Explain what a ground fault is

An unintentional electric path between source of current and grounded surface. They Occur when current is leaking somewhere, essentially electricity is escaping to ground

2
New cards

Explain all of the factors that determine the amount of ground fault current capable of being generated in the event of a fault.

Voltage, conductor size, integrity of connection, grounding scheme of the separately derived grounding system are the factors. Amount of resistance between the fault and the transformer. Size of transformer. Size of the conductors going to fault.

3
New cards

Explain the difference between an arc fault and a bolted fault

An arc fault is an intermittent air gap fault. Jumps through the air.

A bolted fault is a continuous connection across phases-(For example, a hand tool forgotten in MCC bucket that is bridged across conductor phases). Fault that goes through conductive material.

4
New cards

Explain the benefits and disadvantages of an ungrounded system. Indicate the locations in your department where this type of system grounding is used.

Advantage - The first ground fault turns the system into a solidly grounded system.

Disadvantage – Hazardous, unstable voltages, dangerous

No ungrounded in this facility



5
New cards

Explain the benefits and disadvantages of a solidy grounded system. Indicate the locations in your department where this type of system grounding is used.

Solidly Grounded

Advantage – Finding faults is easy, stable voltages.

Disadvantage – High ground fault currents can potentially damage equipment.

(Our lighting transformers are grounded this way).

Lighting panel, power panel, phase to neutral loads.

6
New cards

Explain the benefits and disadvantages of a high resistance grounded system. Indicate the locations in your department where this type of system grounding is used.

High-Resistance

Advantage – Can continue to run equipment with existing ground fault.

Disadvantage – Everyone that works on it must be trained and qualified.

(2nd fault on that substation transformer will trip substation breaker, and will stay off until ground fault(s) are repaired. This will affect all MCC racks on that sub.

(Our 3 phase motors are grounded this way).

7
New cards

Determine the amount of fault current the HRG systems in your plant are designed to sustain. Determine the size of the resistor (in Ohm and Watts) required to deliver this fault current.


HRG = High Resistance Grounding

Our resistors are 5 amps.

R = V/I so, (live phase conductor to neutral wire = 277v) 277v/5a = 55.4 ohms

W = V times I so, W = 277v times 5 = 1,385 watts

8
New cards

Determine the theoretical system voltages you should see in a three phase HRG system when one phase of this system experiences a solid ground fault.

All phase to phase conductors will read 480v. (That is how motors continue to operate when there is a ground fault). The phase with the fault will read near zero when a phase to ground reading is taken.

9
New cards

Explain the impact of a "low grade" ground fault (i.e. - resistance >0 Ohms) on system voltages.

An intermittent ground fault that may come and go- phases may have various voltages (ok, one minute, then bad the next).

The phase that has the “low-grade” ground connection will have lower than 277 V (measured Phase to ground) and the other two

10
New cards

Explain how ground fault annunciation works in your department.

There may be lights in substation or meters to indicate ground fault.

PC&IS C-3 will inform the proper people.



11
New cards

Explain why a ground fault on one substation does not affect the other substations.

The fault doesn’t affect another substation because they are not physically connected due to physical break between the primary and secondary transformer winding. Separately derived system.

12
New cards

Identify some common locations for ground faults in your department.

Motor termination box of the motor (peckerhead)

Any immersed heaters (heat liquid)

Portable welders

Electric Brake

13
New cards

Explain the impact of a ground fault (if any) on a three phase motor connected to an HRG system.

No impact – All 3 phases continue to read 480 volts until another ground fault occurs

14
New cards

Explain why a ground fault must be traced out and repaired even though the plant can continue to run.

A 2nd fault on another phase of the same transformer is a phase to phase short and will cause the substation breaker to trip-MCC fuses blow, etc.

15
New cards

Name the 3 Main Components of AC Motor

Rotor, Stator, Bell Assembly (Frame)

16
New cards

Describe how to connect the 9 motor leads for two different voltages on AC Motor

480v - (T1, 1) (T2, 2) (T3, 3) (4&7 Together) (5&8 Together) (6&9 Together)

230v - (T1, 1&7 Together) (T2, 2&8 Together) (T3, 3&9 Together) (4&5&6 Together)

17
New cards

Explain what TEFC means

Totally Enclosed Fan Cooled

18
New cards

Explain When and why it is important to properly align the motor shafts

To eliminate vibration which will cause faster wear on the motor bearings/other components of the motor. A good way to tell of an improper aligned motor is by excessive noise and vibration

