1/102
Looks like no tags are added yet.
What is an HMI?
Human-Machine Interface (graphical representation of a system; make changes to system; error alerting; data trends)
Which of the following is also referred to as an HMI?
Operator interface
NFPA 70 Article 110.15 requires a 4-wire delta system to identify the high-leg (aka wild leg) by the color;
Orange
What is a PID control system?
Proportional, Integral, Derivative control system
(Proportional = current error value)
(Integral = accumulated error over time)
(Derivative = future, rate of change, predicts temp to prevent overshoot)
In a PID control system, which function prevents overshoot?
Derivative
Which adjustment is made to a PID control system to improve performance?
Tuning (adjusting parameters' gain) using trial and error or the Ziegler-Nichols Method
The Derivative response in a control system is proportional to;
the rate of change in the process variable
The Proportional response in a control system is proportional to;
the difference between the set point and the process variable
The Integral response in a control system is proportional to;
the sums of error over time
What is the term used to describe the delay between the change in a variable, and when the control system processes the change?
Deadtime
What is a disturbance in a controlled environment?
the change in the environment's steady state
What information is obtained from a P&ID document?
Valves, piping, and related control system component
What is the current output for a 50VA control transformer that produces 24 VAC?
2.08 amps (since VA = V x I and I = VA/V)
What is an isolation transformer?
a transformer with a 1:1 winding ratio, designed to reduce supply side harmonics and voltage spikes to the secondary
How are control transformers rated?
Volt-amp
Building prints follow line conventions and lettering prescribed by;
Standard Y14.2M (ANSI)
What would be reviewed when searching for a project's HVAC MasterFormat documentation?
Division 25
A project's BAS/DDC (Direct Digital Control) specs are identified in MasterFormat:
Division 25
Standard symbols used in electrical schematics are defined by;
NEMA ICS 19-2002
NFPA 70 lists requirements for communicating systems in;
Chapter 8
NFPA 70 includes EMS (emergency management systems) installation and operation in;
Article 750
NFPA 70 includes VFD (variable frequency drive) installation requirements in;
Article 430
What is a control strategy for changing the output of a controller in proportion to the rate of change in the control variable?
Derivative
The PI control strategy is a method of adjusting the system by;
an amount proportional to the error and the duration of the error
Which of the following is deadband?
Differential values between the end of one function or mode and the start of another
What is a print that illustrates the relationship between I/O, controllers, piping, and system equipment?
Piping and instrumentation diagram
A controller operates based on the principle of;
logic
NFPA 70 defines low voltage for circuits and equipment operating at less than;
50 volts
What is the selected value to be maintained by a DDC control system?
setpoint
The DDC component that responds to a controller's signal to regulate the flow of a fluid in an environmental system is called the;
actuator
Fluids that are controlled by DDC systems to transfer heat in environmental systems are referred to as a;
control agent
Offset is the difference between the value of the setpoint and the;
control point
What is the output signal of a sensing element that reports the results of a controller's action?
Feedback
A control method in which the controlled device acts in direct response to the amount of offset measured in the system is;
proportional control
When adding an additional start relay to an existing pump's control circuit, the technician should;
wire the relay's contacts in parallel with the existing start controls
When adding an additional control relay to a stop circuit in an existing pump control circuit, the technician should;
connect the relay's N.C. contacts in series with the existing stop controls
What is the name for a type of control system that includes microcomputers?
Electronic
In building automation systems, a variable is a(n);
value that can be measured
HVAC control transformers typically supply;
24 VAC
Generally, basic electric control systems include switches that are;
mechanical
Category 5 unshielded twisted pair includes;
Four twisted pairs of 24 gauge wire
The standard jack for Category 5 unshielded twisted pair is;
RJ-45
A high-speed, interference-immune communications method using the Transmission Control Protocol/Internet Protocol;
ethernet
Networks media includes;
twisted-pair cable
Network topologies that are daisy-chained include;
common bus
100BASE-TX UTP cabling includes;
protective jacket
A cable category that requires shielding;
CAT 7
Media Access Control addresses (MAC addresses) are expressed in;
hexadecimal notation
Network throughput is measured in;
bps (bits per second)
TIA-485 standard is categorized in the ISO model as;
physical layer
The TIA-485 applications guide identifies the star topology as;
not suggested
The typical network topology used with RS-485 is;
Common bus
When comparing RS-485 to RS-232;
RS-485 is more resistant to EM interference
Applications where an ethernet crossover cable is required, is when the network;
nodes are generally of the same type
Cables used to connect one type of network node to a different type of node are called;
patch cable
Ethernet standards include;
Layer 1 and 2
Medium access control is defined in the;
data link layer
The protocol concerned with routing data packets between networks is;
internet protocol
A device such as a computer or printer that has a unique address and is attached to a network;
Node
Ethernet is a local area network architecture that supports minimum data transfer rates of;
10 megabits per second
RS 232 is a;
3-wire standard, serial communications
A controller with embedded software with available features that can be activated by a technician is a(n);
configurable controller
The time that it takes for a controller to update all of its points is called;
scan speed
A simplified method for technicians to input instructions into digital controllers;
point table
A change in the controlled variable that exceeds the upper deadband value during system operation;
overshoot
A truth table is a breakdown of a logic statement by;
listing all possible conditional values and the produced output
A controller designed to manage a single type of HVAC equipment are defined by ASHRAE as a(n);
application-specific controller
Configuarable controllers are;
set-up with menu option
Building automation system controllers should be installed in accordance with local regulations and the standards of the;
National Fire Protection Association (NFPA)
Controllers that only transmit binary outputs signals;
Discrete
Optoisolation devices prevent communication problems with the use of;
photonics
A controller's analog output terminals are commonly designated as COM and;
AO
Addressing a controller's terminal requires the;
terminal's number
In digital systems, the binary number 0 is often labeled;
false
In a digital systems, the binary number 1 is often identified as;
true
A number system with a base of 16 is;
hexadecimal
Structured text is a language that is configured as;
maps
Block programming is a coding method that uses a library of;
functions
Ladder logic is a programming method that consists of two vertical rails and rungs of;
relay logic
A 7 or 8 bit alphanumerical code used to represent the basic alphabet plus numbers and the special symbols is;
American standard code for information interchange
A digital AND gate is a device with an output that is True when;
both of the gate's inputs are True
A digital OR gate;
can be compared to contacts wired in parallel
A pseudo point is;
virtual
Timed override is a control option that allows users to;
temporarily redefine a space as occupied
Optimum start is a control method which;
Supervises control settings based on the condition of a building
A sensor that detects the proximity of a magnetic field uses;
hall effect
A proximity sensor that detects conductive materials uses;
inductance
A sensor that detects either conductive or nonconductive substances uses;
capacitance
A sensor is a device that measures a controlled variable and communicates with a(n);
controller
A signal that changes the state of a controlled device;
output
A sensor that detects a proportional electrical signal;
Analog input
A negative temperature-coefficient temperature sensor;
thermistor
A sensor that produces an electrical signal proportional to temperature;
thermocouple
A thermistor is a temperature-sensitive;
resistor
A sensor that changes resistance with a corresponding change in pressure;
Transducer
A sensor that uses piezoelectric crystals measures;
pressure
Output signal that has a continuous range of values between minimum and maximum limits;
analog
The number of control value units that causes an actuator to move through its entire range is called the;
throttling range
A VFD adjusts the;
frequency of the voltage applied to the motor
A solid-state device that provides a proportional unidirectional current to a load in response to an analog signal is a/an;
SCR