Explain what a ground fault is
An unintentional electric path between source of current and grounded surface. They Occur when current is leaking somewhere, essentially electricity is escaping to ground
Explain all of the factors that determine the amount of ground fault current capable of being generated in the event of a fault.
Voltage, conductor size, integrity of connection, grounding scheme of the separately derived grounding system are the factors. Amount of resistance between the fault and the transformer. Size of transformer. Size of the conductors going to fault.
Explain the difference between an arc fault and a bolted fault
An arc fault is an intermittent air gap fault. Jumps through the air.
A bolted fault is a continuous connection across phases-(For example, a hand tool forgotten in MCC bucket that is bridged across conductor phases). Fault that goes through conductive material.
Explain the benefits and disadvantages of an ungrounded system. Indicate the locations in your department where this type of system grounding is used.
Advantage - The first ground fault turns the system into a solidly grounded system.
Disadvantage – Hazardous, unstable voltages, dangerous
No ungrounded in this facility
Explain the benefits and disadvantages of a solidy grounded system. Indicate the locations in your department where this type of system grounding is used.
Solidly Grounded
Advantage – Finding faults is easy, stable voltages.
Disadvantage – High ground fault currents can potentially damage equipment.
(Our lighting transformers are grounded this way).
Lighting panel, power panel, phase to neutral loads.
Explain the benefits and disadvantages of a high resistance grounded system. Indicate the locations in your department where this type of system grounding is used.
High-Resistance
Advantage – Can continue to run equipment with existing ground fault.
Disadvantage – Everyone that works on it must be trained and qualified.
(2nd fault on that substation transformer will trip substation breaker, and will stay off until ground fault(s) are repaired. This will affect all MCC racks on that sub.
(Our 3 phase motors are grounded this way).
Determine the amount of fault current the HRG systems in your plant are designed to sustain. Determine the size of the resistor (in Ohm and Watts) required to deliver this fault current.
HRG = High Resistance Grounding
Our resistors are 5 amps.
R = V/I so, (live phase conductor to neutral wire = 277v) 277v/5a = 55.4 ohms
W = V times I so, W = 277v times 5 = 1,385 watts
Determine the theoretical system voltages you should see in a three phase HRG system when one phase of this system experiences a solid ground fault.
All phase to phase conductors will read 480v. (That is how motors continue to operate when there is a ground fault). The phase with the fault will read near zero when a phase to ground reading is taken.
Explain the impact of a "low grade" ground fault (i.e. - resistance >0 Ohms) on system voltages.
An intermittent ground fault that may come and go- phases may have various voltages (ok, one minute, then bad the next).
The phase that has the “low-grade” ground connection will have lower than 277 V (measured Phase to ground) and the other two
Explain how ground fault annunciation works in your department.
There may be lights in substation or meters to indicate ground fault.
PC&IS C-3 will inform the proper people.
Explain why a ground fault on one substation does not affect the other substations.
The fault doesn’t affect another substation because they are not physically connected due to physical break between the primary and secondary transformer winding. Separately derived system.
Identify some common locations for ground faults in your department.
Motor termination box of the motor (peckerhead)
Any immersed heaters (heat liquid)
Portable welders
Electric Brake
Explain the impact of a ground fault (if any) on a three phase motor connected to an HRG system.
No impact – All 3 phases continue to read 480 volts until another ground fault occurs
Explain why a ground fault must be traced out and repaired even though the plant can continue to run.
A 2nd fault on another phase of the same transformer is a phase to phase short and will cause the substation breaker to trip-MCC fuses blow, etc.