19
New cards

Name the Motor Attributes that must be the same when replacing an AC Motor with a different brand in a gearbox application

Frame Size, Shaft Size, and Length. Voltage. Others include Enclosure Type, Attachment style, Horsepower, Service Factor, Rotational Speed

20
New cards

Explain where, on a motor, ground faults occur the most frequently and why

On a motor the Peckerhead or terminal box is where the most ground faults occur. This is due to moisture, aging, the vibration from the motor, or people putting in poor or broken terminations

21
New cards

Describe the Labeling Requirements of an MCC and or MCP as it pertains to your site

Fed From

Name of Device

Voltage

Number of Phases

Frequency (Hz)

Flash Hazard Rating

PPE Requirements

SCCR (Manufacturer Applied)

Drawing #

22
New cards

NEC clearance Requirements for Power Distribution Equipment

30” Width or width of panel

42” Clearance out to a concrete wall or other grounded surface

48” If there is another MCC or equipment behind you

6’ To work on MCC

MCC bucket doors must open 90 degrees

23
New cards

Describe what Voltages are used for control and power for motor circuits

120V AC for control power, 480 for power to motor

24V DC for control power, 480 for power to motor

Trying to get away from 120V AC to 24V DC, converting all control power to 24V is our goal now when upgrading projects

24
New cards

Which components remain energized even after an MCC or MCP has been de-energized (Either at main or an individual bucket)

Control Wiring still energized, Watch out for bottom fed disconnects as those knives are still energized. If working on individual bucket, every other bucket is still energized, as well as the bus bar behind the bucket

25
New cards

Describe what safety precautions you must take when working in an MCP that differ from working in MCC

Since MCP was not built for individual motor control, there are still exposed and live conductors energized at 480 Volts

26
New cards

In an MCP with multiple motor starters, describe how you would safely work on a singular motor circuit

Wear appropriate PPE, as other motor starters could still be engaged/energized

Lock it Out

27
New cards

Explain how single line diagrams are connected to the site electrical safety program

  1. With up to date, correct, lines we can lock out the right equipment

  2. Provide the proper connecting info for upstream power distribution systems

  3. Determine the capacity and flash hazard of downstream equipment. Flash Hazard determines level of PPE

  4. Document the bus bracing for the MCC

  5. Let us know if equipment is overdutied or not

  6. Accuracy of these lines are audited for the electrical KEA


28
New cards

Explain the differences between class 1 and class 2 hazardous locations

Class 1 - Ignitable concentrations of flammable gases, vapors or liquids


Class 2 - Ignitable concentrations of Combustible Dusts

29
New cards

Class 1 Division 1 vs Class 1 Division 2

Div 1 - Ignitable concentrations of flammable gases, vapors, or liquids CAN exist all of the time or some of the time under normal operations


Div 2 - Ignitable concentrations of flammable gases, vapors, or liquids NOT likely to exist under normal operation

30
New cards

Identify Hazardous Locations in Department

HDL Process Tank Farm


LFE Tank Farm


Perfume Storage

31
New cards

Determine Rating of a device by observing the device nameplate

Devices should have labeling designating UL Hazard Classification

32
New cards

Explain what each symbol is in a Single Line for an MCC

Covered “Fed From”

Incoming Breaker (Frame and Trip)

Horizontal Bus Ampacity

Combination Starter Symbol (With frame, fuse size, starter size)

Extents of MCC

External Wiring

Wire Labeling

Field Disconnects

Motor HP

Transformer Size and Config

33
New cards

Describe the different voltages that you would encounter in these Lighting panels

480/277v AC, depending on the 480v transformer secondary feeding the panel

34
New cards

Locate a lighting panel, point out the components

Main disconnect is generally at the top or bottom of panel, larger than the other breakers in there

35
New cards

Describe which components remain energized in a panel after a breaker has been de - energized

All breakers besides the one that is de energized, incoming cables, Bus bar, All wiring not connected to de-energized breaker

36
New cards

Describe the different levels of PPE required to work on energized Panels

Class 0-4, refer to PCP 650 PPE Matrix

37
New cards

Explain the operation of the electrical safety door interlock with NEMA switch

Door switch prevents door from being accidently being opened and helps prevent exposing energized components. Use a flat head screwdriver to override the safety for trouble shooting

38
New cards

Explain why operating switches or indicating lamps should not be installed on a local disconnect

