Comprehensive vocabulary flashcards covering fire alarm systems, operational principles, device specifications, system categories, circuit supervision, installation standards, and routine maintenance protocols.

56 Terms

1
New cards

Normally Open Alarm Circuit

An early fire alarm circuit wiring detector contacts in parallel; closing any contact completes the circuit to sound the alarm, but a broken conductor disables all downstream devices without triggering a fault warning.

2
New cards

Normally Closed Alarm Circuit

An early fire alarm circuit wiring contacts in series to continuously energise a line relay; opening any contact drops out the relay to trigger sounders, but a short circuit prevents downstream call points from operating and an open circuit cannot be distinguished from a genuine fire alarm.

3
New cards

Conventional Fire Alarm System

A fire detection system wired as radial circuits into discrete zones with end-of-line supervisory resistors at the final devices, where the control panel indicates the collective zone in which an alarm or fault occurs rather than pinpointing an individual device.

4
New cards

End-of-Line (EOL) Resistor

A resistor (typically 6800 Ω6800\,\Omega) installed across the terminals of the final device on a conventional detection or sounder radial circuit to permit a continuous supervisory monitoring current for open-circuit and short-circuit fault detection.

5
New cards

Call Point Series Resistor

A series resistor (typically 470 Ω470\,\Omega to 680 Ω680\,\Omega) built into a manual call point that produces a partial short circuit of approximately 500 Ω500\,\Omega upon actuation, enabling the control panel to distinguish between an alarm condition and a dead short-circuit fault.

6
New cards

Addressable Fire Alarm System

A system where all automatic detectors and manual call points are wired on a supervised loop and identified by individual digital addresses (such as via a 7-position DIP switch addressing numbers 11 to 127127), allowing the panel to pinpoint the exact device and its programmed physical location.

7
New cards

Multiplexing in Addressable Systems

The digital communication technique where the central control panel sequentially interrogates each device with a brief signal lasting approximately 0.02 s0.02\,\text{s} to assess its individual operating condition over shared loop wiring.

8
New cards

Short-Circuit Isolator Module

A protective device connected along an addressable wiring loop that automatically isolates a faulted or short-circuited cable segment, allowing the healthy remainder of the loop to maintain two-way communication with the control panel.

9
New cards

Category M System

A purely manual fire alarm classification under I.S. 3218 with no subdivisions, relying solely on occupants discovering a fire and manually activating call points to initiate an alarm.

10
New cards

Category L1 System

An automatic fire detection system designed for the total protection of life, installed throughout all areas of the protected building.

11
New cards

Category L2 System

An automatic life safety detection system installed only in defined parts of a building, which incorporates the escape route coverage of either a Category L3 or Category L4 system augmented by detection in specified high-risk areas.

12
New cards

Category L3 System

An automatic life safety detection system installed specifically to protect escape routes and all rooms or spaces opening directly onto those escape routes.

13
New cards

Category L4 System

An automatic life safety detection system installed within escape routes only, permitted solely where structurally protected alternative escape routes are available and occupants are ambulant, wakeful, and trained.

14
New cards

Category P1 System

An automatic fire detection system intended for property protection and business continuity installed throughout the entirety of the protected premises.

15
New cards

Category P2 System

An automatic property protection fire detection system installed only in specified or defined high-risk areas of the building where fire probability or consequence is severe.

16
New cards

Break-Glass Manual Call Point

A manually operated initiating unit containing a spring-loaded switch held depressed by a frangible glass element; breaking the glass releases the switch contacts through an internal series resistor to trigger an alarm.

17
New cards

Manual Call Point Siting and Mounting Limits

Installation guidelines requiring manual call points to be situated on staircase floor landings, exit routes, and exits to open air, mounted at a height of 900 mm900\,\text{mm} to 1200 mm1200\,\text{mm} above floor level, such that travel distance to a unit does not exceed 30 m30\,\text{m}.

