On June 18, 1955, Republic Act No. 1378, otherwise known as the "Plumbing Law of the Philippines," was signed by President __________.
Ramon Magsaysay
In 1902, Master Plumber __________ became the first Chief of the Division of Plumbing Construction and Inspection in the City of Manila.
John F. Hass
The Revised Plumbing Code of 1999 was approved on December 21, 1999, by President __________.
Joseph Ejercito Estrada
All plumbing plans, drawings, specifications, and bills of materials must be submitted in __________ sets with each application for a permit.
six (6)
A plumbing permit becomes null and void if work is not commenced within one year from the date of the permit, or if work is suspended or abandoned for a period of __________ days.
120
The Administrative Authority requires that every request for inspection be filed at least __________ working days before the inspection is intended.
three (3)
A request for inspection of replacement equipment or fixtures must be filed with the Administrative Authority not more than __________ hours after replacement work is completed.
72
An unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet conveying potable water to the flood-level rim of any tank, vat, or fixture is known as an __________.
Air Gap, Water Distribution
A length of soil or waste stack corresponding in general to a story height, but in no case less than __________ meters, within which horizontal branches connect to the stack is a branch interval.
2.43
One fixture unit is defined as equivalent to a rate of flow of __________ liters per minute.
28.3
A structure is classified as combustible construction if any part of its structural framework will ignite and burn at a temperature of __________ or less.
756^\n\circ\text{C}
A soldered joint is obtained by joining metal parts with metallic mixtures or alloys that melt at a temperature below 427^\n\circ\text{C} and above __________.
149^\n\circ\text{C}
Brazed joints are made using alloys which melt at temperatures higher than __________ but lower than the melting temperature of the parts to be joined.
449^\n\circ\text{C}
Horizontal drainage pipes shall be run at a uniform slope of not less than __________ toward the point of disposal.
20mm/m or 2%
Vertical installation of double sanitary tees may be used only when the barrel of the fitting is at least __________ pipe sizes larger than the largest side inlet.
two (2)
When installed vertically, plastic pipe stacks must be supported at every __________ interval.
one- (1) meter
Excavation trenches must be backfilled in thin layers of __________ above the top of the pipe with clean earth.
0.3meter
Water closet bowls for public use must be of the __________ bowl type equipped with open-front seats.
elongated
No water closet or bidet shall be set closer than __________ from its center to any side wall or obstruction.
0.375meter
No urinal shall be set closer than __________ center to center to any similar fixture.
0.6meter
A finished shower receptor dam or threshold shall be not less than 51mm nor more than __________ in depth measured from the top of the dam to the drain.
228mm
All shower compartments, regardless of shape, must have a minimum finished interior area of __________ and be capable of encompassing a 762mm diameter circle.
0.6square meter
In the water test of a drainage and vent system tested in sections, each section must be filled with water to not less than a __________ head of water.
3-meter
In an air test of a drainage and vent system, air is forced into the pipe system until there is a uniform gauge pressure of __________ or sufficient to balance a column of mercury 254mm in height.
34.5kPa
Faucets and diverters must be connected to the distribution supplies such that the hot water supply is located at the __________ side of the combination fittings.
left
Where local water pressure is in excess of __________, an approved-type pressure regulator preceded by an adequately sized strainer must be installed.
551kPa
Each pressure relief valve on a water heating system shall be set at a pressure of not more than __________.
1034kPa
No building water service pipe shall be less than __________ in diameter.
19mm
Horizontal drainage piping must be provided with a cleanout at its upper terminal and at every __________ length or fraction thereof.
15meter
Cleanouts in drainage piping larger than 51mm must have a clearance of not less than __________ in front of the cleanout.
0.45m
The minimum diameter of any pump discharge or discharge pipe from a sump having a water closet connected thereto is __________.
50.8mm
Fixture outlets shall not be connected to horizontal excreta drainage piping within __________ of any vertical to horizontal change of direction of a stack containing suds-producing fixtures.
2.4meter
No water having a temperature above __________ shall be discharged under pressure directly into any part of a drainage system.
60∘C
Each vent opening through the roof shall terminate not less than __________ from, or at least 0.9meter above, any openable window, door opening, air intake, or vent shaft.
3meters
Each soil or waste stack extending __________ or more stories above the building drain must be served by a parallel vent stack connected with a yoke vent at every fifth floor level.
ten (10)
Each plumbing fixture trap, except those with special conditions, must have a water seal of not less than 51mm and not more than __________ deep.
102mm
The vertical distance between a fixture outlet and the trap weir must never allow the tailpiece to exceed __________ in length.
0.6meter
For sizing rainwater piping around Manila and its environs, a rainfall intensity of __________ per hour is normally used.
102mm
Dome-type strainers on roof drains must have a minimum total net inlet area of __________ times the area of the outlet pipe to which they connect.
one and one-half (1-1/2)
The maximum distance between manholes on a building sewer line shall not exceed __________.
91meters
Caulked joints in bell-and-spigot cast iron soil pipe must be filled with molten pig lead to a depth of not less than __________.
25.4mm