The holes in the panel degrade the structural integrity of the disconnect

39
New cards

White, Grey Wire

Grounded Conductor (Neutral)

40
New cards

Black Wire

Line or Load Wire AC or DC over 24V

41
New cards

Blue Wire

24V Control Power

42
New cards

Green/Bare Wire

Grounding Conductor

43
New cards

Yellow Wire

Fed From outside source

44
New cards

Red Wire

120v AC control power

45
New cards

Brown Orange Yellow Wires

480v AC, A,B,C phase

46
New cards

Red, Black, Blue

208v AC, A,B,C 3 Phase

47
New cards

Identify the instances under which temporary installation of wire is permitted

Only there for less than 90 days, and approved by the Electrical System Owner or ESO, Found in NEC 590

48
New cards

What does UPS stand for?

Uninterruptible Power Supply (Battery Back-Up)

49
New cards

Describe which loads are currently connected to your UPS

  • Rack Module Controls - DC modules to prevent a UL in motion from coming to an immediate stop (brake coil collapses) and so ACTIV will always know where inventory is.

    Data Center servers

    HDL Process TDC & PLC systems.


50
New cards

What is a Manual Transfer Switch?

Used to transfer power supply from an MCC to generator. Switch from "Normal" (MCC) to "Off" to "Aux" (generator). To use stop at off when switching. Do NOT switch under load. Not to be used as a disconnect. Arc flash could possibly energize other side of switch.

51
New cards

What is an Automatic Transfer Switch?

Automatically transfers power supply from an MCC to a generator. Does the transfer under load. Used in critical systems, such as distribution center or hospitals.

52
New cards

Explain how to correctly lock-out / tag out when an ATS is involved.

Lock out all possible sources of power, upstream and downstream. Remember that arc flash could energize either side.

53
New cards

Describe how equipment (MCC's / PDP's etc.) should be labeled if a generator is/can be connected

Caution: fed from two sources.

54
New cards

Explain the function of a Ground Fault Circuit Interrupter.

To detect current imbalance between hot & neutral and open the circuit.

55
New cards

Identify the current trip threshold for a GFCI designed for personnel protection.

5 mA

56
New cards

Describe the current trip threshold of a GFCI breaker for equipment protection. Explain what would happen if this device were installed to provide personnel protection.

30 mA

People could receive a potentially fatal shock without the GFCI tripping

57
New cards

Using a hand sketch of a GFCI circuit diagram, explain the theory of operation for a GFCI breaker or receptacle.

Hand sketch of two conductors with current transformer around BOTH phases.

If the same amount of current flowing to the load on the hot wire does NOT come back on the neutral, the GFCI will trip.

58
New cards

Explain how the test circuit in a GFCI works. Determine if a GFCI can be tested de-energized.

Test circuit drains a small amount of current (> 5 mA) from the circuit and trips the GFCI.

GFCI cannot be tested de-energized.

59
New cards

Identify the physical locations requiring a GFCI according to the National Electrical Code (include residential, commercial, and industrial settings).

Garages, Outdoors, Kitchens, Bathrooms, Hot Tubs, Pools, (anywhere within 10 ft of water source). Commercial and Industrial areas where portable cord-connected devices are used (except for office areas)

60
New cards

Identify the tasks requiring a GFCI according to NFPA 70E.

Testing of GFCI’s required by 70E.

Installation Requirements set by NEC.


Required In areas that have high risk of water, moisture, or earth ground contact

61
New cards

Explain why a GFCI will trip on a ground fault but not a short circuit.

Short circuit has all the current going to the load on the hot wire and returning from the load on the neutral – so NO current imbalance.

A ground fault lets current out of the normal circuit path – so Current Imbalance trips the unit.

62
New cards

Determine if any of your department substation breakers have Ground Fault protection. If so, explain the sensing mechanism for the ground fault and determine if this is for personnel or equipment protection.

No

63
New cards

Explain why a GFCI receptacle will function properly to provide personnel protection, even if a dedicated ground conductor is wired to the receptacle.

The ground wire is not in the sensing circuit. [Sensing circuit only uses the Hot & Neutral.] Doesn’t matter if ground is there or not for the GFCI to work.

64
New cards

Explain the testing requirements for a GFCI and why testing is important.

Test every month.

Legally required.

65
New cards

Explain what a Arc Fault Circuit Interrupter is and how it works.

Arc Fault interrupter senses the varying current spikes and trips based on a threshold set by the manufacturer.