Name the 3 Main Components of AC Motor
Rotor, Stator, Bell Assembly (Frame)
Describe how to connect the 9 motor leads for two different voltages on AC Motor
480v - (T1, 1) (T2, 2) (T3, 3) (4&7 Together) (5&8 Together) (6&9 Together)
230v - (T1, 1&7 Together) (T2, 2&8 Together) (T3, 3&9 Together) (4&5&6 Together)
Explain what TEFC means
Totally Enclosed Fan Cooled
Explain When and why it is important to properly align the motor shafts
To eliminate vibration which will cause faster wear on the motor bearings/other components of the motor. A good way to tell of an improper aligned motor is by excessive noise and vibration
Name the Motor Attributes that must be the same when replacing an AC Motor with a different brand in a gearbox application
Frame Size, Shaft Size, and Length. Voltage. Others include Enclosure Type, Attachment style, Horsepower, Service Factor, Rotational Speed
Explain where, on a motor, ground faults occur the most frequently and why
On a motor the Peckerhead or terminal box is where the most ground faults occur. This is due to moisture, aging, the vibration from the motor, or people putting in poor or broken terminations
Describe the Labeling Requirements of an MCC and or MCP as it pertains to your site
Fed From
Name of Device
Voltage
Number of Phases
Frequency (Hz)
Flash Hazard Rating
PPE Requirements
SCCR (Manufacturer Applied)
Drawing #
NEC clearance Requirements for Power Distribution Equipment
30” Width or width of panel
42” Clearance out to a concrete wall or other grounded surface
48” If there is another MCC or equipment behind you
6’ To work on MCC
MCC bucket doors must open 90 degrees
Describe what Voltages are used for control and power for motor circuits
120V AC for control power, 480 for power to motor
24V DC for control power, 480 for power to motor
Trying to get away from 120V AC to 24V DC, converting all control power to 24V is our goal now when upgrading projects
Which components remain energized even after an MCC or MCP has been de-energized (Either at main or an individual bucket)
Control Wiring still energized, Watch out for bottom fed disconnects as those knives are still energized. If working on individual bucket, every other bucket is still energized, as well as the bus bar behind the bucket
Describe what safety precautions you must take when working in an MCP that differ from working in MCC
Since MCP was not built for individual motor control, there are still exposed and live conductors energized at 480 Volts
In an MCP with multiple motor starters, describe how you would safely work on a singular motor circuit
Wear appropriate PPE, as other motor starters could still be engaged/energized
Lock it Out
Explain how single line diagrams are connected to the site electrical safety program
With up to date, correct, lines we can lock out the right equipment
Provide the proper connecting info for upstream power distribution systems
Determine the capacity and flash hazard of downstream equipment. Flash Hazard determines level of PPE
Document the bus bracing for the MCC
Let us know if equipment is overdutied or not
Accuracy of these lines are audited for the electrical KEA
Explain the differences between class 1 and class 2 hazardous locations
Class 1 - Ignitable concentrations of flammable gases, vapors or liquids
Class 2 - Ignitable concentrations of Combustible Dusts
Class 1 Division 1 vs Class 1 Division 2
Div 1 - Ignitable concentrations of flammable gases, vapors, or liquids CAN exist all of the time or some of the time under normal operations
Div 2 - Ignitable concentrations of flammable gases, vapors, or liquids NOT likely to exist under normal operation
Identify Hazardous Locations in Department
HDL Process Tank Farm
LFE Tank Farm
Perfume Storage
Determine Rating of a device by observing the device nameplate
Devices should have labeling designating UL Hazard Classification
Explain what each symbol is in a Single Line for an MCC
Covered “Fed From”
Incoming Breaker (Frame and Trip)
Horizontal Bus Ampacity
Combination Starter Symbol (With frame, fuse size, starter size)
Extents of MCC
External Wiring
Wire Labeling
Field Disconnects
Motor HP
Transformer Size and Config
Describe the different voltages that you would encounter in these Lighting panels
480/277v AC, depending on the 480v transformer secondary feeding the panel
Locate a lighting panel, point out the components
Main disconnect is generally at the top or bottom of panel, larger than the other breakers in there
Describe which components remain energized in a panel after a breaker has been de - energized
All breakers besides the one that is de energized, incoming cables, Bus bar, All wiring not connected to de-energized breaker
Describe the different levels of PPE required to work on energized Panels
Class 0-4, refer to PCP 650 PPE Matrix
Explain the operation of the electrical safety door interlock with NEMA switch
Door switch prevents door from being accidently being opened and helps prevent exposing energized components. Use a flat head screwdriver to override the safety for trouble shooting
Explain why operating switches or indicating lamps should not be installed on a local disconnect
The holes in the panel degrade the structural integrity of the disconnect
White, Grey Wire
Grounded Conductor (Neutral)
Black Wire
Line or Load Wire AC or DC over 24V
Blue Wire
24V Control Power
Green/Bare Wire
Grounding Conductor
Yellow Wire
Fed From outside source
Red Wire
120v AC control power
Brown Orange Yellow Wires
480v AC, A,B,C phase
Red, Black, Blue
208v AC, A,B,C 3 Phase
Identify the instances under which temporary installation of wire is permitted
Only there for less than 90 days, and approved by the Electrical System Owner or ESO, Found in NEC 590
What does UPS stand for?