18
New cards

Optical (Photoelectric Light Scatter) Smoke Detector

A point detector operating on the light-scatter principle where an internal light sensor is shielded from an LED until smoke scatters light onto the sensor, lowering circuit resistance from standby (0.1 mA0.1\,\text{mA} current draw) to approximately 500 Ω500\,\Omega; best suited for slow, smouldering fires.

19
New cards

Ionisation Smoke Detector

A point detector containing twin chambers and a radioactive source that ionises air to support a monitoring current (0.03 mA0.03\,\text{mA}); smoke particles enter the chamber and attach to ions, reducing chamber current to signal an alarm; best suited for fast-burning flaming fires.

20
New cards

Fixed Temperature Heat Detector

A thermal detector utilizing a bimetallic strip or thermistor calibrated to close an alarm contact when an ambient set point (such as 60∘C60^\circ\text{C}, 65∘C65^\circ\text{C}, or 90∘C90^\circ\text{C}) is reached; suitable for smoky, dusty, or steamy environments such as kitchens and boiler rooms.

21
New cards

Rate of Rise Heat Detector

A thermal detector combining an exposed sensor and a thermally shielded reference sensor to detect rapid temperature increases, incorporating a fixed upper-temperature stop; ideal for drying rooms or laundries with wide ambient swings but not kitchens where sudden heat surges naturally occur.

22
New cards

Photoelectric Optical Beam (Line) Detector

A high-level line detector consisting of an optical transmitter and receiver spaced up to 40 m40\,\text{m} apart (or up to 25 m25\,\text{m} with a reflector unit) that triggers an alarm when smoke particles obscure or diffuse the light path across large open areas.

23
New cards

Pulsating Infra-Red Line Detector

An optical line detector spanning distances up to 100 m100\,\text{m} that emits a pulsed infrared beam; it triggers an alarm when flame flicker within 6 m6\,\text{m} on either side of the beam modulates the received signal at a frequency between 4 Hz4\,\text{Hz} and 15 Hz15\,\text{Hz}.

24
New cards

Aspirating Smoke Detection (ASD) System

A high-sensitivity detection system compliant with I.S. EN 54-20 that continuously draws air samples through a network of sampling tubes via a fan or pump into a central chamber using optical or ionisation sensors, where each sampling hole is treated as an individual point detector.

25
New cards

Ultraviolet (UV) and Infra-Red (IR) Flame Detectors

Radiation-sensitive optical detectors that respond directly to flame flicker: UV types sense wavelengths between 200 nm200\,\text{nm} and 270 nm270\,\text{nm} (unaffected by sunlight due to high-altitude ozone absorption), while IR types use flicker-frequency analysis or narrow emission bands to reject solar interference.

26
New cards

Smoke Detector Spacing on Flat Ceilings

Spacing criteria establishing an individual coverage radius of 7.5 m7.5\,\text{m} (112 m2112\,\text{m}^2 area), with practical simplified design limits of 100 m2100\,\text{m}^2 maximum coverage per detector, 5 m5\,\text{m} maximum distance to any wall, and 10 m10\,\text{m} maximum spacing between adjacent detectors.

27
New cards

Heat Detector Spacing on Flat Ceilings

Spacing criteria establishing an individual coverage radius of 5.3 m5.3\,\text{m} (56.3 m256.3\,\text{m}^2 area), with practical simplified design limits of 50 m250\,\text{m}^2 maximum coverage per detector, 3.5 m3.5\,\text{m} maximum distance to any wall, and 7 m7\,\text{m} maximum spacing between adjacent detectors.

28
New cards

Ceiling Depth Limits for Detector Sensing Elements

The vertical mounting depth beneath a ceiling or roof apex: heat detector sensing elements must be positioned between 25 mm25\,\text{mm} and 150 mm150\,\text{mm} below the surface, while smoke detector sensing elements must be positioned between 25 mm25\,\text{mm} and 600 mm600\,\text{mm} below.

29
New cards

Corridor Smoke Detector Spacing Limits

Installation guidelines for corridors less than 2 m2\,\text{m} wide permitting maximum detector spacing along the centreline to increase up to 15 m15\,\text{m} between detectors and 7.5 m7.5\,\text{m} to an end wall (noting that heat detectors are not recommended for escape corridors).

