Branch Circuit
The wire run extending from the final overcurrent protective device to the outlet.
Feeder
Larger size conductors that supply electrical power from the distribution panel to a main panel or subpanel.
Branch Circuit Rating Determination
The rule that the ampere rating of the branch circuit overcurrent protective device (such as a circuit breaker), not the conductor size, determines the rating of the branch circuit.
NEC 210.18
The code rule establishing that if a conductor (e.g., rated for 20A) is protected by a smaller fuse or breaker (e.g., 15A), the circuit is classified according to the overcurrent device rating (15A).
NEC Table 240.6
The code table listing standard ampere ratings for overcurrent protective devices (fuses and inverse time circuit breakers), starting at 15A, 20A, 25A, 30A, 35A, 40A, 45A, and 50A.
Duplex Receptacle (NEC Article 100)
A multiple receptacle consisting of two contact devices sharing a single mounting strap or yoke, counted as two separate receptacles on the same yoke.
Round-Up Rule Restriction (NEC 240.4(B)(1))
The restriction prohibiting rounding up to the next higher standard overcurrent device rating on branch circuits that supply multiple receptacles.
14 AWG
The smallest copper conductor gauge permitted for inside branch wiring, rated for 15A in the 60∘C column.
NEC Table 310.16
The reference table used to determine the allowable ampacity of copper and aluminum conductors across different insulation temperature columns (60∘C, 75∘C, and 90∘C).
100-Ampere Terminal Rule
The requirement dictating that conductors for circuits rated at 100A or less must be sized based on the 60∘C temperature column rating regardless of higher insulation ratings.
Next Higher Standard Rating Rule
The provision allowing an overcurrent protective device to be sized up to the next standard rating (e.g., from 55A up to 60A, or 65A up to 70A) when no standard device matches conductor ampacity, provided the actual load does not exceed the conductor ampacity.
Type NM Cable (NEC 334.10(A)(1))
Nonmetallic-sheathed cable manufactured with 90∘C insulated conductors that is limited to installation exclusively in dry locations.
THHN Insulation
Conductor insulation rated for 90∘C that is restricted strictly to dry locations and not permitted in wet locations.
NEC 334.80
The section permitting the 90∘C conductor rating to be used for adjustment and derating purposes, provided the final calculated ampacity does not exceed the ampacity listed in the 60∘C column.
NEC Table 310.15(C)(1) Adjustment Factor
The adjustment table requiring conductor ampacity to be derated to 70% when 7 to 9 current-carrying conductors are bundled together without maintained spacing.