Uninterruptible Power Supply (Battery Back-Up)
Describe which loads are currently connected to your UPS
Rack Module Controls - DC modules to prevent a UL in motion from coming to an immediate stop (brake coil collapses) and so ACTIV will always know where inventory is.
Data Center servers
HDL Process TDC & PLC systems.
What is a Manual Transfer Switch?
Used to transfer power supply from an MCC to generator. Switch from "Normal" (MCC) to "Off" to "Aux" (generator). To use stop at off when switching. Do NOT switch under load. Not to be used as a disconnect. Arc flash could possibly energize other side of switch.
What is an Automatic Transfer Switch?
Automatically transfers power supply from an MCC to a generator. Does the transfer under load. Used in critical systems, such as distribution center or hospitals.
Explain how to correctly lock-out / tag out when an ATS is involved.
Lock out all possible sources of power, upstream and downstream. Remember that arc flash could energize either side.
Describe how equipment (MCC's / PDP's etc.) should be labeled if a generator is/can be connected
Caution: fed from two sources.
Explain the function of a Ground Fault Circuit Interrupter.
To detect current imbalance between hot & neutral and open the circuit.
Identify the current trip threshold for a GFCI designed for personnel protection.
5 mA
Describe the current trip threshold of a GFCI breaker for equipment protection. Explain what would happen if this device were installed to provide personnel protection.
30 mA
People could receive a potentially fatal shock without the GFCI tripping
Using a hand sketch of a GFCI circuit diagram, explain the theory of operation for a GFCI breaker or receptacle.
Hand sketch of two conductors with current transformer around BOTH phases.
If the same amount of current flowing to the load on the hot wire does NOT come back on the neutral, the GFCI will trip.
Explain how the test circuit in a GFCI works. Determine if a GFCI can be tested de-energized.
Test circuit drains a small amount of current (> 5 mA) from the circuit and trips the GFCI.
GFCI cannot be tested de-energized.
Identify the physical locations requiring a GFCI according to the National Electrical Code (include residential, commercial, and industrial settings).
Garages, Outdoors, Kitchens, Bathrooms, Hot Tubs, Pools, (anywhere within 10 ft of water source). Commercial and Industrial areas where portable cord-connected devices are used (except for office areas)
Identify the tasks requiring a GFCI according to NFPA 70E.
Testing of GFCI’s required by 70E.
Installation Requirements set by NEC.
Required In areas that have high risk of water, moisture, or earth ground contact
Explain why a GFCI will trip on a ground fault but not a short circuit.
Short circuit has all the current going to the load on the hot wire and returning from the load on the neutral – so NO current imbalance.
A ground fault lets current out of the normal circuit path – so Current Imbalance trips the unit.
Determine if any of your department substation breakers have Ground Fault protection. If so, explain the sensing mechanism for the ground fault and determine if this is for personnel or equipment protection.
No
Explain why a GFCI receptacle will function properly to provide personnel protection, even if a dedicated ground conductor is wired to the receptacle.
The ground wire is not in the sensing circuit. [Sensing circuit only uses the Hot & Neutral.] Doesn’t matter if ground is there or not for the GFCI to work.
Explain the testing requirements for a GFCI and why testing is important.
Test every month.
Legally required.
Explain what a Arc Fault Circuit Interrupter is and how it works.
Arc Fault interrupter senses the varying current spikes and trips based on a threshold set by the manufacturer.