1/44
Looks like no tags are added yet.
Type II technicians are certified to service
high-pressure and very high pressure equipment, excluding small appliances and motor vehicles
After the installation of a refrigeration system, the technician should first
pressure test the system using nitrogen
What maintenance task must always be done to recovery/recycle equipment?
change system's oil and filters
What type of leak detection device is used to pinpoint a leak?
soap bubbles
An open compressor that has sat for several months is most likely
to leak from the shaft seal
Two indications that a high pressure system has a leak are
oil traces on flared fittings and high superheat
The EPA requires that all comfort cooling systems with more than 50 lb of refrigerant be repaired whenthe annual leak rate exceeds
10%
The EPA requires that all commercial and industrial process refrigeration systems with more than 50 lbsof refrigerant be repaired when the annual leak rate exceeds
20 and 30%
Why is it likely for a recovery and recycle machine to overheat when drawing a deep vacuum?
because the refrigerant is needed to cool the compressor
What component is directly after the condenser on a system that uses a TXV typemetering device?
the receiver
Which refrigerant requires a separate set of gauges, a vacuum pump, and a recoverymachine when servicing?
R-134A
What methods help to reduce recovery time of a system?
pack ice around the recovery tank, heat the appliance, and recover liquid first
During a recovery, when should the refrigerant be removed from the condenser outlet?
when the condenser is below the receiver
When recovering refrigerant from a system that has a condenser on the roof and the evaporatoron the first floor, the recovery should begin from
the liquid line entering the evaporator
After removing refrigerant from a system, the refrigerant may
be reused in the same system or on another system owned by the same person
What must be done to an empty recovery cylinder before transferring refrigerant into the cylinder?
It must be evacuated
What is commonly used to aid in minimizing the release of refrigerant to the atmosphere?
low loss fittings, and hand valves on the hoses
When using recovery and recycling equipment manufactured after November 15, 1993, technicians must evacuate an appliance containing more than 200 lb of HCFC- 22 to what level before making a major repair?
10" Hg
When using recovery and recycling equipment manufactured before November 15, 1993, technicians must evacuate an appliance containing less than 200 lb of HCFC- 22 to what level before making a major repair?
0" psig
If a leak in an appliance makes the prescribed evacuation level unattainable, the appliance can beevacuated to
0 psig
Which of the following repairs are considered a major repair?
the replacement of a condenser coil
When servicing an open system, which of the following should be replaced?
a filter dryer
In a refrigeration system, high-pressure liquid exits
the condenser and receiver
When evacuating a system, it is required that the vacuum pump pull a minimum of
500 microns
A technician must never
operate a hermetic compressor under a deep vacuum
Non-condensables (air) causes
high head pressure
A technician must never
front seat the discharge service valve while the compressor is in operation
Defined by ASHRAE Standard 15, a sensor and alarm are required for A-1 refrigerants (R-12, R-22,R-11)
to sense oxygen depletion
A refrigeration system must always be protected by
a pressure relief device
To prevent freezing when charging R-12 into an evacuated system, it must be in the vapor form toraise the pressure up to
33 psig
The sale of CFC and HCFC refrigerants have been restricted to certified technicians since
November 14, 1994
Refrigerators built before 1950 often contain
SO2
When first inspecting a hermetic system known to be leaking, you should look for;
traces of oil
When refrigeration units use an open compressor. which part of the compressor is most likely to leak if a unit is notused for several months?
the rotating shaft seal
You can save time recovering the refrigerant from a system by removing as much as possible in the ____________ phase?
liquid
Your recovery/recycling machine has R-502 refrigerant in it. You now have to recover refrigerant from a unit with R-22. What much be done before the R-22 refrigerant can be recovered/recycled?
Recover as much of the R-502 from the recovery unit as possible, change filter, and evacuate
After reaching the required recovery vacuum on an appliance, you should
wait for as least a few minutes to see if the system pressure rises, indicating that there is still refrigerant in liquid formor in the oil
When using recovery and recycling equipment manufactured BEFORE November 15,1993, technicians must evacuate anappliance containing 10 pounds of CFC-500 to the following level before disposing of the appliance
4 inches of Hg vacuum
You are changing out the compressor of a system containing 40 pounds R-502. Your recycling equipment was manufactured AFTER November 15, 1993. In addition to isolating the compressor as much as possible, which of the following procedures should you follow?
Evacuate the isolated section of the system to 10 inches of vacuum and hold
Recovering refrigerant from a system in vapor phase will minimize loss of
oil
Which of the following statements is not true of recycling and recovery equipment manufactured AFTER November 15,1993?
It must meet vacuum standards more stringent than those met by equipment manufactured before November 15,1993
You are going to service a residential split system, providing comfort air-conditioning, you would expect to find what typeof refrigerant?
R-22
The state of the refrigerant leaving the receiver of a refrigeration system is
high pressure liquid
Which of the following is an indicator of a leak in a high pressure system?
Excessive superheat
An operating unit that has areceiver/storage tank requiresrefrigerant system service. Whenservicing the unit
refrigerant should be recovered in the receiver