Total Heat Gains (QtotQ_{tot})

The total thermal load in a kitchen in kW, calculated as Qtot=Q1+Q2+Q3+Q4+Q5Q_{tot} = Q_1 + Q_2 + Q_3 + Q_4 + Q_5, representing the sum of heat gains from kitchen appliances (Q1Q_1), people (Q2Q_2), electrical lighting (Q3Q_3), solar heat through windows and walls (Q4Q_4), and outdoor air (Q5Q_5).

2
New cards

Simultaneous Coefficient (KSIMK_{SIM})

A reduction factor defined as the quotient of the number of appliances in use and the total number of appliances, used to scale heat gains from cooking appliances during peak load estimation.

3
New cards

Total Moisture Emission (WW)

The total moisture generation in a kitchen in kg/h\text{kg/h}, calculated as W=W1+W2+W3W = W_1 + W_2 + W_3, where W1W_1 is moisture from people, W2W_2 is moisture from unhooded kitchen appliances, and W3W_3 is moisture from outdoor air.

4
New cards

Exhaust Mass Flow Rate (MexM_{ex})

The total exhaust air mass flow rate in kg/h\text{kg/h}, determined by Mex=∑(Loiρi)+LgvρgvM_{ex} = \sum(L_{oi}\rho_i) + L_{gv}\rho_{gv}, summing the airflow from individual exhaust hoods or ventilated ceilings and the general exhaust ventilation from the upper zone.

5
New cards

Commercial Kitchen Air Balance Rule

The design requirement specifying that the total airflow exhausted from a kitchen must be at least 10%10\% higher than the airflow supplied directly to the kitchen.

6
New cards

Adjacent Spaces Mass Flow Rate (MadM_{ad})

The mass flow rate of transfer air drawn into the kitchen from adjacent spaces in kg/h\text{kg/h}, defined as Mad=LadρadM_{ad} = L_{ad}\rho_{ad}, where LadL_{ad} is the volume airflow rate and ρad\rho_{ad} is the air density.

7
New cards

Supply Mass Flow Rate (MsupM_{sup})

The mass flow rate of air mechanically supplied to the kitchen in kg/h\text{kg/h}, calculated from the air-balance equation as Msup=Mex−MadM_{sup} = M_{ex} - M_{ad}.

8
New cards

Process Line (ε\varepsilon)

The ratio representing the path of air state change in kJ/kg\text{kJ/kg}, defined as the quotient of total heat gains and total moisture emission: ε=3600QtotW\varepsilon = \frac{3600 Q_{tot}}{W}.

9
New cards

Typical Process Line (ε\varepsilon) Range

The typical value range of ε\varepsilon during maximum kitchen equipment operation, spanning from 5000 kJ/kg5000\,\text{kJ/kg} to 7000 kJ/kg7000\,\text{kJ/kg} (2150 Btu/lb2150\,\text{Btu/lb} to 3009 Btu/lb3009\,\text{Btu/lb}) depending on the catering enterprise type.

10
New cards

Occupied Zone Enthalpy (hozh_{oz})

The enthalpy of air within the occupied zone of the kitchen in kJ/kg\text{kJ/kg}, derived from the energy balance equation: hoz=3600Qtot+Msuphsup+MadhadMexh_{oz} = \frac{3600 Q_{tot} + M_{sup} h_{sup} + M_{ad} h_{ad}}{M_{ex}}.

11
New cards

Mixture Enthalpy (hmixh_{mix})

The enthalpy of the mixture of supply air and air entering from adjacent spaces in kJ/kg\text{kJ/kg}, defined as hmix=Msuphsup+MadhadMexh_{mix} = \frac{M_{sup} h_{sup} + M_{ad} h_{ad}}{M_{ex}}.

12
New cards

Supply Air Temperature Offset

The standard design parameter setting the supply air temperature typically 3∘C3^\circ\text{C} to 5∘C5^\circ\text{C} (5∘F5^\circ\text{F} to 9∘F9^\circ\text{F}) below the target indoor room air temperature.

13
New cards

Mollier Chart (Kitchen HVAC Application)

The psychrometric diagram utilized to find the supply air enthalpy (hsuph_{sup}) and plot the process line (ε\varepsilon) to locate final indoor air parameters at the intersection with the calculated indoor enthalpy.

14
New cards

Hospital and Cafeteria Simultaneous Coefficient

The recommended simultaneous coefficient (KSIMK_{SIM}) range of 0.50.5 to 0.70.7 used for hospital and cafeteria kitchens.

15
New cards

Hotel, School, Restaurant, and Industrial Simultaneous Coefficient

The recommended simultaneous coefficient (KSIMK_{SIM}) range of 0.60.6 to 0.80.8 applied to hotel, school, restaurant, and industrial kitchens.