1/24
Vocabulary practice flashcards covering ATEX directives, hazardous area classifications, explosion protection concepts, and intrinsic safety equipment.
ATEX
An abbreviation for "Atmosphères Explosibles," referring to European Union directives governing equipment and safety in explosive atmospheres.
ATEX 2014/34/EU
An EU directive covering equipment intended for use in explosive atmospheres, establishing manufacturer compliance responsibilities.
ATEX 1999/92/EC
An EU directive focused on worker protection, establishing employer duties to classify hazardous areas, conduct risk assessments, and select compliant equipment.
Hazardous Area
An area where flammable gas, vapour, mist, or combustible dust may be present in quantities sufficient to require special precautions for the construction, installation, and use of electrical apparatus.
Flashpoint
The lowest temperature at which a liquid gives off vapour in sufficient quantity to form an ignitable mixture with air (e.g., −43∘C for petrol, >55∘C for diesel).
Ignition Temperature
The minimum temperature required to cause combustion of a substance without an external spark or flame (e.g., 560∘C for hydrogen, 365∘C for ethanol).
Gas Groups
Classification of explosive gases based on ignition energy: Group I (Mining), Group IIA (Propane), Group IIB (Ethylene), and Group IIC (Hydrogen/Acetylene), where a higher letter indicates a lower required ignition energy.
Temperature Class
Equipment surface temperature ratings ranging from T1 (450∘C) down to T6 (85∘C), which equipment surfaces must not exceed to prevent ignition.
Zone 0
A gas or vapour hazardous area in which an explosive atmosphere is continuously present or present for long periods, requiring Category 1G equipment.
Zone 1
A gas or vapour hazardous area in which an explosive atmosphere is likely to occur in normal operation, requiring Category 2G or 1G equipment.
Zone 2
A gas or vapour hazardous area in which an explosive atmosphere is not likely to occur in normal operation, or only for short periods, requiring Category 3G, 2G, or 1G equipment.
Zone 20
A dust hazardous area in which an explosive dust cloud is continuously present, requiring Category 1D equipment.
Zone 21
A dust hazardous area in which an explosive dust cloud is likely to occur in normal operation, requiring Category 2D or 1D equipment.
Zone 22
A dust hazardous area in which an explosive dust cloud is not likely to occur in normal operation, or will exist only for short periods, requiring Category 3D, 2D, or 1D equipment.
110V CTE
A Centre Tapped to Earth power configuration (55V−0−55V) mandatory for most portable tools on construction sites to limit shock voltage to earth to 55V.
Ingress Protection (IP) Rating
A standard two-digit code (IPXY) where the first numeral X (0 to 6) indicates protection against ingress of solid objects/dust, and the second numeral Y (0 to 8) indicates protection against water.
Flameproof (Ex d / EExd)
An explosion protection concept where an enclosure contains internal explosions and cools escaping hot gases via engineered flamepath gaps to prevent external ignition.
Increased Safety (Ex e / EExe)
An explosion protection concept that prevents arcs, sparks, and excessive temperatures in normal use by providing extra insulation and increased creepage and clearance distances.
Intrinsic Safety (Ex i / EExi)
An explosion protection concept that restricts electrical and thermal energy under normal and fault conditions below the threshold capable of causing ignition (e.g., <0.02mJ for IIC).
Pressurization (Ex p)
An explosion protection concept that prevents external explosive atmospheres from entering an enclosure by continuously purging and maintaining an internal positive pressure with air or inert gas.
Encapsulation (Ex m)
An explosion protection concept in which spark- or heat-producing electrical components are completely encased in resin to prevent them from contacting an explosive atmosphere.
Dust Ignition Proof (Ex tD)
A protection method for combustible dust environments that utilizes a dust-tight enclosure and limits external surface temperature.
Simple Apparatus
Non-energy-storing electrical devices (e.g., thermocouples, switches, LEDs) that can be installed directly in a hazardous area when part of an intrinsically safe circuit.
Zener Barrier
A safe-area associated apparatus consisting of a fuse, current-limiting resistor, and zener diodes to earth that clamps voltage and limits current to hazardous area field devices.
IS Earth
A dedicated, high-integrity grounding connection with resistance of <1Ω to main earth, providing the low-impedance path necessary for zener diodes to safely clamp fault voltages.