30
New cards

Ceiling Obstruction Rules for Detectors

Installation rules stating that ceiling downstands or beams with a depth exceeding 10%10\% of floor-to-ceiling height must be treated as walls, and detectors must maintain a minimum clearance of 500 mm500\,\text{mm} from any such obstruction.

31
New cards

Centrifugal Fire Alarm Bell

A modern polarised audible device consisting of a miniature D.C. motor driving a rotating striker through a reduction gearbox to strike an enamelled steel gong, consuming approximately 25 mA25\,\text{mA} to produce an audio output of roughly 90 dB90\,\text{dB}.

32
New cards

Electromagnetic Fire Alarm Bell

A traditional sounder where current energises a solenoid coil to magnetically pull a steel plunger against a strike dome, simultaneously opening a set of contacts to interrupt current and spring-return the plunger.

33
New cards

Fire Alarm Siren

A polarised audible device producing a high audio output between 100 dB100\,\text{dB} and 105 dB105\,\text{dB} while drawing a relatively low current of approximately 15 mA15\,\text{mA}, making it suited for noisy factories and industrial works.

34
New cards

Electronic Sounder

A solid-state polarised acoustic warning device consuming around 20 mA20\,\text{mA} to generate roughly 100 dB100\,\text{dB} of sound, configurable to emit continuous, intermittent, or warble (variable pitch) alarm patterns.

35
New cards

Reverse Polarity Sounder Supervision

A monitoring method where the control panel maintains a reverse DC voltage on the sounder circuit during normal standby; series diodes inside each sounder block current while allowing supervisory current through a 6800 Ω6800\,\Omega EOL resistor to detect open and short circuits.

36
New cards

General Alarm Audibility Requirement

The requirement that sounders produce a minimum sound level of either 65 dB65\,\text{dB} or 5 dB5\,\text{dB} above any persistent background noise exceeding 30 s30\,\text{s} (whichever is greater) across 500 Hz500\,\text{Hz} to 1000 Hz1000\,\text{Hz}, without exceeding a maximum level of 118 dB118\,\text{dB}.

37
New cards

Bedhead Audibility Requirement

The mandatory minimum sound pressure level of 75 dB75\,\text{dB} required at the bedhead with all intervening doors closed in premises where an audible alarm is designed to awaken sleeping occupants.

38
New cards

Door Acoustic Attenuation

The reduction in fire alarm sound intensity caused by building partitions, rated as a loss of at least 20 dB20\,\text{dB} through standard single doors and at least 30 dB30\,\text{dB} through solid fire-rated doors.

39
New cards

Sounder Circuit Redundancy Rules

Mandatory installation criteria requiring that a fire alarm system provide at least two sounders wired across at least two separate circuits, ensuring audible coverage remains operative if one circuit fails and that at least one sounder near the panel stays operational.

40
New cards

Standby Power Supply Battery Duration

Secondary power capacity requiring rechargeable cells (lead-acid or nickel-cadmium, minimum 4 year4\,\text{year} design life) to power the full alarm load for at least 30 minutes30\,\text{minutes} following a minimum standby period of 24 hours24\,\text{hours}.

41
New cards

Mains Electrical Supply for Fire Alarm Panels

A dedicated 230 V230\,\text{V}, 50 Hz50\,\text{Hz} AC supply connected via an exclusive switch-fuse with a red cover labelled 'FIRE ALARM: DO NOT SWITCH OFF', transformed and rectified to provide a safe operating DC voltage and maintain battery float charge.

42
New cards

Detection Zone Boundaries and Limits

A physical subdivision within a protected building restricted to a maximum floor area of 2000 m22000\,\text{m}^2, a maximum search distance of 30 m30\,\text{m}, and a single storey (unless the entire building floor area is ≤300 m2\le 300\,\text{m}^2).

