C)(2), an AC general-use snap switch used as a controller for a motor load shall not exceed what percentage of the ampere rating of the switch?
80%
According to NEC Ref: 332.30, Mineral-Insulated (Type MI) cable must be securely supported and fastened within how many inches of a panelboard or cabinet?
72 inches (6 feet)
According to NEC Ref: 366.23(A), sheet metal auxiliary gutters shall not contain more than how many current-carrying conductors at any cross section without derating?
30 conductors
According to NEC Ref: 250.52(A)(3)(1), what are the minimum dimensions for a concrete-encased steel reinforcing bar (rebar) grounding electrode?
20 feet in length and 21 inch in diameter
What electromagnetic device consists of an iron frame, plunger, and electrical coil, and is energized to produce linear push or pull motion?
A solenoid
According to NEC Ref: 310.15(B)(16) and 110.14(C), what is the allowable ampacity of a #6 copper THHW conductor terminated in a switchboard rated at 75∘C?
65 amps
According to NEC Chapter 9, Note 4, what is the maximum permissible conductor fill percentage for a conduit nipple having a length of 24 inches or less?
60%
Under NEC Ref: 314.17(B)(2) Exception, internal cable clamps are not required in a nonmetallic box not larger than 241”×4” if Type NM cable is securely stapled within how many inches of the box?
8 inches
Under NEC Ref: 210.23(E), branch circuits larger than how many amperes are restricted to supplying only non-lighting loads?
50 amps
According to NEC Annex C, Table C.11, what is the maximum number of #6 AWG Type THW conductors permitted in a 1-inch Schedule 40 PVC conduit?
4 conductors
According to NEC Table 314.16(B)(1), how many cubic inches of box volume are required for each #10 AWG conductor in an outlet box?
2.50 cubic inches
Under NEC Ref: 310.10(G)(1), what is the smallest conductor size permitted to be connected in parallel for phase, neutral, or grounded conductors?
1/0 AWG
According to NEC Ref: 230.71(B), what is the maximum number of disconnect switches or circuit breakers permitted to disconnect a single electrical service?
6 disconnects
Under NEC Ref: 334.80, the allowable ampacity of Type NM (nonmetallic-sheathed) cable is determined using which temperature rating column in Table 310.16?
The 60∘C column
Under NEC Ref: 250.64(E)(1), when a short section of ferrous metal raceway is used to encase a grounding electrode conductor (GEC) for physical protection, to what must both ends be bonded?
To the grounding electrode conductor itself
Under NEC Ref: 220.51 and 220.60, a residential feeder supplies 75 A of electric space heating and 25 A of electric air conditioning. What is the required feeder load capacity?
75 amperes. Space heating and air conditioning are non-coincident loads; only the larger load is required to be calculated.
Under NEC Ref: 430.36, when fuses are used for motor overload protection, in what system must a fuse be inserted into the grounded conductor as well as each ungrounded conductor?
A 3-wire, 3-phase AC system with one conductor grounded (corner-grounded delta)
When is an electrical contractor permitted to conceal electrical work within walls or ceilings?
Only after obtaining official electrical inspection approval
According to NEC Ref: 210.70(A)(2)(2), which exterior door of a dwelling unit is not required to have an outdoor luminaire installed?
A vehicle garage door
According to NEC Ref: 300.9, the interior of raceways installed in wet locations above grade shall be considered what type of location?
A wet location
According to NEC Ref: 210.11(C)(1), what is the minimum number of small-appliance branch circuits required for kitchen and dining areas in a dwelling unit?
2 circuits
According to NEC Ref: 300.15(C), when a raceway is used solely for the physical protection of a multiconductor cable, what must be installed on the conduit end?
A fitting or bushing to protect the cable from abrasion
According to NEC Table 250.102(C)(1), what is the minimum size aluminum main bonding jumper for a service having one 800 kcmil aluminum conductor per phase?
250 kcmil
Under NEC Ref: 310.12(A) and 550.33(C), what is the minimum copper conductor size for a 100-amp feeder supplying a mobile home?
#4 AWG copper (100 A×0.83=83 A minimum ampacity)
Calculate the required box cubic-inch capacity for a device box containing two 12/3 NM cables with ground, one single-pole switch, and one internal cable clamp.
22.5 in3. Calculation: 6 insulated conductors (6) + ground wire (1) + device (2) + internal clamp (1) = 10 equivalent conductors. With a multiplier of 2.25 in3 per #12 conductor: 10×2.25=22.5 in3.
Four 4-inch PVC conduits are installed as service entrance, each containing four 500 kcmil THWN copper conductors (16 conductors total, 4 sets). What is the maximum overcurrent device rating?
1200 amps. Sizing: 500 kcmil THWN is rated at 380 A. Applying an 80% adjustment factor for four current-carrying conductors gives 380 A×0.80=304 A. Across four parallel runs: 304 A×4=1216 A, permitting a maximum standard rating of 1200 A.
According to NEC Ref: 250.64(B)(2), which size copper grounding electrode conductor must always be protected from physical damage by an enclosure or raceway?
#8 AWG
Under NEC Ref: 680.26(B), what is the minimum size and type of conductor required for equipotential bonding around a swimming pool?
#8 AWG solid copper
According to NEC Ref: 680.7(A), a flexible cord used to connect fixed or stationary pool equipment shall not exceed how many feet in length?
3 feet
According to NEC Ref: 690.31(G), where DC photovoltaic source or output circuits are run inside a building or structure, in what type of raceway must they be contained?
Metal raceway (such as Electrical Metallic Tubing - EMT) or metal enclosure
Under NEC Ref: 230.79, what is the minimum required rating for the service disconnecting means supplying a commercial service garage?
100 amps
Under NEC Ref: 210.52(H), dwelling unit hallways measuring how many feet or more in length require at least one receptacle outlet?
10 feet
What is the secondary full-load current available from a 150 kVA, single-phase transformer with a 120/240 V secondary voltage?
625 amperes (I=240 V150,000 VA=625 A)
According to NEC Ref: 250.52(A)(5), rod-type grounding electrodes shall have a minimum length of how many feet?
8 feet
Under NEC Ref: 625.50, the coupling means of electric vehicle supply equipment (EVSE) shall be stored not less than how many inches above the floor indoors, and how many inches above grade outdoors?
18 inches above floor level indoors, and 24 inches above grade level outdoors
Under the Michigan Skilled Trades Regulation Act 407 of 2016 (MCL 339.5717(3)), what is the maximum number of registered apprentice electricians permitted per electrical journeyman or master electrician on a job site?
No more than 3 registered apprentice electricians to 1 electrical journeyman or master electrician