43
New cards

Alarm Zone Criteria

An area bounded by fire-resisting construction configured so that occupants receive an unambiguous, uniform alert or evacuation warning without acoustic confusion from adjacent zones, coinciding with one or more detection zones.

44
New cards

Main Emergency Isolating Switch

A dedicated, clearly marked switch positioned at the fire brigade entrance that directly or remotely disconnects the entire electrical supply to an installation during a fire event.

45
New cards

Firefighter's Switch Requirements

A red-painted switch complying with I.S. EN 60669-2-6 or I.S. EN 60947-3, labelled 'Fireman's Switch' with clear ON and OFF positions and an anti-accidental-reset latch, mounted no higher than 2.75 m2.75\,\text{m} above standing level to isolate discharge lighting.

46
New cards

Wiring Penetration Fire Stopping (I.S. 10101 Clause 527.2)

The requirement that any opening remaining around cable or containment penetrations through fire-rated elements must be sealed internally and externally to match the element's rated fire resistance, backed by cable supports within 750 mm750\,\text{mm} to resist mechanical collapse.

47
New cards

Flammable Liquid Equipment Precaution (I.S. 10101 Clause 421.5)

The safety rule mandating containment precautions, such as a retention pit or ventilated fire-resistant chamber with sills, whenever electrical equipment in a single location contains flammable liquid in excess of 25 L25\,\text{L}.

48
New cards

Standard PH 30 vs Enhanced PH 120 Fire-Resistant Cables

Cable classifications under I.S. EN 50200 where Standard PH 30 provides 30 minutes30\,\text{minutes} of fire survival, whereas Enhanced PH 120 (meeting BS 8434-2) provides 120 minutes120\,\text{minutes}, mandatory in buildings over 30 m30\,\text{m} high, phased evacuation, or critical routes through occupied zones.

49
New cards

Fire Alarm Cable Segregation Rules

The requirement that fire alarm circuits be mechanically separated from other services using dedicated conduit/trunking, metallic sheathing (e.g., MICC), or an air spacing of at least 300 mm300\,\text{mm} along parallel runs (15 mm15\,\text{mm} at 90∘90^\circ crossovers).

50
New cards

Fire Alarm Cable Support Integrity

The installation rule requiring that all cable supports and fixings be non-combustible and capable of withstanding the same fire exposure as the cable, strictly prohibiting plastic clips, plastic ties, or plastic trunking as the sole means of support.

51
New cards

Fire Alarm Loop Route Physical Separation

The mandatory installation principle under I.S. 3218 requiring that the send and return legs of an addressable loop follow separate physical routes, strictly prohibiting four-core or multi-core cables from sharing both loop legs.

52
New cards

Fire Alarm Conductor Sizing and Colour Coding

Installation standards requiring conductors to have a cross-sectional area of at least 1 mm21\,\text{mm}^2 (except for data cables) and all system cables to feature a single, uniform distinguishing colour, with red or orange preferred.

53
New cards

Cable Reaction to Fire Rating (Class Dca-s2,d2,a2)

The mandatory cable performance standard under I.S. 10101 / EN 50575, specifying flame propagation and heat release (Dca\text{D}_{ca}), smoke production (s2s2), burning droplets (d2d2), and combustion gas acidity (a2a2).

54
New cards

Routine Testing Schedule: Daily and Weekly Checks

The maintenance protocol requiring daily checks that the panel indicates normal operation without unaddressed faults, followed by weekly operation of a different initiating device, verification of sounder operation, battery connection checks, and event log entries.

55
New cards

Routine Testing Schedule: Quarterly and Annual Checks

The maintenance protocol requiring quarterly logbook reviews, simulated panel faults, battery inspections, and structural alteration reviews, followed by annual in situ testing of every detector and physical inspection of all fittings and cable integrity.

56
New cards

Fire Alarm Control Panel Auxiliary Circuits

Ancillary control interfaces actuated by the alarm system upon confirmation of fire, including electromagnetic fire door releases, escape door lock releases, ventilation and damper shutdown, extinguishing system activation, and off-site monitoring transmission links.